The grounding system of a shielded computer room is the core infrastructure for electromagnetic protection and safe operation of shielded rooms. It follows three core principles: single-point grounding, priority of combined grounding, and low-impedance current discharge. The system is designed in compliance with standards including GB50174-2017 Code for Design of Electronic Information System Computer Room and GB/T50719-2021 Technical Code for Electromagnetic Shielding Chamber Engineering.
By constructing an equipotential bonding network and low-resistance grounding channels, the system unifies the electric potential of shielding enclosures, equipment, cables and lightning protection systems. It effectively eliminates ground loop interference, prevents ground potential counterattack, and rapidly discharges static electricity and lightning current, ensuring shielding effectiveness (80–120 dB attenuation in the 10 kHz–18 GHz frequency band) and stable operation of precision equipment. It is widely deployed in high-security scenarios such as classified computer rooms, military laboratories, financial data centers, and medical imaging centers.
On-site Installation of Shielded Room Grounding System
2. System Composition
The shielded room grounding system consists of five core modules: equipotential bonding unit, grounding main line unit, grounding electrode unit, lightning protection unit and insulation isolation unit. These modules jointly build a three-level grounding architecture (shield protection ground, grid functional ground, single-point reference ground):
- Equipotential Bonding Unit: Comprises equipotential copper busbars, grounding terminal boxes, copper braided straps and jumpers. It achieves equipotential connection of metal components inside the room (shield enclosures, cabinets, raised floor supports, metal pipelines) to eliminate potential differences.
- Grounding Main Line Unit: Adopts pure copper busbars or multi-strand copper cables as the main grounding channel linking the equipotential network and grounding electrodes, featuring short, straight and thick layout for low high-frequency impedance.
- Grounding Electrode Unit: Includes vertical grounding electrodes, horizontal grounding conductors, graphite grounding modules and resistance-reducing agents buried in outdoor soil to build a low-resistance grounding grid that meets grounding resistance standards.
- Lightning Protection Unit: Consists of power surge protective devices (SPDs), signal lightning arresters and equipotential connectors to discharge lightning current and induced overvoltage and prevent surge damage to equipment.
- Insulation Isolation Unit: Contains insulation pads, insulation boards and insulated cables. It provides insulation between shielding enclosures and building foundations, as well as between different grounding systems to avoid stray current interference.
3. System Classification
The system is classified from four dimensions: grounding architecture, functional purpose, grounding resistance grade and equipotential connection mode, to adapt to diverse scenario requirements.
3.1 Classification by Grounding Architecture
- Combined Grounding System (Mainstream Solution): The shielding ground, lightning protection ground, protective ground and working ground share one set of grounding grid with grounding resistance ≤1 Ω. It avoids ground potential counterattack and complies with mandatory requirements of GB50174.
- Independent Grounding System (Special Scenarios): The shielding enclosure is equipped with a separate grounding grid physically isolated from the building grounding system, only applied to specific scenarios such as metrology and calibration laboratories, with grounding resistance ≤0.5 Ω.
3.2 Classification by Functional Purpose
- Shielding Ground: Connects shielding enclosures to discharge induced surface charges and guarantee shielding effectiveness, grounding resistance ≤1 Ω.
- Protective Ground: Links equipment casings and metal racks to prevent electric leakage hazards, grounding resistance ≤4 Ω.
- Working Ground: Includes AC working ground (power neutral wire) and DC working ground (equipment signal reference ground) to support normal equipment operation, grounding resistance ≤4 Ω.
- Lightning Protection Ground: Connects lightning arresters and air terminals to discharge lightning current, grounding resistance ≤10 Ω.
- Anti-static Ground: Connects raised floors and workbenches to discharge static electricity, grounding resistance ranging from 1 Ω to 10 Ω.
3.3 Classification by Grounding Resistance Grade
Production Workshop for Grounding System Components
- Basic Grade: Grounding resistance ≤4 Ω, applicable to ordinary shielded rooms and non-classified data centers.
- Standard Grade: Grounding resistance ≤1 Ω, applicable to classified computer rooms, financial computer rooms and industrial control centers.
- Advanced Grade: Grounding resistance ≤0.5 Ω, applicable to military laboratories, quantum computing laboratories and high-precision test rooms.
3.4 Classification by Equipotential Connection Mode
- S-type (Star) Single-point Grounding: All equipment converges to a single grounding reference point, suitable for small computer rooms and low-frequency scenarios to suppress ground loop interference.
