Toggle1. Cover / Document Information
– Document Title: Rack-Mounted Plug-In Air Conditioner Technical Design Solution
– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.
– Brand: KITOZER (Pioneer)
– Date: August 2026
– Version: V1.0
– Project Type: Technical design solution for Rack-Mounted Plug-In Air Conditioner
2. Table of Contents Structure
1. Company Introduction
2. Project Overview
3. User Requirement Analysis
4. Overall Design Description
5. Detailed System Design and Product Technical Parameters
6. Project Quotation and Configuration List
7. Core Solution Advantages
8. Technical Q&A
9. Construction Schedule Plan
10. Construction Organization Plan
11. After-Sales Service System
12. Operation and Maintenance Training Plan
13. Typical Project Cases
14. SEO Optimization System and Website Backend Configuration
15. Contact Information
3. Company Introduction
3.1 Company Development Overview
Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise dedicated to the computer room construction and intelligent protection field for more than two decades, integrating R&D, production, sales, engineering implementation and after-sales service. The company focuses on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has grown into a source manufacturer with core competitiveness in the domestic computer room construction field.
After more than twenty years of industry accumulation, the company has built a large-scale production and manufacturing base equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and professional testing laboratories, with an annual production capacity of hundreds of sets of shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields.
3.2 Core Business System
The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:
– Computer room EPC general contracting service: one-stop services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;
– Core equipment R&D and production: independently produces KITOZER brand series products, including shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization;
– Computer room environmental monitoring system: provides full-element monitoring solutions for temperature and humidity, water leakage, access control, video, fire protection, UPS and power distribution, realizing intelligent and unattended O&M;
– Shielding and security protection products: shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military and scientific research fields.
3.3 Brand and Qualification Honors
The core brand KITOZER (Pioneer) focuses on computer room equipment and shielding products, positioned as an “efficient, green, innovative and safe” solution provider. Products have passed multiple authoritative tests and comply with national and industry standards. The company holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and follows the ISO9001 quality management standard.
3.4 Core Competitive Advantages
1. Source production, controllable quality: own production base and professional processing equipment; core products independently produced with full-process quality control, providing more cost-effective solutions without intermediate links;
2. Customized design, matching needs: tailor-made solutions per site conditions, technical requirements, configuration and budget, with multiple design options provided free of charge;
3. Professional team, rich experience: a professional technical team of engineers and project managers with more than ten years of industry experience;
4. Quality after-sales, full guarantee: a 7×24 professional online service system with dedicated project follow-up from early coordination to later O&M.
4. Project Background and Objectives
4.1 Project Background
With the rapid development of the digital economy and AI industry, server density in data centers and computing rooms keeps rising — single-cabinet power climbing from the traditional 3-5 kW to 10 kW, 20 kW and beyond. Traditional room-level precision AC can no longer handle the local hot spots of high-density cabinets: low cooling efficiency, high energy consumption and disordered airflow are prominent. Meanwhile, distributed scenarios — edge computing sites, small integrated rooms, shielded rooms and outdoor cabinets — have growing demand for compact, easily installed, highly reliable cabinet-level cooling.
This solution provides a complete rack-mounted plug-in air conditioner solution covering product selection, system design, engineering implementation and after-sales O&M. Cabinet-level precise supply cooling solves high-density cabinet heat dissipation, lowers room PUE, improves data center stability and efficiency, and adapts to standard 19-inch and customized cabinets across industries.
4.2 Product Overview
The KITOZER rack-mounted plug-in air conditioner series is self-developed precision cooling equipment for cabinet-level needs: plug-in frame installation directly inside standard server cabinets without occupying additional room space; near-source cooling achieving “cool where the heat is” — greatly improving efficiency; the core cooling solution for new-generation high-density data centers, micro-module rooms and integrated cabinets.
4.3 Project Objectives
Cooling performance: cover 3-15 kW single-cabinet cooling per load; stable output at 10-40℃ ambient without obvious fade at high temperature; supply temperature control ±1℃ meeting server inlet requirements; eliminate local hot spots with uniform top-to-bottom inlet temperatures.
Installation adaptation: standard 19-inch plug-in design compatible with standard mounting holes; 3U/4U/6U heights deployed at top, middle or bottom; full front and side maintenance without removing equipment; customization for shielded, outdoor, container and explosion-proof cabinets.
Intelligent control: local keypad operation with real-time display; standard protocols for environment-monitoring and BMS integration; intelligent speed control for on-demand cooling; complete fault self-diagnosis with audible/visual, remote and SMS alarms.
Reliability and safety: industrial-grade core parts with MTBF ≥100,000 h for 7×24 operation; multi-level protections (overcurrent, over/undervoltage, overload, high/low pressure, anti-freeze); environmentally friendly refrigerant with zero ozone depletion; electrical safety per national codes.
Energy saving and O&M: EER ≥3.0 with excellent part-load efficiency; natural cooling mode at low ambient temperature; simple filter maintenance without specialists; strong parts commonality with ample spares and short repair time.
5. User Requirement Analysis
5.1 Cooling Performance Requirements
Cooling covering 3-15 kW single-cabinet loads per heat density; stable output at 10-40℃ ambient; supply temperature control ±1℃ per server inlet requirements; elimination of local hot spots with uniform top-to-bottom inlet temperatures avoiding overheating downtime.
5.2 Installation Adaptation Requirements
Standard 19-inch plug-in design compatible with standard cabinet mounting holes; 3U/4U/6U heights at top, middle or bottom; front/side maintenance without removing equipment for dense micro-module layouts; customization for shielded cabinets, outdoor integrated cabinets, container room cabinets and explosion-proof cabinets.
5.3 Intelligent Control Requirements
Local keypad operation with real-time temperature, humidity, status and alarm display; standard protocols integrating with environment-monitoring and BMS systems for remote centralized management; intelligent speed control adjusting fan speed and cooling output per real-time cabinet temperature; complete fault self-diagnosis with audible/visual, remote and SMS alarms.
5.4 Reliability and Safety Requirements
Industrial-grade core parts with MTBF ≥100,000 h for 7×24 operation; multi-level protections (overcurrent, overvoltage, undervoltage, overload, high/low pressure, anti-freeze); environmentally friendly refrigerant (zero ozone depletion) per green development; electrical design per national room electrical safety codes with leakage and grounding protection.
