Server Rack System
The server racks utilize a nine-fold profile frame structure. Both front and rear doors are mesh doors to meet the heat dissipation requirements of the main equipment. The front door is a single door, and the rear door is a double door. The data center originally had four 600*1000*2000 server racks. After expansion, this increased to eight racks. To maintain consistency and aesthetics, the four additional racks also use the 600*1000*2000 size. The racks are mainly composed of the following components: a welded (or spliced) nine-fold profile frame, mounting beams, perforated strips, a top cover, a bottom plate, front and rear doors, side doors, a front windshield, and a false panel. The image shows a rendering of the racks. The rack’s static load capacity is 1200kg, dimensions are 600*1000*2000, and usable space is 42U.

Frame
The cabinet frame is a monolithic structure welded from rolled nine-fold profiles. In situations where transport conditions are unsuitable (e.g., insufficient elevator height or inaccessible stairs), a modular structure can be used. Nine-fold profile material: 1.5mm thick high-quality cold-rolled SPCC steel plate. Surface treatment: degreasing, phosphating, electrostatic powder coating.
Square Hole Strip
The square hole strip is made of 2.0mm thick high-quality magnesium-aluminum-zinc coated sheet, which is aesthetically pleasing and anti-static. The mounting holes on the square hole strip have semi-circular position identification notches and ink-screened numerical markings, making equipment mounting and alignment easier.
Perforated Area
The front and rear doors of the perforated area are hexagonal mesh doors, with a door width of W and a height of H. The dimensions of the mesh perforated area on the door are shown in the figure. The distance from the mesh area to the edge in the door width (W) direction is less than 45mm, and the distance from the mesh area to the edge in the door height (H) direction is less than 20mm.


Wind deflectors
Wind deflectors are installed on the air intake side of the cabinet in front of the equipment mounting surface, on the top, bottom, left, and right sides, to prevent cold air from flowing out through other openings and gaps before entering the heat-generating equipment.

Dummy Panels
Dummy panels are used to cover the gaps between devices, preventing cold air from flowing out. The dummy panels used are made of metal with clips; the texture and color of the metal dummy panels match the surface of the server rack, making the entire rack look more harmonious. The dummy panels have clips, so no screws or tools are needed for installation; they can be installed manually.

Side door between racks
When racks are installed in parallel, a side door is added between every two racks to prevent the spread of smoke and fire between racks in case of fire, which could cause greater damage.