- M-type (Mesh) Grounding: Grid-shaped equipotential network with multi-point connections, suitable for large computer rooms and high-frequency scenarios with high grounding reliability.
- S-M Hybrid Grounding: Combines the advantages of star and mesh structures, balancing single-point reference and multi-point redundancy, applicable to medium-to-large high-grade shielded rooms.
4. System Schematic Diagram
Structural Schematic of Shielded Room Grounding System
5. System Configuration List (Three Tiers: Basic / Standard / Advanced, Brand: KITOZER)
5.1 Basic Tier Configuration List (Basic Grade, Grounding Resistance ≤4 Ω, Small Non-Classified Shielded Room)
è¡¨æ ¼
| No. | Product Name | Model & Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Equipotential Copper Busbar | KT-TP-303 | Pure copper, 30mm×3mm, 6m long, conductivity ≥58 MS/m, tin-plated anti-corrosion surface | 4 | Pcs | KITOZER | Laid around the room perimeter in a ring |
| 2 | Grounding Terminal Box | KT-DBX-01 | 304 stainless steel, 300×200×150mm, 10 built-in terminals, IP54 protection | 1 | Set | KITOZER | Wall-mounted, equipotential convergence point |
| 3 | Copper Braided Strap | KT-BZ-16 | Tin-plated copper, 16 mm² cross-section, 20mm width, 1m length, copper lugs crimped at both ends, DC resistance ≤0.05 mΩ | 20 | Pcs | KITOZER | Cross-connection for shielding enclosures and cabinets |
| 4 | Yellow-Green Ground Cable | KT-GX-25 | ZR-BVR, 25 mm², yellow-green dual-color, flame-retardant, rated voltage 450/750 V | 50 | M | KITOZER | Equipment grounding branch lines |
| 5 | Vertical Grounding Electrode | KT-JD-50 | Hot-dip galvanized angle steel, 50×50×5mm, 2.5m length, galvanized layer ≥85 μm | 6 | Pcs | KITOZER | Vertical grounding conductors for outdoor grounding grid |
| 6 | Horizontal Grounding Conductor | KT-TP-404 | Hot-dip galvanized flat steel, 40×4mm, 6m length, galvanized layer ≥85 μm | 4 | Pcs | KITOZER | Horizontal connection for outdoor grounding grid |
| 7 | Grounding Module | KT-MK-01 | Graphite resistance-reducing type, 500×400×60mm, grounding resistance ≤10 Ω, resistance reduction rate ≥50% | 2 | Blocks | KITOZER | Reduce resistance in high soil resistivity areas |
| 8 | Resistance-Reducing Agent | KT-JZ-01 | Eco-friendly long-term type, resistivity ≤5 Ω·m, pH 7–9, service life ≥10 years | 50 | Kg | KITOZER | Backfill around grounding electrodes for resistance reduction |
| 9 | Class II Power SPD | KT-SPD40 | Waveform 8/20 μs, Imax ≥40 kA, In ≥20 kA, voltage protection level ≤1.5 kV, 220 VAC | 2 | Sets | KITOZER | Lightning protection at UPS input end |
| 10 | Insulation Pad | KT-JY-5 | Polyurethane, 100×100×5mm, insulation resistance ≥100 MΩ, withstand voltage ≥5 kV | 50 | Pcs | KITOZER | Insulation between shielding enclosures and foundations |
5.2 Standard Tier Configuration List (Standard Grade, Grounding Resistance ≤1 Ω, Medium-Sized Classified / Financial Shielded Room)
è¡¨æ ¼
| No. | Product Name | Model & Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Equipotential Copper Busbar | KT-TP-404 | Pure copper, 40mm×4mm, 6m long, conductivity ≥58 MS/m, tin-plated anti-corrosion surface, equipped with insulating brackets | 6 | Pcs | KITOZER | Laid around room perimeter + under raised floor in grid layout |
| 2 | Grounding Terminal Box | KT-DBX-02 | 316 stainless steel, 400×300×200mm, 20 built-in terminals, IP65 protection, equipped with disconnection card | 2 | Sets | KITOZER | Main & auxiliary equipotential convergence points |
| 3 | Copper Braided Strap | KT-BZ-25 | Tin-plated copper, 25 mm² cross-section, 30mm width, 1.5m length, copper lugs crimped at both ends, DC resistance ≤0.03 mΩ, impedance ≤10 mΩ @ 1 GHz | 30 | Pcs | KITOZER | Cross-connection for shielding enclosures, cabinets and metal pipelines |
