This refers to various types of high-reliability precision air conditioners designed for computer room environments to ensure that IT equipment operates under suitable temperature and humidity conditions.

Server Room Air Conditioning System

Calculation Basis for Precision Air Conditioning in the Server Room: Based on a power consumption of 4KW per server rack, a total of 4 server racks will consume 16KW of power. With a server room area of ​​20 square meters, the cooling capacity of the server room air conditioning is 18.8KW. Therefore, a 20KW precision air conditioner will be used for server room cooling.

Qt = Q1 + Q2

Qt: Total Cooling Capacity (KW)

Q1: Indoor Equipment Load (=Equipment Power × 0.8)

Q2: Ambient Heat Load (=0.14kW/m² × Server Room Area)