KITOZER
KITOZER

Sewage Treatment Plant Engineering Automation Monitoring System

Table of Contents

1. Cover / Document Information

– Document Title: Sewage Treatment Plant Engineering Automation Monitoring System Technical Design Solution

– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Date: August 2026

– Version: V1.0

– Project Type: Technical design solution for Sewage Treatment Plant Engineering Automation Monitoring System

2. Table of Contents Structure

1. Company Introduction

2. Project Overview

3. User Requirement Analysis

4. Overall Design Description

5. Detailed System Design and Product Technical Parameters

6. Project Quotation and Configuration List

7. Core Solution Advantages

8. Technical Q&A

9. Construction Schedule Plan

10. Construction Organization Plan

11. After-Sales Service System

12. Operation and Maintenance Training Plan

13. Typical Project Cases

14. SEO Optimization System and Website Backend Configuration

15. Contact Information

3. Company Introduction

3.1 Company Development Overview

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise dedicated to the computer room construction and intelligent protection field for more than two decades, integrating R&D, production, sales, engineering implementation and after-sales service. The company focuses on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has grown into a source manufacturer with core competitiveness in the domestic computer room construction field.

After more than twenty years of industry accumulation, the company has built a large-scale production and manufacturing base equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and professional testing laboratories, with an annual production capacity of hundreds of sets of shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields.

3.2 Core Business System

The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:

– Computer room EPC general contracting service: one-stop services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;

– Core equipment R&D and production: independently produces KITOZER brand series products, including shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization;

– Computer room environmental monitoring system: provides full-element monitoring solutions for temperature and humidity, water leakage, access control, video, fire protection, UPS and power distribution, realizing intelligent and unattended O&M;

– Shielding and security protection products: shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military and scientific research fields.

3.3 Brand and Qualification Honors

The core brand KITOZER (Pioneer) focuses on computer room equipment and shielding products, positioned as an “efficient, green, innovative and safe” solution provider. Products have passed multiple authoritative tests and comply with national and industry standards. The company holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and follows the ISO9001 quality management standard.

3.4 Core Competitive Advantages

1. Source production, controllable quality: own production base and professional processing equipment; core products independently produced with full-process quality control, providing more cost-effective solutions without intermediate links;

2. Customized design, matching needs: tailor-made solutions per site conditions, technical requirements, configuration and budget, with multiple design options provided free of charge;

3. Professional team, rich experience: a professional technical team of engineers and project managers with more than ten years of industry experience;

4. Quality after-sales, full guarantee: a 7×24 professional online service system with dedicated project follow-up from early coordination to later O&M.

4. Project Background and Objectives

4.1 Project Background

A sewage treatment plant phase-3 expansion requires a full automation monitoring system: sludge dewatering workshop PLC control, toxic-gas monitoring, HD security surveillance, central control room and platform, unified with phases 1-2. The plant’s wet, dusty, corrosive, EMI-heavy environment demands industrial-grade design, redundant networks, physical isolation of production and office networks, and reuse of existing surveillance equipment.

4.2 Project Objectives

Full-process automation of the dewatering workshop (concentration, conditioning/dosing, dewatering, discharge, deodorization) with interlock and alarm linkage; online H2S monitoring with three-level response; unified HD video surveillance with 30-day+ storage; central control room SCADA platform integrating phases 1-3; industrial network with ring redundancy and security isolation; UPS-backed uninterrupted operation; response <=1s, MTBF >=50,000h, availability >=99.9%.

4.3 Project Scope

Self-control system (PLC station, HMI, network, instruments), security surveillance (front-end cameras, NVR, center equipment, transmission), central control room (operator/engineer stations, data server, UPS, switches, industrial gateway), software (PLC programming, SCADA, office), plus migration/reuse of existing monitoring equipment.

4.4 Significance

Raises production automation, safety and management; protects personnel from toxic gas; reduces energy, labor and O&M cost; enables smart-water integration and environmental compliance; protects prior investment through equipment reuse.

5. User Requirement Analysis

5.1 Automation Requirements

Dewatering train full-process auto-control with sequential start/stop, dosing ratio control, deodorization linkage; local interlock protection, alarms and HMI independent of the central network; data collection/control response <=1s; central refresh <=2s.

5.2 Security Surveillance Requirements

HD 4MP video at 25fps, clear day/night; 24h recording, >=30-day storage; search/playback by time, channel, event with multi-channel sync; local + remote client + mobile; unified management and reuse of existing cameras into the phase-3 platform; intelligent functions (face capture, intrusion, line crossing).

5.3 Central Control Room and Platform

Unified screens (process diagrams, data lists, trend curves); centralized alarm management with multi-level priority, popup + sound, permanent records; long-term history with daily/weekly/monthly reports and export; multi-level user permissions with full operation audit; platform compatibility and expansion for new devices/sections.

5.4 Network and Security

Industrial devices with ring redundancy (single-link fault no impact); production control network physically isolated from office/external networks — only authorized one-way transfer; UPS >=30 min backup for core equipment; lightning/surge protection for outdoor devices.