| 4 | Yellow-Green Ground Cable | KT-GX-35 | ZR-BVR, 35 mm², yellow-green dual-color, flame-retardant, rated voltage 450/750 V, anti-aging | 80 | M | KITOZER | Equipment grounding branch lines and main line connections |
| 5 | Vertical Grounding Electrode | KT-JD-60 | Hot-dip galvanized angle steel, 60×60×6mm, 3m length, galvanized layer ≥100 μm, high corrosion resistance | 8 | Pcs | KITOZER | Vertical grounding conductors for outdoor grounding grid |
| 6 | Horizontal Grounding Conductor | KT-TP-505 | Pure copper busbar, 50×5mm, 6m long, conductivity ≥58 MS/m, tin-plated anti-corrosion | 6 | Pcs | KITOZER | Horizontal connection for outdoor grounding grid, low impedance |
| 7 | Grounding Module | KT-MK-02 | Composite graphite & electrolyte, 600×500×80mm, grounding resistance ≤5 Ω, resistance reduction rate ≥70%, stable long-term performance | 4 | Blocks | KITOZER | Reduce resistance in high soil resistivity areas |
| 8 | Resistance-Reducing Agent | KT-JZ-02 | Nano-carbon conductive type, resistivity ≤3 Ω·m, pH 7–8, service life ≥20 years, eco-friendly & non-corrosive | 80 | Kg | KITOZER | Backfill around grounding electrodes for resistance reduction |
| 9 | Class I Power SPD | KT-SPD100 | Waveform 10/350 μs, Iimp ≥25 kA, In ≥100 kA, voltage protection level ≤2.5 kV, 380 VAC | 1 | Set | KITOZER | Inlet end of main power distribution cabinet in computer room |
| 10 | Class II Power SPD | KT-SPD40 | Waveform 8/20 μs, Imax ≥40 kA, In ≥20 kA, voltage protection level ≤1.5 kV, 220 VAC | 3 | Sets | KITOZER | UPS input/output ends, row cabinet |
| 11 | Signal Lightning Arrester | KT-SPD-XH | RJ45 interface, 1000 Mbps transmission, protection level ≤50 V, response time ≤1 ns, PoE compatible | 8 | Sets | KITOZER | Lightning protection for switch and server network ports |
| 12 | Insulation Board | KT-JY-8 | Black industrial rubber, 1000×2000×8mm, insulation resistance ≥200 MΩ, withstand voltage ≥10 kV, moisture-proof & flame-retardant | 20 | ㎡ | KITOZER | Fully laid at the bottom of shielding enclosures for insulation |
| 13 | Equipotential Connector | KT-LJ-01 | Current capacity 100 kA, trigger voltage ≤100 V, insulation resistance ≥500 MΩ, dual-mode isolation/conductivity | 2 | Sets | KITOZER | Equipotential connection between shielding ground and lightning protection ground |
5.3 Advanced Tier Configuration List (Advanced Grade, Grounding Resistance ≤0.5 Ω, Large Military / High-Precision Shielded Room)
è¡¨æ ¼
| No. | Product Name | Model & Specification | Technical Parameters | Qty | Unit | Brand | Remarks |
|---|---|---|---|---|---|---|---|
| 1 | Equipotential Copper Busbar | KT-TP-505 | Pure copper, 50×5mm, 6m long, conductivity ≥58 MS/m, tin-plated anti-corrosion surface, high-density insulating brackets, M-type grid layout | 8 | Pcs | KITOZER | Six-sided equipotential grid inside the room |
| 2 | Grounding Terminal Box | KT-DBX-03 | 316L stainless steel, 500×400×250mm, 30 built-in terminals, IP67 protection, equipped with monitoring module and disconnection card | 3 | Sets | KITOZER | Main / auxiliary / backup equipotential convergence points |
| 3 | Copper Braided Strap | KT-BZ-35 | Tin-plated copper, 35 mm² cross-section, 40mm width, 2m length, copper lugs crimped at both ends, DC resistance ≤0.02 mΩ, impedance ≤5 mΩ @ 1 GHz, wide temperature resistance | 50 | Pcs | KITOZER | High-frequency cross-connection for all metal components |
| 4 | Yellow-Green Ground Cable | KT-GX-50 | ZR-VVP shielded cable, 50 mm², yellow-green dual-color, flame-retardant, rated voltage 0.6/1 kV, anti-aging & corrosion-resistant | 120 | M | KITOZER | Grounding main trunk connections |