5.5 Energy Saving and O&M Requirements
EER ≥3.0 with excellent part-load efficiency; natural cooling mode switching automatically at low ambient temperature; simple maintenance with easily removable filters; strong parts commonality, ample spares and short repair time.
6. Design Principles and Applicable Standards
6.1 Applicable Standards
GB 50174-2017 (data center design), GB/T 2887-2011 (computer site general specification), YD/T 1821-2008 (communication station AC equipment requirements), GB 50462-2008 (room construction and acceptance), GB 40879-2021 (data center energy efficiency limits and grades), GB 50243-2016 (ventilation and AC construction acceptance), GB 50054-2011 (low-voltage distribution), plus site conditions and equipment requirements.
6.2 Design Principles
Reliability first: mature technology and components ensuring 7×24 continuous stable cooling.
High efficiency: near-source cooling reducing transmission loss; intelligent regulation improving energy efficiency and lowering PUE.
Standardization and compatibility: standard rack design compatible with mainstream 19-inch cabinets and environment-monitoring systems.
Scalability: reserved expansion space for later cabinet power upgrades.
Easy O&M: modular design with fast core-part replacement and simple maintenance.
Customization: special-scenario solutions for shielded rooms, outdoor cabinets and high altitude.
6.3 System Architecture
Five parts integrated inside the cabinet forming an independent cabinet-level cooling loop: refrigeration host unit (compressor, evaporator, condenser, throttling device — vapor-compression cycle producing cooling); supply air distribution unit (centrifugal fans, ducts, guide components — precise delivery to the server inlet side); intelligent control unit (controller, temperature sensors, display, communication module — operation control, monitoring, alarms, remote communication); power distribution and protection unit (breaker, fuse, leakage protection); filtration unit (G4/F5 filters keeping the server environment clean).
6.4 Refrigeration Working Principle
Vapor-compression cycle in four processes: compression — low-pressure low-temperature refrigerant vapor is drawn by the compressor and compressed into high-temperature high-pressure gas discharged to the condenser; condensation — the high-temperature high-pressure gas exchanges heat with room ambient air in the condenser, releasing heat and condensing into high-pressure liquid; throttling — the high-pressure liquid passes the throttling device, dropping pressure into a low-temperature low-pressure liquid-vapor mixture entering the evaporator; evaporation — the low-temperature low-pressure refrigerant absorbs heat from the cabinet return air in the evaporator, evaporating into vapor and cooling the air into cold supply delivered to the cabinet; the heat-absorbed refrigerant vapor is drawn again by the compressor for the next cycle. The equipment uses front-return/front-supply or side-supply airflow: cold air directly into the cabinet cold side, hot air from the cabinet rear back to the return side — a closed loop avoiding cold/hot mixing and greatly improving efficiency.
6.5 Airflow Organization Design
Near-source supply/return for standard cold/hot aisle layouts: top installation — cold air down into the front cold zone, hot air rising from the rear to the return side (top-down loop); bottom installation — cold air up into the front cold zone, hot air falling from the rear (bottom-up loop); middle installation — precise cooling of local high-heat-density zones in ultra-high or tiered cabinets. Cold air acts directly on server inlets with near-zero transmission loss — far more efficient than room-level AC, solving high-density heat dissipation.
7. System Architecture and Working Principle
7.1 Series Overview
KTZ-JK-03 (3 kW, 3U): rated cooling 3 kW (max 3.2 kW), EER 3.2; fully enclosed scroll DC variable-frequency compressor; R410A refrigerant (ODP 0, charge 0.8 kg); copper-tube aluminum-fin evaporator 2.8 m² and condenser 3.2 m² with hydrophilic treatment; electronic expansion valve with PID control; operating ambient 10-40℃; built-in receiver and oil separator. Supply: rated 600 m³/h (max 720), external static 30 Pa, rear-curved centrifugal DC brushless fan, 0-100% stepless, front horizontal supply, front return, G4 filter 380×180×20 mm, ≤48 dB(A). Electrical: 220V/50Hz single-phase ±15%, rated 0.94 kW / max 1.1 kW, 4.3/5 A, soft start, IP20, class B insulation, grounding ≤4 Ω, overload/overcurrent/over/undervoltage protections. Control: microcomputer controller, LCD Chinese menu, 16-30℃ range, ±0.5℃ accuracy, 0.1℃ resolution, 2 NTC sensors (±0.3℃), modes cooling/ventilation/auto, RS485 Modbus-RTU standard, alarms (high/low temperature, compressor/fan/sensor faults, filter clogging) via audible/visual and dry contacts, power-fail memory with auto recovery. Structure: 19-inch, 3U (133 mm), 482.6 mm wide, 600 mm deep, 28 kg net, cold-rolled steel RAL7035, full front maintenance, top/middle/bottom installation. Reliability: MTBF ≥100,000 h, MTTR ≤2 h, design life ≥10 years, 20-80% RH, -20℃ to 60℃ storage, GB/T 2423.10 vibration, GB/T 17626 EMC.
KTZ-JK-05 (5 kW, 4U): rated 5 kW (max 5.5), EER 3.3; scroll DC VFD compressor; R410A 1.2 kg; evaporator 4.2 m², condenser 4.8 m²; ambient 0-45℃. Supply 1000 m³/h (max 1200), static 45 Pa, EC fan, dual-side horizontal supply, front return, G4 std / F5 optional, 420×220×20 mm filter, ≤52 dB(A). Electrical: 220V single ±15%, 1.52/1.8 kW, 6.9/8.2 A, soft start, IP20, class B, leakage protection added. Control: 32-bit controller, LCD, ±0.5℃, humidity ±3% RH, 3 sensors, modes cooling/dehumidifying/ventilation/auto/sleep, RS485 + optional Ethernet/SNMP, group control up to 32 units, power-fail memory with delayed start. Structure: 4U (177 mm), 700 mm deep, 42 kg, 1.2 mm steel, full front maintenance with slide rails, built-in drip pan, optional drain pump. MTBF ≥120,000 h, built-in class C lightning protection.