5.5 Performance and Environment

Response <=1s; refresh <=2s; MTBF >=50,000h; availability >=99.9%; field devices for wet/dusty/corrosive industrial environments; outdoor -30~+60 degC; 4MP 25fps smooth video.

5.6 O&M and Service

Standardized modular design for easy fault location/replacement; comprehensive training for independent operation and simple troubleshooting; >=1 year free warranty with on-site repair/replacement; long-term support and upgrades.

6. Design Principles and Applicable Standards

6.1 Design Principles

Advanced + mature: mainstream architecture and proven products, avoiding unproven risks. Reliability + stability first: industrial-grade field devices with high protection, wide temperature and strong immunity; redundant network with self-healing. Practical + easy: features around real production/security needs; simple intuitive interface. Safety + compliance: production, network and data security per industrial control system guidelines. Expandable + compatible: standard interfaces, modular design, multi-protocol, protecting existing investment. Economy: optimized configuration, high cost-performance, maximum reuse, lifecycle-cost awareness.

6.2 Applicable Standards

GB 50093-2013 (instrument engineering), GB 50908-2013 (industrial control computer), GB 50395-2007 (video surveillance), GB 50348-2018 (security engineering), GB/T 30094-2013 (industrial Ethernet switches), industrial control system security guidance, GB 50343-2012 (lightning), GB 50054-2011 (distribution), GB 50311-2016 (cabling), CJJ 60-2011 (WWTP O&M), project drawings, equipment lists and brand requirements.

7. System Architecture and Working Principle

7.1 Five-Layer Architecture

Perception/execution layer: H2S detectors, process sensors/instruments; pumps, fans, dewaterers, conveyors; front-end cameras. Field control layer: PLC stations — local acquisition, logic, output, interlock, alarm and HMI; standalone operation without central network. Network transport layer: industrial Ethernet ring for automation; gigabit Ethernet for surveillance; fiber/copper aggregation; industrial gateway isolating production from external networks. Platform service layer: data server, storage, SCADA, video management platform — storage, processing, analysis, alarm, report, permission, video storage/playback. Application/presentation layer: operator stations, engineer station, video management PC, field touchscreens — graphic display, remote operation, parameter configuration, maintenance.

7.2 Automation Design

“Centralized monitoring, distributed control” — control logic at field PLC stations; central room for global monitoring/management; separation avoids single-point production impact. High-performance PLC with modular IO and margin; industrial touchscreens for local operation; industrial-grade instruments with shielded analog cabling; three-level gas safety system (field sound/light alarm + PLC interlock + central warning); industrial switches in ring with link redundancy and self-healing.

7.3 Security Surveillance Design

“Front-end capture – network transport – central storage – unified management”: outdoor fixed bullets + dynamic PTZ cruising; indoor domes; waterproof shielded outdoor cabling in conduits with lightning protection; NVR centralized storage with surveillance-grade disks (30+ days); seamless integration of existing systems via protocol compatibility and platform interfacing.

7.4 Network Design

Physical isolation of automation and surveillance networks; ERPS ring for automation (self-healing <=20ms); industrial gateway (physical isolation + protocol ferry) for one-way authorized data to external networks; signal and power cables in separate layers with safe spacing.

8. Detailed Technical Design

8.1 Automation Core Equipment

PLC cabinet: floor industrial cabinet 2000x800x600mm (custom), cold-rolled steel >=2.0mm (door >=1.5mm, back >=2.5mm), electrostatic coating RAL7035, IP30, nine-fold profile frame, front glass window, galvanized rails, DIN rails, trunking, earthing busbar, fan, light, dust screen, locks; per GB 7251.1 with withstand/insulation/power-on tests. PLC CPU: 32-bit RISC >=600MHz; program >=128KB Flash (permanent), data >=64KB RAM + RTC (>=100h retention); local 256 DI + 128 AI, remote expansion; 2 Ethernet (Modbus TCP/TCP/IP/UDP) + 1 RS485 (Modbus RTU/free port), optional Profibus/Profinet; boolean <=0.08us, float <=0.3us; module/channel/comm/power diagnostics; -20~+60 degC; IEC 61131-2 immunity (+-8kV ESD, +-2kV EFT/surge); DC24V +-20%; MTBF >=50,000h. DI 16ch: DC24V 15-30V, >=7mA, opto-isolated >=1500VAC, <=1ms, LED, spring terminals. DO 16ch: transistor NPN, DC24V 0.5A/pt (common 8A), <=0.1ms, OCP/SCP/rev protection. AI 8ch: 4-20/0-20mA, 0-10/+-10V software-configurable, 12-bit+sign, +-0.2% F.S., <=10ms/ch, CMRR >=120dB, 2/3-wire. AO 4ch: 4-20/0-20mA, 0-10V, 12-bit, +-0.3% F.S., load >=500 ohm, <=10ms. PLC power: AC220V +-15%, DC24V +-1%, >=120W, ripple <=50mVpp, >=85%, full protection, MTBF >=100,000h. Communication module: 2 gigabit ports (RJ45/SFP), Modbus TCP/UDP/ICMP, layer-2 switching, ERPS/RSTP/MSTP self-healing <=20ms, 1500VAC isolation, -40~+75 degC. Touchscreen: 10″ 1024×600 TFT, resistive, ARM >=600MHz, RAM/Flash >=128MB, RS232+RS485+Ethernet, Modbus + mainstream PLC protocols, SCADA screens/alarms/trends/recipes/permissions, front IP65, DC24V <=10W. Low-voltage parts: MCBs 1-63A C-curve >=6kA; contactors 9-95A AC220V coil >=10M cycles; relays DC24V 5A/250VAC with LED and test button; copper terminals 16-100A labeled; level-2 SPD 20kA <=25ns with failure indication.