| 5 | Vertical Grounding Electrode | KT-JD-80 | Hot-dip galvanized angle steel, 80×80×8mm, 3.5m length, galvanized layer ≥120 μm, high corrosion resistance, driving depth ≥3m | 12 | Pcs | KITOZER | Vertical grounding conductors for outdoor grounding grid |
| 6 | Horizontal Grounding Conductor | KT-TP-606 | Pure copper busbar, 60×6mm, 6m long, conductivity ≥58 MS/m, tin-plated anti-corrosion, excellent high-frequency low-impedance performance | 8 | Pcs | KITOZER | Closed ring horizontal connection for outdoor grounding grid |
| 7 | Grounding Module | KT-MK-03 | Superconducting graphite composite, 800×600×100mm, grounding resistance ≤2 Ω, resistance reduction rate ≥85%, service life ≥30 years, adaptable to harsh soil | 6 | Blocks | KITOZER | Powerful resistance reduction in high soil resistivity areas |
| 8 | Resistance-Reducing Agent | KT-JZ-03 | Superconducting ionic type, resistivity ≤1 Ω·m, pH 7–7.5, service life ≥30 years, non-corrosive & acid-alkali resistant | 120 | Kg | KITOZER | Full-area backfill of grounding grid for resistance reduction |
| 9 | Class I Power SPD | KT-SPD120 | Waveform 10/350 μs, Iimp ≥40 kA, In ≥120 kA, voltage protection level ≤2.0 kV, 380 VAC, remote monitoring function | 2 | Sets | KITOZER | Dual-circuit incoming power of main distribution cabinet in computer room |
| 10 | Class II Power SPD | KT-SPD60 | Waveform 8/20 μs, Imax ≥60 kA, In ≥30 kA, voltage protection level ≤1.0 kV, 220 VAC, remote monitoring function | 4 | Sets | KITOZER | UPS, precision air conditioner, row cabinet |
| 11 | Class III Power SPD | KT-SPD20 | Waveform 8/20 μs, Imax ≥20 kA, In ≥10 kA, voltage protection level ≤0.8 kV, 220 VAC, fine protection | 6 | Sets | KITOZER | Front end of servers and precision equipment |
| 12 | Signal Lightning Arrester | KT-SPD-XH2 | Composite RJ45 + optical fiber, 10 Gbps transmission, protection level ≤30 V, response time ≤0.5 ns, compatible with single/multi-mode fiber | 16 | Sets | KITOZER | Core switches, servers, storage equipment |
| 13 | Insulation Board | KT-JY-10 | High-density polyurethane, 1200×2400×10mm, insulation resistance ≥500 MΩ, withstand voltage ≥15 kV, moisture-proof, flame-retardant & anti-aging | 30 | ㎡ | KITOZER | Full bottom insulation of shielding enclosure, suspended design |
| 14 | Equipotential Connector | KT-LJ-02 | Current capacity 200 kA, trigger voltage ≤50 V, insulation resistance ≥1000 MΩ, intelligent monitoring & remote alarm | 3 | Sets | KITOZER | Multi-system equipotential linkage & fault isolation |
| 15 | Grounding Resistance Monitor | KT-JC-01 | Measuring range 0.01 Ω–100 Ω, accuracy ±1%, remote transmission, sound-light alarm, supports 4G/Ethernet | 1 | Set | KITOZER | Real-time grounding resistance monitoring with abnormal alarm |
6. Full Product Technical Parameters
6.1 Equipotential Copper Busbar (KT-TP Series)
- Material: High-purity T2 pure copper, conductivity ≥58 MS/m
- Specifications: 30×3mm, 40×4mm, 50×5mm, 60×6mm, 6m per piece
- Surface Treatment: Tin plating (thickness ≥5 μm), anti-oxidation & anti-corrosion
- Insulating Bracket: High-strength ABS, insulation resistance ≥100 MΩ, spacing 1.5m
- Operating Temperature: -40℃ ~ +120℃
- Flame Retardant Grade: UL94 V-0
6.2 Grounding Terminal Box (KT-DBX Series)
- Material: 304 stainless steel (Basic Tier) / 316 stainless steel (Standard Tier) / 316L stainless steel (Advanced Tier)
- Dimensions: 300×200×150mm (Basic), 400×300×200mm (Standard), 500×400×250mm (Advanced)
- Protection Grade: IP54 (Basic), IP65 (Standard), IP67 (Advanced)
- Wiring Terminals: 10/20/30 positions, silver-plated pure copper, rated current ≥200 A