KTZ-JK-08 (8 kW, 6U): rated 8 kW (max 8.8), EER 3.4; scroll DC VFD compressor; R410A 1.8 kg; double-row evaporator 6.5 m², condenser 7.2 m²; ambient -5℃ to 45℃; large receiver, molecular-sieve dryer, sight glass; capacity 20-100% stepless. Supply 1600 m³/h (max 1900), static 60 Pa, 2 EC fans, dual-side supply with adjustable guide vanes, large front return, G4 + F5 dual filtration, 450×250×25 mm, ≤55 dB (≤45 low speed). Electrical: 220V single ±20%, 2.35/2.8 kW, 10.7/12.7 A, soft start, IP20, class F, PF ≥0.95, THDi ≤5%, molded-case breaker + complete protections. Control: 32-bit ARM industrial controller, 7-inch color touchscreen, ±0.3℃, 30-80% RH ±3%, 4 sensors (return/supply T+H), modes cooling/dehumidifying/humidifying (opt.)/ventilation/auto/energy-saving/natural cooling; RS485 + Ethernet, Modbus-RTU/TCP + SNMP; 4G/WiFi/dry contacts/fire linkage expansion; alarms with web/SMS/email; group control up to 64 units with load sharing and rotation; logs exportable; natural cooling auto-switch with compressor stop. Structure: 6U (266 mm), 800 mm deep, 65 kg, 1.5 mm steel, full front maintenance with heavy slide rails, large drip pan with standard drain pump, rear waterproof glands. MTBF ≥150,000 h, MTTR ≤1.5 h, design life ≥12 years, 15-90% RH, class C lightning 8 kV, salt spray 48 h.
KTZ-JK-12 (12 kW, 6U): rated 12 kW (max 13.2), EER 3.5; dual DC VFD scroll compressors; R410A 2.6 kg; triple-row evaporator 9.8 m², condenser 11.2 m²; dual electronic expansion valves with independent PID; ambient -5℃ to 45℃; capacity 10-100% with compressor rotation. Supply 2400 m³/h (max 2800), static 80 Pa, 2 EC fans, dual-side supply, front + side three-face return, G4 + F5, 480×280×25 mm, ≤58 dB (≤48 low). Electrical: 380V/50Hz three-phase ±15%, 3.43/4.1 kW, 6.6/7.9 A, soft start, IP20, class F, PF ≥0.98, THDi ≤3%, molded-case breaker + phase-loss/sequence protection. Control: 32-bit ARM, 7-inch touchscreen, ±0.3℃, 30-80% RH ±3%, 6 sensors, modes incl. natural cooling and duty, RS485 + Ethernet, Modbus/SNMP/BACnet, 4G/dry contacts/fire linkage/third-party platforms, multi-level alarms with APP push, group control up to 128 units with master/standby, load sharing, rotation, 1+ year data storage with cloud sync, adaptive defrost. Structure: 6U, 900 mm deep, 92 kg, 1.5 mm steel, full front maintenance, large drip pan with standard pump, load-bearing rails ≥80 kg. MTBF ≥180,000 h, MTTR ≤1.5 h, design life ≥15 years, class C lightning 10 kV, salt spray 72 h.
KTZ-JK-15 (15 kW, 8U): rated 15 kW (max 16.5), EER 3.5; dual DC VFD scroll compressors; R410A 3.2 kg; four-row evaporator 12.5 m², condenser 14.2 m²; ambient -10℃ to 45℃; efficient oil return; 10-100% capacity. Supply 3000 m³/h (max 3500), static 100 Pa, 3 EC fans, three-side supply, front + dual-side return, G4 + F6, ≤60 dB (≤50 low). Electrical: 380V three-phase ±15%, 4.29/5.1 kW, 8.2/9.8 A, PF ≥0.98, full protections with phase protection. Control: 32-bit ARM high-end controller, 10-inch touchscreen, ±0.2℃, ±2% RH, 8 sensors for multi-point cabinet placement, Modbus/SNMP/BACnet/OPC UA, AI energy saving via load-learning optimization, group control up to 256 units, 3-year data storage. Structure: 8U (355 mm), 1000 mm deep, 125 kg, 2.0 mm steel, full front maintenance, ultra-heavy rails. MTBF ≥200,000 h, MTTR ≤1 h, design life ≥15 years, class B lightning 15 kV, salt spray 96 h.
7.2 Special Custom Models
Shielded type: electromagnetic shielding treatment with waveguide windows at air openings and power filters — shielding effectiveness per national B-class standards for classified rooms and shielded cabinets. High-temperature type: high-temperature compressor and condenser with ambient ceiling up to 60℃ — for outdoor cabinets, high-temperature workshops and desert areas. Low-temperature type: low-temperature start kit operating at -30℃ — for northern outdoor sites. Explosion-proof type: Exd II BT4 — for chemical, mining and flammable environments. Size customization: width, depth and height per non-standard cabinets.
7.3 Accessories and Integration
Return-air guide hoods and supply guide vane kits optimizing airflow; G4/F5 filters (G4 standard, F5/F6 optional); RS485 + Modbus communication module for environment-monitoring integration; Ethernet/SNMP module for Web remote monitoring; multi-point NTC temperature/humidity sensors; class C power surge protectors; built-in drain pumps (1.5 m head) for non-gravity drainage; standard rack mounting kits; group control (32-256 units) with load sharing, rotation and master/standby; 4G/WiFi/APP push; fire linkage.
8. Detailed Technical Design
8.1 Selection Design
Cooling capacity per cabinet IT total power at 1.2-1.5× margin: e.g. 6 kW cabinet → 8 kW model; larger for uneven density or high ambient; high-density cabinets with multiple units (e.g. 2 × 12 kW for 20 kW cabinets with one-standby redundancy); shielded/high-temperature/low-temperature/explosion-proof models per scenario.
8.2 Installation Position Design
6U+ large models at the cabinet top with top-down coverage; 3U/4U small models at middle or bottom for local hot-spot cooling; ultra-high cabinets with top + middle combination; standard 19-inch mounting without drilling or cutting — no damage to cabinet structure.
8.3 Airflow and Condensate Design
Near-source supply/return per cabinet cold/hot aisle layout; guide vanes adjustable for precise direction; condensate via built-in drip pan to gravity drainage or optional drain pump (1.5 m head) or evaporative disposal in low-humidity environments.
8.4 Control and Monitoring Design
RS485 Modbus-RTU standard; Ethernet/SNMP/BACnet/OPC UA for medium/high models; environment-monitoring and BMS integration; group control with load sharing/rotation/master-standby; Web/APP remote monitoring and alarms; power-fail memory with delayed start; natural cooling auto-switch; adaptive defrost; log storage and export.
8.5 Electrical and Safety Design
Single-phase 220V (3-8 kW) or three-phase 380V (12-15 kW) with soft start; molded-case breakers and complete protections (overload, overcurrent, leakage, over/undervoltage, phase-loss/sequence, high/low pressure, anti-freeze); class C/B lightning protection; grounding ≤4 Ω; R410A environmentally friendly refrigerant.