8.2 Field Instruments

H2S detector: electrochemical, 0-10ppm, 0.01ppm resolution, +-3% F.S., T90 <=30s, recovery <=60s, sensor life >=2 years; 4-20mA (<=500 ohm) + RS485 Modbus RTU; 2 relay outputs (independent level-1/2 thresholds, 5A/250VAC); DC24V <=100mA; cast-aluminum anti-corrosion housing; IP66; Ex d IIC T6 Gb; wall/pipe/clamp mounting; -20~+50 degC; per GB 15322.1. Field sound/light alarm: LED strobe red 1-2Hz, siren >=110dB at 1m, DC24V <=200mA, IP65, ABS, -30~+70 degC.

8.3 Cables and Conduits

KVV 3×1.5mm2 control cable: oxygen-free copper, PVC, 450/750V, <=70 degC, flame-retardant C (GB/T 19666), per GB/T 9330. DJYPV 2x2x1.0mm2 computer cable: per-pair braid + overall braid >=85% density, HDPE insulation, 120 ohm +-10%, 450/750V, C-class, per GB/T 19666. SC20 hot-dip galvanized steel conduit: Q235B, outer 26.9mm, wall >=2.5mm, zinc >=85um avg, threaded joints, per GB/T 3091, indoor life >=20 years / outdoor >=10 years.

8.4 Central Control Room Hardware

Operator station: 4U rack industrial PC, Core i5 >=3.0GHz 4C4T, 16GB DDR4, 512GB SSD + 2TB HDD, dual gigabit (redundant), 300W industrial supply, 27″ 1080p IPS; MTBF >=50,000h. Engineer station: Core i7 >=3.2GHz 8C8T, 32GB, 1TB SSD, 4GB discrete GPU, Win10 Pro, 24″ display. Data server: 2U rack, Xeon Silver >=2.1GHz 8C16T, 32GB DDR4 ECC (max 256GB), 2x4TB RAID1 + 4 spare bays, RAID 0/1/5/10, dual gigabit, 550W Gold, remote management, Windows Server 2019. Core industrial switch: managed gigabit, 8×10/100/1000 + 4x SFP, >=24Gbps/18Mpps, 4K VLAN, ERPS/RSTP/MSTP <=20ms, Web/CLI/SNMP v1/v2/v3, port security/802.1X/ACL, IP40, dual DC12-48V, -40~+75 degC, MTBF >=100,000h. Field industrial switch: unmanaged gigabit 8E+2SFP, >=20Gbps, IP40, DC12-48V, -40~+75 degC. Industrial gateway: dual-host + physical isolation matrix, >=100Mbps, delay <=1ms, 4+4 gigabit ports + management port, protocol ferry (Modbus TCP, OPC DA/UA, S7, EtherNet/IP), deep protocol parsing with whitelist, ACL, virus/malware defense, full audit log, dual power, MTBF >=50,000h. UPS: online double-conversion 3kVA/2.4kW, input AC220V +-25%, PF >=0.99, output 220V +-1% pure sine, 0ms transfer, 8x12V/7Ah, >=30 min full load / >=1h half, LCD, RS232 management, <=45dB, MTBF >=100,000h.

8.5 Software

PLC programming: IEC 61131-3 five languages (LD/FBD/ST/IL/SFC), compile/download/upload/online modify, monitor/force/breakpoint, offline simulation, diagnostics, Win7/10/11 x64, single-node permanent license. SCADA: >=512 points (expandable), hundreds of drivers (Modbus RTU/TCP, OPC, DDE), screen configuration with vector library and animation, real-time DB refresh <=1s, history with compression and export, multi-level alarms (popup + sound, records, statistics, print), real-time/history trends with multi-variable comparison, daily/weekly/monthly/shift reports with Excel export, multi-level permissions with audit log, WEB publishing; Windows Server 2016/2019.

8.6 Surveillance Front-End

Bullet camera: 1/2.7″ CMOS 4MP 2560×1440 25fps; H.265+/H.265/H.264+/H.264; 4mm lens F1.6 ~80°; IR >=50m with Smart IR; 120dB WDR, BLC, HLC, 3D DNR, EIS; face detect/capture (8 faces), line crossing, intrusion, motion, object left/removed; ONVIF/GB28181, dual stream; RJ45 + DC12V + PoE 802.3af; <=7W; IP66 aluminum; -30~+60 degC. PTZ dome: 1/2.8″ 4MP 25fps; 23x optical + 16x digital, 4.8-110mm F1.6-F3.5; IR >=150m smart; 360° continuous pan, -15~90° tilt, 0.1-160°/s, 256 presets +-0.1°, 8 cruise paths x32 presets, 4 pattern scans; auto tracking, face capture, intrusion/line/parking; gigabit port + audio + alarm I/O + SD slot; AC24V <=30W; IP66, TVS 6000V; -40~+70 degC. Dome camera: 1/2.7″ 4MP 25fps; 2.8mm ~90°; IR >=30m; WDR/BLC/3D DNR; motion/intrusion/face; IK10 vandal-proof; PoE, <=5W; IP40 indoor; ceiling mount.