- Additional Functions: Disconnection card (Standard & Advanced), grounding resistance monitoring module (Advanced)
- Operating Temperature: -20℃ ~ +60℃
6.3 Copper Braided Strap (KT-BZ Series)
- Material: Multi-strand tin-plated copper wire, single wire diameter ≥0.15mm
- Cross-section: 16 mm², 25 mm², 35 mm², width 20/30/40mm
- DC Resistance: ≤0.05 mΩ (16 mm²), ≤0.03 mΩ (25 mm²), ≤0.02 mΩ (35 mm²)
- High-Frequency Impedance: ≤10 mΩ @ 1 GHz (Standard), ≤5 mΩ @ 1 GHz (Advanced)
- Terminal Treatment: Crimped pure copper lugs with tin plating for anti-corrosion
- Temperature Resistance: -55℃ ~ +150℃
- Tensile Strength: ≥200 MPa
6.4 Yellow-Green Ground Cable (KT-GX Series)
- Model: ZR-BVR (Basic & Standard) / ZR-VVP shielded cable (Advanced)
- Cross-section: 25 mm², 35 mm², 50 mm²
- Insulation Material: Flame-retardant PVC (Basic & Standard), flame-retardant cross-linked PVC (Advanced)
- Rated Withstand Voltage: 450/750 V (Basic & Standard), 0.6/1 kV (Advanced)
- Conductor: Multi-strand oxygen-free copper, conductivity ≥58 MS/m
- Color: Yellow-green dual-color, compliant with IEC 60446
- Flame Retardant Standard: GB/T 18380.3, self-extinguishing after flame removal
- Operating Temperature: -30℃ ~ +90℃
6.5 Vertical Grounding Electrode (KT-JD Series)
- Material: Hot-dip galvanized Q235B angle steel
- Specifications: 50×50×5mm (Basic), 60×60×6mm (Standard), 80×80×8mm (Advanced)
- Length: 2.5m (Basic), 3m (Standard), 3.5m (Advanced)
- Galvanized Layer Thickness: ≥85 μm (Basic), ≥100 μm (Standard), ≥120 μm (Advanced)
- Grounding Resistance: ≤10 Ω (soil resistivity ≤100 Ω·m)
- Corrosion Resistance Service Life: ≥10 years (Basic), ≥15 years (Standard), ≥20 years (Advanced)
6.6 Grounding Module (KT-MK Series)
Interior of Standard Shielded Computer Room
- Material: Graphite (Basic), composite graphite & electrolyte (Standard), superconducting graphite composite (Advanced)
- Dimensions: 500×400×60mm (Basic), 600×500×80mm (Standard), 800×600×100mm (Advanced)
- Grounding Resistance: ≤10 Ω (Basic), ≤5 Ω (Standard), ≤2 Ω (Advanced)
- Resistance Reduction Rate: ≥50% (Basic), ≥70% (Standard), ≥85% (Advanced)
- Service Life: ≥10 years (Basic), ≥20 years (Standard), ≥30 years (Advanced)
- Applicable Soil: Resistivity 100–5000 Ω·m, acid-alkali resistant & anti-corrosion
6.7 Resistance-Reducing Agent (KT-JZ Series)
- Type: Eco-friendly long-term type (Basic), nano-carbon conductive type (Standard), superconducting ionic type (Advanced)
- Resistivity: ≤5 Ω·m (Basic), ≤3 Ω·m (Standard), ≤1 Ω·m (Advanced)
- pH Value: 7–9 (Basic), 7–8 (Standard), 7–7.5 (Advanced)
- Valid Period: ≥10 years (Basic), ≥20 years (Standard), ≥30 years (Advanced)
- Characteristics: Eco-friendly, non-corrosive, acid-alkali resistant, non-leaching, stable long-term performance
- Operating Temperature: -40℃ ~ +80℃
6.8 Power SPD (KT-SPD Series)
- Models: KT-SPD100 (Class I), KT-SPD40 (Class II), KT-SPD60 (Advanced Class II), KT-SPD20 (Class III)
- Waveform: 10/350 μs (Class I), 8/20 μs (Class II & III)
- Current Capacity: Iimp ≥25 kA (Class I), Imax ≥40 kA (Class II), Imax ≥60 kA (Advanced Class II), Imax ≥20 kA (Class III)
- Voltage Protection Level: ≤2.5 kV (Class I), ≤1.5 kV (Class II), ≤1.0 kV (Advanced Class II), ≤0.8 kV (Class III)
- Operating Voltage: 380 VAC (Class I), 220 VAC (Class II & III)
- Additional Functions: Remote monitoring (Advanced), failure alarm, thermal disconnection protection
- Response Time: ≤25 ns
6.9 Signal Lightning Arrester (KT-SPD-XH Series)
Power Distribution Cabinet Grounding Layout
- Interface: RJ45 (100/1000 Mbps), composite RJ45 + optical fiber (Advanced 10 Gbps)
- Transmission Rate: 1000 Mbps (Standard), 10 Gbps (Advanced)
