Raised Access Flooring for Server Rooms: Height, Load and Cable Underfloor

The Floor Is a Plenum

Raised access flooring does two jobs: it creates a space under the floor for cables and conditioned air, and it provides a flat, level surface for server racks. Here’s how to specify it.

Key Specs

Parameter Standard High Load
Panel size 600×600mm 600×600mm
Height (underfloor) 300mm 450mm
Panel material Steel + anti-static tile Steel + anti-static tile
Load rating 500kg/m² 1000kg/m²
Ground resistance 10^6 – 10^9 ohm 10^6 – 10^9 ohm
Reference price $45/m² $75/m²

Cable Underfloor

The underfloor space carries power cables (left side), data cables (right side), and CRAC cold air. Use cable separators to keep power and data at least 150mm apart. Ground every panel to the floor stringers.

Installation Note

Racks sit on the raised floor. Anchor each rack through a floor panel into the subfloor with M16 expansion bolts. Don’t rely on the floor panel alone to carry a 1500kg rack – the panel must transfer load to the subfloor.

KITOZER / Guangzhou Laian Intelligent System Development Co., Ltd. – raised flooring, server room infrastructure. Call +86 13922289957 (WeChat) or +86 18520668845. WhatsApp +86 19068534140. Web: www.gdlain.com | www.lain.com.cn. Address: Chaotian Park, Zhongrun Industrial Zone, Shilou, Panyu, Guangzhou, China.