8.7 Monitoring Center

NVR: 16 channels, >=80Mbps, 4x4MP simultaneous decode, VGA+HDMI (4K), ONVIF, schedule/motion/alarm/manual recording, instant/normal/event/tag playback with speed control, U disk/network backup, 4x SATA3 (up to 10TB each), 4x10TB surveillance disks 40TB (21 cameras H.265 24h >=30 days), gigabit, 2xUSB3.0 + 2xUSB2.0 + RS232/485, 8 alarm in / 2 out, mobile APP, 1.5U rack, <=20W (excl. disks). Security core switch: 16 gigabit + 4 SFP, >=48Gbps/36Mpps, 4K VLAN, STP/RSTP/MSTP, link aggregation, Web/CLI/SNMP, AC100-240V. Video management PC: i5 >=2.9GHz 6C6T, 16GB, 512GB SSD + 1TB HDD, Win10 Pro, 23.8″ IPS.

8.8 Transmission and Auxiliaries

Outdoor Cat6 FTP: 23AWG oxygen-free copper, aluminum-foil total shield 100%, water-blocking yarn, PE sheath, 250MHz/1000Mbps, 100 ohm +-15, NXT >=54dB@100MHz, TIA/EIA 568-C.2, outdoor life >=10 years. ZC-BVV 3×2.5mm2: flame-retardant C, 300/500V, <=70 degC, GB/T 5023. GYXTW 6-core OM1 multimode fiber: 62.5/125um, 200MHz-km@850nm / 500MHz-km@1300nm, attenuation <=3.5/1.5dB/km, center loose tube + parallel steel wires + corrugated steel tape armor + PE sheath, tensile 600N/1500N, crush 1000N/3000N, -40~+70 degC, YD/T 769. PC20 conduit: rigid PVC, wall >=1.5mm, B1 flame-retardant, >=2000V, >=400N, -5~+65 degC. Outdoor device box: 304 stainless 400x300x200mm (custom), >=1.2mm body / >=1.5mm door, IP65, anti-theft triangle lock, 12-core splice tray, 5-port 1-optical-4-electrical switch, distribution module (breaker + terminals), 2-in-1 power+network SPD, galvanized mounting plate, -40~+70 degC, life >=15 years.

9. Recommended Configuration and Preliminary Budget

9.1 Configuration Summary

Automation: dewatering workshop PLC station (1 batch, brand-selected: Schneider/Siemens/AB/Emerson PLC, ABB/Schneider/Siemens components, KITOZER fallback), control cables, galvanized conduit/stainless trunking; 1 H2S monitoring alarm set (0-10ppm, Ex d IIC T6, with sound/light alarm); KVV/DJYPV cables 40m each, SC20 conduit 80m. Central room: 1 operator station, 1 engineer station, 1 data server (RAID1), 1 core industrial switch, 1 field industrial switch, 1 industrial gateway, 1 UPS 3kVA, 1 touchscreen (in PLC set); PLC programming software, programming/debugging service, SCADA runtime (expandable), SCADA adjustment/expansion service (phase 1-3 integration), office software. Surveillance: 6 bullet 4MP, 5 PTZ 4MP, 10 dome 4MP; 1 NVR 16ch with 40TB; 1 security core switch; 1 video PC; Cat6 outdoor FTP 900m, ZC-BVV 700m, GYXTW 6-core 550m, PC20 1000m, 8 outdoor 304 device boxes; migration/reuse service for existing surveillance.

9.2 Budget Notes

Brand-selected quotation (first-line brands preferred, KITOZER fallback); final pricing per confirmed lists and drawings, tax-inclusive, in RMB (CNY) only; includes 12-month warranty, training and lifetime support; reuse/migration work itemized separately.