8.6 Commissioning Design
Pre-power checks; power-on and parameter setting; mode tests; cooling performance and temperature accuracy tests; alarm tests; environment-monitoring integration; 24-hour trial run; documentation and training.
9. Recommended Configuration and Preliminary Budget
9.1 Configuration Summary
Host equipment:
| No. | Product | Model | Cooling | Specification | Unit |
|---|---|---|---|---|---|
| 1 | Plug-in AC | KTZ-JK-03 | 3 kW | 3U, 220V single, front-return/front-supply | pc |
| 2 | Plug-in AC | KTZ-JK-05 | 5 kW | 4U, 220V single, dual-side supply | pc |
| 3 | Plug-in AC | KTZ-JK-08 | 8 kW | 6U, 220V single, dual-side supply | pc |
| 4 | Plug-in AC | KTZ-JK-12 | 12 kW | 6U, 380V three-phase, dual compressor | pc |
| 5 | Plug-in AC | KTZ-JK-15 | 15 kW | 8U, 380V three-phase, three-side supply | pc |
| 6 | Shielded plug-in AC | KTZ-JK-05P | 5 kW | 4U, shielding treatment, waveguide openings | pc |
| 7 | High-temperature plug-in AC | KTZ-JK-08GW | 8 kW | 6U, 60℃ ambient tolerance | pc |
Accessories: return-air guide hood; supply guide vane kit; G4 filters (2); F5 filters (2, optional); RS485+Modbus communication module; Ethernet/SNMP module; 3 multi-point NTC sensors; class C surge protector; built-in drain pump (1.5 m); standard rack mounting kit.
Engineering services: on-site survey; installation (rack fixing, electrical, piping, labeling); commissioning (power-on, parameters, performance, 24-h trial run); environment-monitoring integration; operation training (1 day).
Standard single-unit delivery example (KTZ-JK-08): host 18,600 + standard accessories 2,920 + standard services 4,500 = 26,020 CNY total.
9.2 Quotation Notes
The prices are tax-inclusive, excluding transport and off-site travel; batch purchases receive tiered discounts; custom models quoted per content. All prices are indicative and quoted in RMB (CNY) only — no foreign-currency conversion is provided. Warranty: 2 years whole unit, 3 years core parts (compressor, controller, fans); 7×24 hotline with 4-hour Pearl River Delta on-site response; quarterly free patrol during warranty; lifetime maintenance at cost.
10. Technical Specifications
10.1 System Performance Summary
| Item | Specification |
|---|---|
| Series | KTZ-JK-03/05/08/12/15 (3-15 kW) + shielded/high-temperature/low-temperature/explosion-proof |
| Cooling capacity | 3-15 kW (max 3.2-16.5 kW); EER ≥3.0-3.5 |
| Compressor | Fully enclosed scroll DC variable frequency (dual on 12/15 kW) |
| Refrigerant | R410A, ODP 0, environmentally friendly |
| Expansion valve | Electronic, PID control (dual independent on 12/15 kW) |
| Ambient range | 10-40℃ (3 kW); 0-45℃ (5/8/12 kW); -10℃ to 45℃ (15 kW); 60℃ (high-temperature) |
| Supply airflow | 600-3000 m³/h; static 30-100 Pa; EC fans, 0-100% stepless |
| Airflow | Front/side return; front/dual-side/three-side supply with adjustable vanes |
| Filtration | G4 standard (F5/F6 optional); clogging alarm |
| Temperature control | ±0.5℃ (3/5 kW); ±0.3℃ (8/12 kW); ±0.2℃ (15 kW) |
| Humidity | ±3% RH (5-12 kW); ±2% RH (15 kW); dehumidifying std, humidifying opt. |
| Power | 220V single (3-8 kW) / 380V three-phase (12-15 kW); soft start |
| Noise | ≤48-60 dB(A) rated; ≤45-50 dB(A) low speed |
| Protection | Overload/overcurrent/leakage/over-undervoltage/high-low pressure/anti-freeze/phase |
| Communication | RS485 Modbus-RTU std; Ethernet/SNMP/BACnet/OPC UA (medium/high) |
| Group control | 32-256 units, load sharing, rotation, master/standby |
| Natural cooling | Auto-switch at low ambient, compressor stop |
| MTBF / MTTR | ≥100,000-200,000 h / ≤1-2 h |
| Design life | 10-15 years |
| Warranty | 2 years whole unit, 3 years core parts |
10.2 Key Component Specifications
| Model | Key Parameters |
|---|---|
| KTZ-JK-03 | 3 kW, EER 3.2, 3U, 600 m³/h, ±0.5℃, ≤48 dB, 28 kg |
| KTZ-JK-05 | 5 kW, EER 3.3, 4U, 1000 m³/h, dual-side supply, ≤52 dB, 42 kg |
| KTZ-JK-08 | 8 kW, EER 3.4, 6U, 1600 m³/h, 7-in touchscreen, ±0.3℃, 65 kg |
| KTZ-JK-12 | 12 kW, EER 3.5, dual compressor, 6U, 2400 m³/h, BACnet, 92 kg |
| KTZ-JK-15 | 15 kW, EER 3.5, dual compressor, 8U, 3000 m³/h, AI energy saving, 125 kg |
| JK-05P shielded | 5 kW, waveguide openings, power filter, B-class shielding |
| JK-08GW high-temp | 8 kW, 60℃ ambient, remote monitoring |
| Communication module | RS485 Modbus-RTU / Ethernet SNMP |
| Sensors | NTC ±0.3℃, multi-point T/H |
| Drain pump | 1.5 m head, optional |
| Surge protector | Class C (220/380V) |
11. Key Advantages and Customer Value
11.1 Near-Source Cooling — Leading Efficiency
Traditional room-level AC delivers cold through ducts and floors with large losses and severe cold/hot mixing — actual efficiency below 60%. The plug-in AC installs directly in the cabinet with cold air reaching server inlets — near-zero loss, over 40% efficiency gain. With DC VFD compressors and EC fans, part-load efficiency advantages are greater — reducing room PUE by 0.2-0.4 and saving significant long-term electricity.
11.2 Rack Installation — Extreme Space Saving
Standard 19-inch plug-in structure occupying only cabinet U space — no additional floor space, no ducts or water piping. Compared with in-row AC, single-cabinet space occupation is reduced over 70% — ideal for space-tight micro-module rooms, integrated cabinets and edge sites; more server computing power in the same room area.
