Oversize the AC and you waste money. Undersize it and servers overheat. Here’s the quick formula for sizing a server room cooling system.
The Formula
Total heat (kW) = IT load (kW) + lighting (0.02 kW/m²) + people (0.1 kW/person) + solar gain (window area × 0.15 kW/m²).
Worked Example
A 50m² server room with 5 racks at 4kW each = 20kW IT load. Add 1kW for lighting, 0.2kW for 2 people, 1kW for solar gain. Total: 22.2kW.
Selecting the AC
| Room Size | Typical IT Load | Recommended Unit | Price |
|---|---|---|---|
| <20m² | 5-8kW | KZ-CR5 (5kW precision) | $3,200 |
| 20-50m² | 10-20kW | KZ-CR12 (12kW precision) | $5,800 |
| 50-100m² | 20-40kW | KZ-CR25 (25kW precision) | $9,500 |
| 100m²+ | 40kW+ | Two KZ-CR25 (N+1) | $19,000 |
Why Precision AC?
Commercial room AC cycles on/off and controls temperature but not humidity. Precision air conditioners (KZ-CR series) hold temperature to ±1°C and humidity to ±5% RH, 24/7. They’re built for continuous duty.
KITOZER / Guangzhou Laian Intelligent System Development Co., Ltd. – precision cooling, server room AC. Call +86 13922289957 (WeChat) or +86 18520668845. WhatsApp +86 19068534140. Web: www.gdlain.com | www.lain.com.cn. Address: Chaotian Park, Zhongrun Industrial Zone, Shilou, Panyu, Guangzhou, China.