10. Technical Specifications

10.1 System Specification Summary

System Key Specifications
Automation PLC cabinet 2000x800x600mm IP30; CPU 32-bit >=600MHz, program >=128KB, 256DI/128AI, 2 Ethernet + 1 RS485, boolean <=0.08us, MTBF >=50,000h; DI16/DO16 transistor/AI8 +-0.2%/AO4 +-0.3%; power 120W +-1%; comm module gigabit ERPS <=20ms; 10″ HMI front IP65; MCBs/contactors/relays/terminals/SPD 20kA
H2S monitoring Electrochemical 0-10ppm, 0.01ppm, +-3% F.S., T90 <=30s; 4-20mA + RS485 Modbus; 2 relay alarms; IP66; Ex d IIC T6; sound/light alarm >=110dB IP65; three-level response (alarm -> ventilation -> device shutdown)
Central room Operator station (i5/16GB/512SSD+2TB/dual-NIC/27″); engineer station (i7/32GB/1TB SSD/4GB GPU); data server (Xeon Silver/32GB ECC/2x4TB RAID1/Win Server 2019); core switch 8E+4SFP ERPS <=20ms; gateway dual-host >=100Mbps <=1ms; UPS 3kVA >=30min 0ms transfer
Surveillance 6 bullet + 5 PTZ (23x zoom, IR >=150m, auto-track) + 10 dome (IK10); all 4MP 2560×1440 25fps H.265+; IP66 outdoor, TVS 6000V; NVR 16ch >=80Mbps, 40TB, >=30-day storage; ONVIF/GB28181; mobile APP
Network/security Automation ring ERPS self-healing <=20ms; physical isolation of automation/surveillance/office networks; industrial gateway with protocol ferry, whitelist, ACL, audit; SPD at every outdoor box
Transmission Cat6 FTP outdoor 900m; ZC-BVV 3×2.5 700m; GYXTW 6-core OM1 550m; PC20 conduit 1000m; 8 outdoor 304 IP65 boxes; KVV/DJYPV instrument cables; SC20 conduit
Performance Response <=1s; refresh <=2s; MTBF >=50,000h (core), 100,000h (power/switch/UPS); availability >=99.9%; outdoor -30~+60 degC; 4MP 25fps smooth
Schedule/service ~21 days (prep 3, cabling 5, installation 4, debug 4, trial 3, acceptance 2); 12-month warranty; 7×24 support; 2h response, 4h/8h on-site; training (operator/maintenance/management)

10.2 Standards Compliance

GB 50093, GB 50908, GB 50395, GB 50348, GB/T 30094, GB 50343, GB 50054, GB 50311, CJJ 60, GB 15322.1 (gas detector), IEC 61131-2 (PLC immunity), GB/T 19666 (flame retardant), GB/T 9330, GB/T 5023, YD/T 769 (fiber), GB 7251.1 (cabinets); brand-selected per project requirements.

11. Key Advantages and Customer Value

11.1 Architecture Advantage

Five-layer distributed architecture with clear responsibilities — independent reliable field control plus centralized management; PLC stations run standalone without the central system; mature “front-end – network – center storage – unified management” surveillance architecture with excellent expansion.

11.2 Reliability and Stability

Industrial-grade field devices — wide temperature, high protection, strong immunity for wet/corrosive/EMI-heavy plant environments; ring-redundant automation network self-healing in <=20ms; first-line brand or high-quality KITOZER core equipment with strict factory tests and long MTBF — 7×24 continuous operation.

11.3 Cost and Value

Optimized configuration without redundancy; maximum reuse of existing surveillance equipment through migration into the new platform; national-standard cables/conduits at controlled cost; modular design lowering lifecycle O&M and upgrade cost — high value delivery.

11.4 Safety Protection

Production, network and data security: toxic-gas monitoring with interlock protection; industrial gateway physically isolating production from external networks; multi-level permissions and full audit; UPS preventing data loss and monitoring gaps; lightning/surge protection for outdoor equipment.

11.5 Expandability and Compatibility

Standard interfaces and protocols; new sections/devices plug in seamlessly; SCADA point and NVR channel margin for direct expansion; Modbus/ONVIF compatibility across brands and eras; plant-level and smart-water platform interfacing.

11.6 Localized Service

Full-process service from design, supply, installation, commissioning, training to after-sales; professional teams with broad service radius; free on-site service in warranty; long-term technical support and maintenance after.

12. Technical Q&A (50+ Items)

12.1 Automation

Q1: What processes can the dewatering PLC station automate?

A: Sludge feed pump control, conditioning dosing ratio, dewaterer start/stop and parameter adjustment, discharge conveyor linkage, deodorization fan/spray linkage — full automation with interlock protection and fault alarms.

Q2: Does a PLC fault affect production?

A: No — distributed control: the PLC executes all logic locally without the central room or network; even if the central system fails, field control continues; the touchscreen provides local operation and status.

Q3: How does the system respond to H2S exceedance?

A: Three levels: level 1 — field sound/light alarm + central popup; level 2 — automatic ventilation linkage; level 3 (danger) — interlock shutdown of relevant devices; all alarms recorded and traceable.

Q4: Will motor interference affect instrument signals?

A: No — analog signals use computer cable with per-pair + overall shields (>=85% braid), single-end earthed; power and signal cables laid in separate layers with safe spacing — stable accurate transmission.

Q5: How long is history data stored?

A: Dedicated data server with large storage holds 3+ years of history at normal sampling; query, trend replay, report generation and export supported.

Q6: Is remote access supported?

A: Yes — SCADA WEB publishing for authorized browser access; the industrial gateway physically isolates and allows only authorized one-way data — production network security maintained.

Q7: Can users modify PLC programs?

A: The engineer station has licensed software; trained maintainers may view, modify and debug; major logic changes recommended by professionals for production safety.

Q8: What happens during a power failure?

A: UPS (3kVA, >=30min) keeps monitoring and data alive; PLC retentive memory holds parameters; orderly shutdown prevents data loss.

Q9: What is the control response time?

A: Data acquisition/control <=1s; central screen refresh <=2s; interlock actions execute locally in milliseconds.

Q10: Can phases 1-2 systems integrate?