11.3 Precise Temperature Control — Equipment Stability
High-precision NTC sensors with a 32-bit intelligent controller achieve temperature control up to ±0.2℃ with uniform stable supply — avoiding server frequency throttling or downtime from temperature fluctuation. Multi-point monitoring captures local hot spots in real time, automatically adjusting cooling output — completely solving top-to-bottom temperature differences and local overheating for 7×24 stable IT operation.
11.4 Full Front Maintenance — Dense Deployment
All parts — compressor, fans, filters and control board — are serviceable from the front without side or rear maintenance space. Cabinets can be densely arranged, especially in closed cold-aisle micro-module scenarios — greatly improving space utilization and lowering daily O&M difficulty.
11.5 Intelligent Control — Convenient O&M
Standard RS485 with Ethernet/SNMP/BACnet on medium/high models seamlessly integrating with existing environment-monitoring and building automation systems; multi-unit group control with load sharing, rotation and master/standby extending equipment life; Web/APP remote monitoring and alarm push — no on-site presence required, greatly reducing O&M labor.
11.6 Industrial-Grade Quality — Reliable and Durable
Well-known industrial-grade core components; strict high/low temperature, vibration and EMC testing; MTBF up to 200,000 h; multi-level electrical and refrigeration protections handling voltage fluctuation and harsh conditions; every unit passes 48-hour continuous factory testing.
11.7 Flexible Customization — Full Scenario Adaptation
Shielded, high-temperature, low-temperature and explosion-proof models plus customized sizes, colors and functions — adapting to shielded rooms, outdoor cabinets, industrial sites, vehicles and mines.
11.8 Source-Factory Full-Process Service
20 years of room equipment experience; one-stop service from design, customization, production and installation to after-sales — no middlemen, better cost-performance, faster response.
12. Technical Q&A (50+ Items)
12.1 Basics
Q1: What is a rack-mounted plug-in air conditioner? How is it different from ordinary room AC?
A: It is precision cooling equipment installed directly inside standard 19-inch server cabinets — cabinet-level near-source cooling. Compared with room-level AC, it is compact, flexibly installed, with low cooling loss and high efficiency — specifically solving high-density cabinet local heat dissipation; room-level AC cools whole rooms but handles local hot spots poorly with higher energy.
Q2: Can it be installed in any standard cabinet?
A: Standard models fit all IEC 60297-compliant 19-inch server cabinets with matching U space, adequate power capacity and return-air space; shallow cabinets accept short-depth custom models; non-standard widths are customizable.
Q3: How is the cooling capacity selected?
A: Per cabinet IT total power at 1.2-1.5× margin: e.g. 6 kW cabinet → 8 kW model; larger for uneven density or high ambient; high-density cabinets may use multiple units.
Q4: Where is the best installation position?
A: 6U+ large models at the top with top-down coverage of the whole cabinet front; 3U/4U small models at middle or bottom for local hot spots; ultra-high cabinets use top + middle combinations.
Q5: Does it need a drain pipe? How is condensate handled?
A: Refrigeration produces condensate into the built-in drip pan — standard gravity drainage into the room drain system; optional built-in drain pump (1.5 m head) where gravity is impossible; low-humidity environments may use evaporative disposal without external piping.
Q6: Is it noisy? Will it disturb offices?
A: 48-60 dB(A) rated, down to 45 dB(A) at low speed — comparable to office cabinet AC; rooms are usually separate spaces; low-noise models or sound insulation available for open office areas.
Q7: How often are filters cleaned or replaced?
A: G4 initial filters — clean every 1-2 months, replace every 6-12 months; F5/F6 medium filters — clean every 3 months, replace every 12-18 months; adjust per room cleanliness; the clogging alarm reminds automatically.
Q8: Can it integrate with an existing environment-monitoring system?
A: Yes — RS485 with Modbus-RTU standard; Ethernet/SNMP/BACnet on medium/high models — seamless integration with most environment-monitoring and building automation systems; our technicians complete the joint commissioning.
Q9: Will it auto-restart after a power outage?
A: Yes — power-fail memory restores operation automatically on recovery; configurable delayed start avoids simultaneous multi-unit grid impact.
Q10: Does the refrigerant need periodic refilling?
A: No — the sealed system does not leak under normal use; only leak-finding and refilling after a leak fault; normally no refilling within 5-8 years.
12.2 Product and Performance
Q11: What are the models and capacities?
A: KTZ-JK-03 (3 kW, 3U), JK-05 (5 kW, 4U), JK-08 (8 kW, 6U), JK-12 (12 kW, 6U, dual compressor), JK-15 (15 kW, 8U, dual compressor) plus shielded (05P), high-temperature (08GW), low-temperature and explosion-proof models.
Q12: What is the EER, and why does it matter?
A: EER ≥3.0-3.5 (cooling output per input power) — higher means more cooling per watt; with VFD compressors and EC fans, part-load efficiency is excellent — lower electricity and PUE.
Q13: What is the temperature control accuracy?
A: ±0.5℃ (3/5 kW), ±0.3℃ (8/12 kW), ±0.2℃ (15 kW) with high-precision NTC sensors — meeting strict server inlet requirements.
Q14: What are the airflow configurations?
A: Front return with front supply (3 kW), dual-side supply (5/8 kW), front + side three-face return (12 kW), three-side supply (15 kW) — with adjustable guide vanes for precise direction.
Q15: What is natural cooling?
A: When the ambient temperature is below the set value, the compressor stops and fans alone ventilate — saving most energy in winter; automatic switching with intelligent judgment; adaptive defrost on 12 kW.
Q16: What are the protections?
A: Overload, overcurrent, leakage, over/undervoltage, high/low pressure, anti-freeze, filter clogging, fan/compressor/sensor faults, phase-loss/sequence (three-phase), drain faults — complete equipment and load safety.
Q17: What is the operating ambient range?
A: 10-40℃ (3 kW), 0-45℃ (5/8/12 kW), -10℃ to 45℃ (15 kW), up to 60℃ (high-temperature model), -30℃ start (low-temperature model).
Q18: What is the MTBF/MTTR and design life?
A: MTBF ≥100,000-200,000 h by model; MTTR ≤1-2 h via modular front maintenance; design life 10-15 years.
Q19: What group control is supported?
A: 32-256 units by model with load sharing, rotation, master/standby switching and coordinated scheduling — extending equipment life and ensuring redundancy.