A: Yes — the SCADA adjustment/expansion service adds the new PLC station to the existing platform, configuring phase 1-3 integration and linkage logic.

12.2 Surveillance

Q11: How clear is the video? Night performance?

A: All cameras are 4MP 2560×1440; outdoor bullets/PTZs have high-power IR (50-150m) with Smart IR preventing overexposure — excellent night monitoring.

Q12: How long is video stored?

A: 16-channel NVR with 40TB surveillance-grade disks stores 21 4MP H.265 cameras 24h for 30+ days; expandable by adding disks.

Q13: Can existing cameras be integrated?

A: Yes — the migration service relocates and re-commissiones reusable cameras into the new NVR/platform — unified management, storage and preview, maximizing reuse.

Q14: What can the PTZ do?

A: 360° continuous pan, tilt, 23x optical zoom, 256 presets, cruise paths, pattern scans, auto tracking, face capture, intrusion/line-crossing analytics — for wide-area dynamic monitoring.

Q15: Will outdoor cameras be struck by lightning?

A: No — outdoor boxes integrate 2-in-1 power+network SPDs; cameras have TVS 6000V lightning protection — multi-layer protection for rainy seasons.

Q16: Can phones view the surveillance?

A: Yes — mobile APP preview, playback and PTZ control for authorized users anywhere.

Q17: What intelligent functions are included?

A: Face detection/capture, line crossing, region intrusion, motion detection, object left/removed, auto tracking, optional vehicle detection.

Q18: Are indoor cameras vandal-resistant?

A: Domes are IK10 vandal-proof with metal housing and acrylic dome — suited to public/industrial interiors.

12.3 Network and Security

Q19: How is the automation network protected?

A: ERPS ring with self-healing <=20ms (single-link fault no impact); industrial-grade switches -40~+75 degC; physical isolation from office/external networks.

Q20: What does the industrial gateway do?

A: Dual-host physical isolation + protocol ferry; deep protocol parsing with whitelist (only legal commands pass); ACL by IP/port/protocol; virus/malware defense; full audit logging.

Q21: Are automation and surveillance networks separated?

A: Yes — physically separate networks; surveillance risk cannot propagate to production control.

Q22: What about cyber attacks?

A: Physical isolation, protocol whitelisting, ACLs, port security/802.1X, anti-SQL/script injection, audit logs and permission controls form defense in depth.

Q23: How is data security ensured?

A: RAID1 server storage, UPS-backed orderly shutdown, permission-controlled access, operation audit trail, backup and restore procedures.

12.4 Equipment and Environment

Q24: What are the PLC performance specs?

A: 32-bit >=600MHz; boolean <=0.08us; program >=128KB; 256DI/128AI local; 2 Ethernet + 1 RS485; module diagnostics; IEC 61131-2 immunity (+-8kV ESD).

Q25: What is the MTBF of core equipment?

A: PLC/switch/power >=50,000-100,000h; system availability >=99.9%; UPS MTBF >=100,000h.

Q26: What environment can field devices withstand?

A: PLC/switch -20~+75 degC (storage -40~+85); outdoor devices -30~+60 degC; humidity 5-95% no condensation; IP30 cabinets, IP66 outdoor devices/boxes, IP65 HMI front.

Q27: Why H.265 encoding?

A: H.265+/H.265 halves storage and bandwidth versus H.264 at the same 4MP quality — 30+ days on 40TB for 21 cameras.

Q28: What is the UPS backup time?

A: 3kVA online UPS: >=30 min full load, >=1h half load; 0ms transfer (pure sine) — monitoring and data uninterrupted.

Q29: How are outdoor boxes configured?

A: 304 stainless IP65, 12-core splice tray, 1-optical-4-electrical switch, distribution with breaker/terminals, 2-in-1 SPD, anti-theft lock — per-point aggregation and protection.

Q30: What cables are used and why shielded?

A: DJYPV computer cable (per-pair + overall braid) for analog signals; Cat6 FTP outdoor for cameras; GYXTW armored fiber for the ring — shield + separation ensure signal integrity in heavy EMI.

12.5 Construction and Acceptance

Q31: What is the construction period?

A: ~15-20 days of site work (21 days total with acceptance), adjustable per project; parallel work streams compress the schedule.

Q32: Does construction affect production?

A: No — detailed plan and outage windows avoid peak periods; integration work done off-peak; strict adherence to plant safety rules.

Q33: What is the acceptance standard?

A: Per national codes, drawings and scheme — appearance/installation, cabling and labeling, system function tests, performance tests, documentation handover; all indicators pass before acceptance.

Q34: What documents are delivered?

A: As-built drawings, equipment lists and certificates, PLC program and SCADA project files, O&M manuals, test reports, acceptance report.

Q35: How is hidden work verified?

A: Conduit/cable hidden work recorded and accepted (signed) with photo evidence before covering.

Q36: What safety measures apply on site?

A: Certified operators with PPE; three-level distribution with two-level protection; harnesses for high work; hot-work permits with extinguishers; daily inspections and education.

12.6 Service and Maintenance

Q37: What is the warranty?

A: 12 months free from acceptance — non-human faults repaired/replaced on site free; free technical consultation, optimization and minor adjustments; phone follow-ups and inspection.

Q38: Fault response time?

A: 7×24 hotline; general issues 2h response with remote guidance; on-site 4h urban / 8h suburban; general faults within 24h; major outages invoke emergency plans with temporary restoration.

Q39: Post-warranty service?

A: Annual maintenance agreements (inspection, repair, upgrade, support); per-visit paid service at reasonable cost; spares guaranteed >=5 years; upgrade/expansion services.

Q40: What training is provided?

A: Operators (operations, alarms, reports, video playback, PTZ); maintainers (PLC principles, instruments, network, cameras/NVR troubleshooting, software basics); managers (data analysis, permissions, audit, management system) — >=2 days with assessment and certificates.

Q41: Can the system expand later?

A: Yes — SCADA points (>=512, expandable), NVR channels (16, expandable), spare PLC IO/slots and standard protocols accept new sections/devices seamlessly.

Q42: How is the existing monitoring reused?

A: Reusable cameras are dismantled, re-based, rewired and re-commissioned into the phase-3 platform — unified management with preserved function.

Q43: Why choose the KITOZER/Lain solution?

A: 20+ years of industrial automation and security engineering; brand-selected first-line components with KITOZER fallback; own engineering teams; full lifecycle service; proven plant projects.

Q44: What is the system availability?

A: >=99.9% annually with redundant network, UPS, RAID storage and modular maintenance.

Q45: Are explosion-proof options available?

A: Yes — H2S detector is Ex d IIC T6; hazardous-area field devices and wiring per codes.

Q46: How does it support environmental compliance?

A: Full data records, automatic reports, traceable export and interfaces to environmental online platforms.

Q47: What is the noise level of the UPS?

A: <=45dB at 1m — quiet for the control room.

Q48: Is remote monitoring of the plant available to managers?

A: Yes — WEB publishing and mobile APP give authorized managers anytime access.

Q49: How are alarm records managed?

A: Multi-level priority, popup + sound, permanent storage, statistics and printing; time-stamped for traceability.

Q50: What makes this solution cost-effective?

A: Optimized configuration, maximum reuse of existing equipment, national-standard materials, modular low-cost maintenance, energy/labor savings and long lifecycle support.

13. Construction Schedule

13.1 Overall Schedule

Stage Work Days Responsible Acceptance node
Preparation Site survey, disclosure, materials/equipment arrival, tools, temporary facilities 3 PM Material arrival acceptance
Cabling Automation/surveillance/fiber laying; conduit and tray installation; termination and tests 5 Crew lead Hidden-work acceptance
Installation PLC cabinets, central equipment, cameras, device boxes, instruments; cabinet and device wiring 4 Crew lead Installation acceptance
Commissioning Single-point debug, PLC program debug, SCADA screens, surveillance debug, linkage tests 4 Technical lead Function tests
Trial run Continuous trial, parameter optimization, rectification 3 Technical lead Trial records
Acceptance As-built docs, acceptance application, formal acceptance, training handover 2 PM Final acceptance

Total ~21 days, adjustable to site conditions.

14. Construction Organization and Quality/Safety Measures

14.1 Organization

PM-led project team: PM (overall management, coordination, progress/quality/safety/cost, customer liaison); technical lead (design, disclosure, programming, commissioning, problem solving); crew lead (site organization, dispatch, process execution); safety officer (safety management, training, inspections); QC (quality checks, staged acceptance, material/process control); documentation clerk (records, as-built docs, archives). All experienced and certified.

14.2 Preparation

Technical: drawing review, technical/safety disclosure, construction scheme, familiarization with requirements. Materials: procurement, incoming inspection, classified storage; tools and instruments calibrated. Site: temporary power/water/warehouse, safety facilities, plant coordination. Personnel: entry, safety education, role assignment.

14.3 Core Processes

Cabling: per drawing — straight level runs, firm fixing; conduit protection of insulation; clear two-end labels; power and signal in separate layers with spacing; hidden work recorded and accepted before covering. Installation: firm accurate mounting; cabinets level/vertical with good earthing; camera angles set for clear images; outdoor devices waterproof-sealed; wiring standard with clear line numbers and neat dressing. Commissioning: single-point first, then linkage; local first, then central; staged tests with records; 72h continuous trial verifying stability.

14.4 Quality Assurance

Three-level inspection (team self-check -> QC recheck -> project final); all materials inspected before use; construction strictly per national codes, drawings and scheme with per-process acceptance; hidden work signed by the customer with photo evidence; complete traceable records.

14.5 Safety and Civilized Construction

National safety codes and plant rules; certified operators with PPE; standard temporary power with RCDs (no random wiring); harnesses and proper scaffolding for high work; hot-work permits with extinguishers and supervision; tidy materials and daily cleanup; regular safety inspections and education.

14.6 Progress Assurance

Detailed schedule with daily node tracking; advance procurement; parallel/cross work streams; daily progress meetings; catch-up plans with added resources if delayed.

14.7 Emergency Plan

Specific contingency plans for electric shock, fire, falls and equipment damage — emergency supplies, first aid, clear procedures and responsible persons; regular drills.