Q20: What is the electrical requirement?
A: 220V single-phase (3-8 kW) or 380V three-phase (12-15 kW) with soft start; PF ≥0.95-0.98, THDi ≤3-5%; grounding ≤4 Ω; class C/B lightning protection.
12.3 Installation
Q21: Will installation damage the existing cabinet structure?
A: No — standard 19-inch rack mounting using the cabinet’s own mounting posts and screws — no drilling or cutting, no damage to the original structure or appearance.
Q22: What are the installation steps?
A: Position marking → rail installation and leveling (load-bearing) → equipment racking and fixing → electrical wiring (de-energized, per code) → drain connection (slope, sealed) → communication wiring (shielded, labeled) → pre-power checks (wiring, fixing, piping, insulation) → power-on and parameter setting → mode/performance/alarm tests → cleaning → 24-hour trial run.
Q23: Can the customer’s own staff install it?
A: Yes — with professional electricians and O&M staff following the installation manual; first commissioning recommended by factory technicians; batch projects include installation training.
Q24: What is the standard delivery period?
A: Single-site single-unit projects 7-10 working days; batch projects 15-30 working days: start 1, survey 1-2, confirmation 1, production 3-7, delivery 1-3, installation 1/unit, commissioning 0.5/unit, trial run 1, acceptance 0.5, training 0.5-1.
Q25: What are the electrical wiring requirements?
A: De-energized operation with “do not close” signs and supervision; correct live/neutral/earth connections, firm and insulated; sized cables; grounding ≤4 Ω; power and communication separated.
Q26: What are the condensate drainage requirements?
A: Gravity drain with proper slope and sealed joints; drain pump (1.5 m head) where gravity impossible; evaporative disposal in low-humidity environments.
Q27: What pre-power checks are required?
A: Verify wiring, fixing, piping and communication; insulation tests; no tools/debris; then energize per commissioning procedure.
Q28: What commissioning is performed?
A: Power-on, parameter setting, mode tests (cooling/ventilation/auto/natural cooling), cooling performance and temperature accuracy tests, alarm tests, environment-monitoring joint tests, 24-hour trial run with monitoring.
Q29: What acceptance items apply?
A: Equipment models/quantities/positions; installation firmness and levelness; wiring and grounding compliance; cooling effect and temperature accuracy; alarm and communication functions; documentation (certificates, test reports, as-built drawings).
Q30: What safety measures apply during installation?
A: Certified staff; safety disclosure; de-energized electrical work with tags and supervision; harnesses for high work; extinguishers, no open flame; daily power cut and cleanup; warning signs.
12.4 O&M
Q31: How often are filters cleaned?
A: G4 every 1-2 months (replace 6-12 months); F5/F6 every 3 months (replace 12-18 months); adjust per room cleanliness; the clogging alarm reminds automatically.
Q32: What daily maintenance is required?
A: View display parameters and alarms; check fan operation and noise; clean filters; check condensate drainage; quarterly professional patrol (parameters, cooling effect, electrical safety, filter cleaning, part tightening, dust removal, hazard finding) with a report.
Q33: What is the warranty and response?
A: 2-year whole-unit warranty, 3 years on core parts (compressor, controller, fans); 7×24 hotline with 1-hour remote response; 4-hour Pearl River Delta on-site, 8 hours in-province, 24 hours nationwide; urgent faults prioritized.
Q34: What spare parts are available?
A: A headquarter warehouse stocks all series parts; common parts delivered within 48 hours, special within 72; batch projects may reserve parts on site; all original with warranty.
Q35: How are alarms handled?
A: Identify the code and level (high/low temperature, compressor/fan/sensor faults, filter clogging, voltage, drainage); minor issues reset or clean; serious faults contact service — never disassemble.
Q36: How is the drain pump maintained?
A: Check pump operation and debris periodically; clean the drip pan; verify drainage during patrol; replace the pump if abnormal (front maintenance, no rack removal).
Q37: What records should be kept?
A: Daily operation logs, filter cleaning records, quarterly patrol reports, alarm logs and energy data — for trend analysis and early fault detection.
Q38: What training is provided?
A: 1-day training at acceptance (half theory + half practice): principles, operation, menu/parameter setting, filter removal/cleaning/installation, patrol methods, fault codes and simple handling, alarm reset and emergency operation — with assessment and manuals; free refresher.
Q39: How is the environment-monitoring integration maintained?
A: Verify communication status during patrol; check data upload and alarm push; firmware upgrades free for life; hardware upgrades (communication modules, fans, capacity) available.
Q40: What services continue after warranty?
A: Lifetime repair at cost-only parts and reasonable service fees; annual maintenance agreements (patrol, priority on-site, part discounts); free software upgrades; service supervision hotline with 24-hour reply and satisfaction tracking.
12.5 Special Scenarios
Q41: Can it be used in shielded rooms without breaking shielding?
A: Yes — the dedicated shielded model with waveguide windows and power filters meets national confidentiality standards, installable in shielded cabinets and rooms without degrading shielding performance.
Q42: Can it be installed in outdoor cabinets? Will it stop cooling in summer heat?
A: The high-temperature model operates stably at 60℃ ambient without obvious cooling fade — for outdoor communication and integrated cabinets; dust/water upgrades available.
Q43: What about low-temperature northern sites?
A: The low-temperature model with a start kit operates at -30℃; natural cooling mode saves energy in winter.
Q44: Can it be used in explosive environments?
A: The explosion-proof model (Exd II BT4) suits chemical, mining and flammable environments.
Q45: Can multiple units cool one cabinet?
A: Yes — e.g. 2 × 12 kW for 20 kW cabinets with one-standby redundancy; group control coordinates load sharing and rotation.
Q46: What about custom sizes?
A: Width, depth and height customized per non-standard cabinets; colors and logos customizable for brand consistency.
Q47: How does the system handle high-humidity rooms?
A: Dehumidifying mode standard; humidity control ±3% RH (5-12 kW) / ±2% RH (15 kW) preventing condensation, short circuits and corrosion.
Q48: How is energy saved in winter?
A: Natural cooling mode with compressor stop; duty mode maintaining base temperature; AI load-learning optimization (15 kW); VFD compressors and EC fans at part load.
Q49: What are the green credentials?
A: R410A with zero ozone depletion; high EER and natural cooling reducing energy; low noise; recyclable materials — supporting green data center and dual-carbon goals.