15. After-Sales Service

15.1 Warranty Commitment

12-month free warranty from acceptance; free repair/replacement/on-site service for non-human faults; free technical consultation, optimization and minor function adjustments; phone follow-ups and on-site inspections proactively.

15.2 Response Mechanism

7×24 hotline; general issues 2h response with remote guidance; on-site 4h urban / 8h suburban; general faults within 24h; major outages invoke emergency plans restoring operation with minimal production impact.

15.3 Post-Warranty

Annual maintenance agreements (inspection, repair, upgrade, support); per-visit paid service at reasonable cost; spares guaranteed >=5 years; system upgrade and expansion services for future needs.

15.4 Spare Parts

Common spares and wear parts stocked for rapid replacement; original genuine parts; end-of-life models get compatible replacement solutions.

16. Training Plan

16.1 Training Objectives and Audience

Training objectives: through systematic training, enable management personnel to fully understand the system structure, working principles and performance characteristics, master daily operation methods and inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation.

Training audience: management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and equipment knowledge.

16.2 Tiered Training Content System

Level 1: Basic operation training (1 day)

– Basic principles: system concepts, structure composition, performance indicators;

– Daily operation standards: correct operation of equipment, control and safety systems;

– Daily inspection contents: daily/weekly/monthly check items;

– Safety precautions: usage prohibitions and emergency handling procedures.

Level 2: Maintenance training (1 day)

– Detailed structure of each subsystem and working principles;

– Daily maintenance methods: cleaning, fastening checks, routine care;

– Common fault identification and simple handling;

– Emergency handling procedures for power failure, fire and equipment faults.

Level 3: Advanced management training (as needed)

– Performance influencing factors and how to avoid degradation;

– Upgrade and expansion knowledge and specification requirements;

– Relevant national standards interpretation.

16.3 Training Methods and Schedule

– Methods: combination of “theory explanation + on-site practice + Q&A interaction”;

– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable; a free repeat training session is provided for newly assigned personnel.

16.4 Training Assessment and Documentation Delivery

– Assessment: theory written test plus practical operation; training qualification certificates issued upon passing; supplementary training for those who fail;

– Documentation delivery: complete O&M documentation, including operation and maintenance manual, equipment manuals and certificates, completion drawings and hidden work records, test reports and after-sales service contact card, all bound into volumes.

17. Anonymous Typical Project Scenarios

All project scenarios below are anonymous, generalized examples provided for reference only. No real customer names, addresses or identifiable details are disclosed.

17.1 Large WWTP Automation and Surveillance Project

Background. A 100,000 t/d plant needed full automation — inlet, biological, sedimentation, sludge dewatering and deodorization PLC control plus central SCADA and plant-wide surveillance.

Solution. Full-process PLC systems, central control room platform and complete HD surveillance; three-level gas safety; redundant ring network with industrial gateway isolation.

Results. Automation rate above 90%; labor cost down 40%; energy down 15%; zero safety accidents — highly rated by the customer.

17.2 Industrial Park Environment Monitoring and Security Project

Background. A chemical industrial park needed toxic-gas online monitoring, wastewater/waste-gas monitoring, HD video surveillance and perimeter alarms.

Solution. Unified environment + security system with real-time data, exceedance warnings, full-coverage surveillance and event tracing.

Results. Raised park safety management; passed environmental and safety supervision acceptance.

17.3 Water Plant Central Control Upgrade and Expansion Project

Background. A water plant’s aging central control system lacked points and was fragmented across multiple systems.

Solution. Upgraded SCADA and server, added new-section automation, integrated legacy systems into one unified platform.

Results. Resolved aging, capacity and fragmentation issues; stability and ease of operation greatly improved; met smart-water upgrade needs.

17.4 Municipal Sludge Disposal Center Automation Project

Background. A municipal sludge disposal center needed full PLC automation and video surveillance across reception, drying, incineration and discharge.

Solution. Complete automation with precise key-parameter control and full-process surveillance; interlock and emergency protection.

Results. Higher disposal efficiency, lower operating cost and assured production safety.

18. SEO Optimization Section

All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.

18.1 Keyword System

– Core keywords: technical design solution, system configuration, technical parameters, construction and O&M services;

– High-conversion long-tail keywords: design solution, configuration list, technical parameters, construction plan, after-sales service;

– Industry traffic keywords: system architecture, applicable standards, technical Q&A, project cases;

– Brand keywords: KITOZER, Guangzhou Lain.

18.2 SEO Tag System

– Title tag: the article title — Guangzhou Lain KITOZER;

– Meta description: Guangzhou Lain professionally provides complete technical design solutions with detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant performance, third-party testing supported;

– H1 tag: the article title;

– H2 tags: system design and product parameters, construction organization plan, after-sales service and training, engineering cases.

18.3 Internal Link Anchor Text

– Core anchor text: technical design solution, system construction;

– Long-tail anchor text: configuration list, technical parameters, construction plan;

– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.

19. Official Contact Information

– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Official Website: https://gdlain.com

– Tel: +86 139 2228 9957 (WeChat available), +86 185 2066 8845 (WeChat available)

– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China

For any inquiries about this technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific requirements.

Scroll to Top