Q50: Why choose the KITOZER/Lain solution?
A: 20 years of room equipment experience, source-factory self-developed series with industrial-grade quality, near-source efficiency (PUE -0.2 to -0.4), full scenario customization, professional installation and complete after-sales — a reliable cabinet-level cooling solution.
12.6 Project Cases
Q51: What are the results in AI computing rooms?
A: An AI computing room with 86 × 12 kW units (top-mounted, DCIM-integrated) achieved uniform cabinet temperatures with no hot spots, PUE reduced from 1.6 to 1.28, over one million kWh saved annually, and 30% space utilization gain.
Q52: What about classified shielded rooms?
A: 24 × shielded units passed all shielding tests with precise temperature control and stable operation — highly recognized.
Q53: What about outdoor edge sites?
A: 120 × high-temperature units ran stably at 60℃ summer ambient with no downtime; remote centralized management reduced O&M cost 60%.
Q54: What about university research data centers?
A: 42 × 8 kW units deployed on demand in a micro-module room — tidy, efficient cooling with simple O&M, meeting research computing needs.
Q55: How is the solution scaled for batch projects?
A: Tiered batch pricing, standard production within 7 days, 48-hour on-site installation after arrival, quarterly patrols and on-site spare reserves — efficient batch delivery and support.
Q56: How is the total cost controlled?
A: Near-source efficiency and natural cooling cut electricity; rack installation saves space; front maintenance reduces labor; long life and industrial-grade parts lower replacement — optimal lifecycle cost.
Q57: How is the solution monitored remotely?
A: Web/APP via Ethernet/SNMP/4G — real-time status, alarms, parameter settings; environment-monitoring platform integration for unified management.
Q58: What happens on a fire alarm?
A: Fire linkage options shut down the unit on fire alarm per room logic, preventing airflow spread; units restart after confirmation.
Q59: How is service quality supervised?
A: Service supervision hotline with 24-hour reply; post-service customer evaluation tied to engineer performance; regular customer visits for continuous improvement.
Q60: How is the solution delivered end to end?
A: Free survey and three design options → source-factory production (standard 7 days) → standardized installation → commissioning with 24-hour trial run → training and documentation → 2/3-year warranty with quarterly patrol and lifetime support — one-stop service.
13. Construction Schedule
13.1 Overall Period
Single-site single-unit projects: 7-10 working days total; batch projects 15-30 working days per quantity and site distribution.
13.2 Detailed Schedule
| Stage | Work | Duration | Responsible | Deliverable |
|---|---|---|---|---|
| 1. Project start | Contract, project team, customer interface, requirements and milestones | 1 day | PM | Start document |
| 2. Survey | Cabinet dimensions, power, environment, drainage, communication interfaces; installation position confirmation | 1-2 days | Engineer | Survey report, drawings |
| 3. Confirmation | Final solution and configuration signed by the customer; production order | 1 day | PM + technical | Solution confirmation |
| 4. Production | Standard models produced, inspected, packed; custom per cycle | 3-7 days | Production + QC | Qualified products |
| 5. Delivery | Shipping, arrival notice, delivery confirmation | 1-3 days | Logistics | Dispatch note |
| 6. Incoming inspection | Joint unpacking (model, accessories, quantity, appearance) | 0.5 day | Engineer | Incoming acceptance |
| 7. Installation | Racking and fixing, electrical wiring, piping, communication, labels | 1 day/unit | Engineer + electrician | Installation records |
| 8. Commissioning | Power-on, parameter setting, performance/alarm tests, DCIM integration | 0.5 day/unit | Engineer | Commissioning records |
| 9. Trial run | 24-hour continuous run monitoring parameters and cooling effect | 1 day | Engineer | Trial-run records |
| 10. Acceptance | Joint acceptance, report signing, documentation and spares handover | 0.5 day | PM | Acceptance report, as-built docs |
| 11. Training | Operation, daily maintenance and common fault handling training | 0.5-1 day | Engineer | Training records, assessment |
13.3 Key Node Control
Final solution within 24 hours of survey; standard models ship within 7 days; installation within 48 hours of arrival; acceptance organized within 24 hours of commissioning completion.
14. Construction Organization and Quality/Safety Measures
14.1 Organization Structure
Project manager (1): overall progress, quality, safety, customer liaison. Technical lead (1): design, disclosure, commissioning guidance, problem solving. Construction engineers (2): installation, wiring, piping. QC/safety officer (1): quality inspection, safety supervision, civilized construction. After-sales contact (1): post-delivery liaison and service follow-up.
14.2 Pre-Construction Preparation
Technical: full disclosure of drawings, codes and solution; key/difficult points with special plans; commissioning tools and instruments prepared. Materials: equipment and accessories counted and verified (model, quantity, integrity); tools (drill, screwdrivers, wrenches, crimping pliers, multimeter, megger); auxiliaries (power/signal cables, conduits, ties, screws, sealant); PPE (helmets, insulating gloves, harnesses, extinguishers). Site: entry procedures completed; power, transport routes and temporary storage confirmed; work area cleared; warning signs.
14.3 Core Construction Processes
Position marking → rail installation (level, load-bearing) → equipment racking and fixing → electrical wiring (de-energized, per code) → drain connection (slope, sealed) → communication wiring (shielded, labeled) → pre-power checks (wiring, fixing, piping, insulation) → power-on, parameter setting, mode tests → performance tests (cooling effect, temperature accuracy, alarms) → cleaning → 24-hour trial run.
14.4 Quality Control
Construction strictly per national codes and drawings without unauthorized changes; each process inspected by QC before the next; all equipment/materials/accessories verified — unqualified prohibited; concealed works accepted and signed by the customer before covering; commissioning per procedure with detailed records; full completion acceptance at the end.
14.5 Safety Management
Certified staff per safety rules; safety disclosure before work; electrical work de-energized with “do not close” signs and supervision; harnesses for high work; extinguishers, no open flame; daily power cut and cleanup; full-time safety officer monitoring and correcting violations.
14.6 Civilized Construction and Contingency
Standard dress and badges; customer site rules observed; materials/tools neatly placed; noise control; waste removed — work finished, site clean; damage compensated. Contingency: equipment damaged in transit — photo evidence, replacement dispatch protecting the schedule; electrical fault — power off, investigate, resume; commissioning fault — repair on site or replace with standby; sudden outage — power off devices, restart after stable supply; injury — stop work, first aid, hospital if serious.
15. After-Sales Service
15.1 Warranty Commitment
2-year whole-unit free warranty from acceptance; 3 years on core parts (compressor, controller, fans); non-artificial, non-force-majeure faults repaired/replaced free with no travel fees; lifetime repair at cost-only parts and reasonable fees after warranty.
15.2 Response
7×24 hotline; 1-hour remote response; 4-hour Pearl River Delta on-site, 8 hours in-province, 24 hours nationwide (remote areas extended); urgent faults affecting room operation prioritized with engineers and parts.
15.3 Periodic Patrol
Free quarterly on-site patrol during warranty: running parameters, cooling effect, electrical safety, filter cleaning, part tightening, dust removal, hazard finding — with a formal report and maintenance advice; annual maintenance agreements after warranty (patrol, priority on-site, part discounts).
15.4 Spare Parts
Headquarter warehouse stocking all series parts; common parts within 48 hours, special within 72; on-site reserves for batch projects; all original with warranty.
15.5 Technical Upgrade
Lifetime free control software upgrades; hardware upgrades (communication modules, fans, capacity); preferential upgrade schemes for existing customers after product iteration.
15.6 Service Supervision
Supervision hotline with 24-hour reply; post-service customer evaluation tied to engineer performance; regular visits for continuous improvement.
16. Training Plan
16.1 Objectives and Audience
Objectives: enable customer O&M staff to master equipment operation, daily maintenance, common fault judgment and emergency handling — independent O&M for long-term stable operation.
Audience: room O&M staff, equipment managers and electricians — unlimited headcount.
16.2 Training Content
Theory: working principles and system composition; model parameters and performance; component functions; operating modes and control logic; safety rules; daily maintenance knowledge.
Practice: start/stop; display menu operation and parameter setting; filter removal/cleaning/installation; patrol content and methods; normal/abnormal status identification; fault code recognition and simple handling; alarm reset and emergency operation.
O&M management: maintenance cycles and content; record-keeping standards; fault reporting flow; emergency plans.
16.3 Methods and Assessment
On-site face-to-face training at acceptance (theory + hands-on); video and remote training; manuals and courseware delivered; free refresher for new staff. Standard 1 day (half theory, half practice), adjustable. Assessment by theory questions + practical operation — pass before independent operation; free retraining for failures.
16. Training Plan
16.1 Training Objectives and Audience
Training objectives: through systematic training, enable management personnel to fully understand the system structure, working principles and performance characteristics, master daily operation methods and inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation.
Training audience: management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and equipment knowledge.
16.2 Tiered Training Content System
Level 1: Basic operation training (1 day)
– Basic principles: system concepts, structure composition, performance indicators;
– Daily operation standards: correct operation of equipment, control and safety systems;
– Daily inspection contents: daily/weekly/monthly check items;
– Safety precautions: usage prohibitions and emergency handling procedures.
Level 2: Maintenance training (1 day)
– Detailed structure of each subsystem and working principles;
– Daily maintenance methods: cleaning, fastening checks, routine care;
– Common fault identification and simple handling;
– Emergency handling procedures for power failure, fire and equipment faults.
Level 3: Advanced management training (as needed)
– Performance influencing factors and how to avoid degradation;
– Upgrade and expansion knowledge and specification requirements;
– Relevant national standards interpretation.
16.3 Training Methods and Schedule
– Methods: combination of “theory explanation + on-site practice + Q&A interaction”;
– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable; a free repeat training session is provided for newly assigned personnel.
16.4 Training Assessment and Documentation Delivery
– Assessment: theory written test plus practical operation; training qualification certificates issued upon passing; supplementary training for those who fail;
– Documentation delivery: complete O&M documentation, including operation and maintenance manual, equipment manuals and certificates, completion drawings and hidden work records, test reports and after-sales service contact card, all bound into volumes.
17. Anonymous Typical Project Scenarios
All project scenarios below are anonymous, generalized examples provided for reference only. No real customer names, addresses or identifiable details are disclosed.
17.1 Internet Company AI Computing Room Project
Project overview. A new AI computing room with single-cabinet power up to 12 kW — traditional precision AC could not solve local hot spots, and PUE remained high.
Implementation. KTZ-JK-12 plug-in AC units, one per cabinet, top-mounted, integrated with the customer’s environment-monitoring system.
Project scale. 86 units deployed across two micro-module rooms.
Results. Uniform cabinet temperatures with no hot spots and stable server operation; room PUE reduced from 1.6 to 1.28, saving over one million kWh annually; space utilization improved 30%.
17.2 Classified Unit Shielded Room Project
Project overview. A classified room required cooling equipment that would not break shielding effectiveness while ensuring equipment heat dissipation.
Implementation. KTZ-JK-05P shielded plug-in AC units with waveguide air openings and power filtering — shielding effectiveness compliant.
Project scale. 24 units deployed.
Results. All shielding tests passed; precise temperature control with stable equipment operation — highly recognized by the customer.
17.3 Operator Edge Computing Site Project
Project overview. Dozens of outdoor edge sites across the city with high ambient temperatures, unattended operation and inconvenient maintenance.
Implementation. KTZ-JK-08GW high-temperature plug-in AC units with remote monitoring and alarms.
Project scale. 120 units deployed.
Results. Stable operation at 60℃ summer ambient with no downtime; remote centralized management reduced O&M cost by 60%.
18. SEO Optimization Section
All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.
18.1 Keyword System
– Core keywords: technical design solution, system configuration, technical parameters, construction and O&M services;
– High-conversion long-tail keywords: design solution, configuration list, technical parameters, construction plan, after-sales service;
– Industry traffic keywords: system architecture, applicable standards, technical Q&A, project cases;
– Brand keywords: KITOZER, Guangzhou Lain.
18.2 SEO Tag System
– Title tag: the article title — Guangzhou Lain KITOZER;
– Meta description: Guangzhou Lain professionally provides complete technical design solutions with detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant performance, third-party testing supported;
– H1 tag: the article title;
– H2 tags: system design and product parameters, construction organization plan, after-sales service and training, engineering cases.
18.3 Internal Link Anchor Text
– Core anchor text: technical design solution, system construction;
– Long-tail anchor text: configuration list, technical parameters, construction plan;
– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.
19. Official Contact Information
– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.
– Brand: KITOZER (Pioneer)
– Official Website: https://gdlain.com
– Tel: +86 139 2228 9957 (WeChat available), +86 185 2066 8845 (WeChat available)
– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China
For any inquiries about this technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific requirements.