- Protection Level: ≤50 V (Standard), ≤30 V (Advanced)
- Response Time: ≤1 ns (Standard), ≤0.5 ns (Advanced)
- Compatibility: PoE, single/multi-mode optical fiber (Advanced)
- Operating Voltage: Adaptive 5 V / 12 V / 24 V
- Protection Grade: IP30
6.10 Insulation Pad / Insulation Board (KT-JY Series)
- Material: Polyurethane (pad), black industrial rubber (Standard board), high-density polyurethane (Advanced board)
- Dimensions: 100×100×5mm (pad), 1000×2000×8mm (Standard board), 1200×2400×10mm (Advanced board)
- Insulation Resistance: ≥100 MΩ (pad), ≥200 MΩ (Standard board), ≥500 MΩ (Advanced board)
- Withstand Voltage Strength: ≥5 kV (pad), ≥10 kV (Standard board), ≥15 kV (Advanced board)
- Characteristics: Moisture-proof, flame-retardant, anti-aging, anti-corrosion
- Operating Temperature: -30℃ ~ +80℃
6.11 Equipotential Connector (KT-LJ Series)
Integrated Equipment of Grounding System
- Current Capacity: 100 kA (Standard), 200 kA (Advanced)
- Trigger Voltage: ≤100 V (Standard), ≤50 V (Advanced)
- Insulation Resistance: ≥500 MΩ (Standard), ≥1000 MΩ (Advanced)
- Functions: Dual-mode isolation (normal) / conduction (fault), intelligent monitoring (Advanced)
- Operating Voltage: ≤1 kV
- Response Time: ≤100 ns
6.12 Grounding Resistance Monitor (KT-JC-01)
- Measuring Range: 0.01 Ω – 100 Ω
- Measuring Accuracy: ±1% (0.1 Ω – 10 Ω), ±2% (other ranges)
- Communication Interfaces: 4G, Ethernet, RS485
- Alarm Functions: Sound-light alarm with adjustable threshold
- Power Supply: 220 VAC / DC 12 V
- Operating Temperature: -20℃ ~ +60℃
7. Full Product Application Scope
7.1 Equipotential Copper Busbar
- Application Scenarios: Shielded computer rooms, data centers, precision laboratories, military facilities
- Functions: Build equipotential grids, connect shielding enclosures, cabinets and metal pipelines to eliminate potential differences
- Applicable Grades: All Basic / Standard / Advanced shielded rooms
7.2 Grounding Terminal Box
- Application Scenarios: Computer room walls, equipment rooms, grounding wells, equipotential convergence points
- Functions: Central convergence of grounding cables, provide reliable connection points for inspection and maintenance
- Applicable Grades: All Basic / Standard / Advanced shielded rooms
7.3 Copper Braided Strap
- Application Scenarios: Joints of shielding enclosures, cross-connection between cabinets and ground busbars, grounding of metal doors & windows, connection of high-frequency equipment
- Functions: High-frequency low-impedance cross-connection, discharge surface charges, guarantee shielding effectiveness
- Applicable Grades: Standard & Advanced shielded rooms (essential for high-frequency scenarios)
7.4 Yellow-Green Ground Cable
- Application Scenarios: Equipment grounding branch lines, grounding main line connections, anti-static grounding, protective grounding
- Functions: Conduct grounding current and provide reliable discharge channels
- Applicable Grades: All Basic / Standard / Advanced shielded rooms
7.5 Vertical Grounding Electrode / Horizontal Grounding Conductor
- Application Scenarios: Outdoor grounding grid, building foundation grounding, resistance reduction areas
- Functions: Construct grounding grid to discharge current into earth and reduce grounding resistance
- Applicable Grades: All Basic / Standard / Advanced shielded rooms
7.6 Grounding Module
- Application Scenarios: Areas with high soil resistivity (rock, sandy soil), scenarios hard to meet grounding resistance standards
- Functions: Powerful resistance reduction, stable grounding resistance, extend service life of grounding grid
- Applicable Grades: Standard & Advanced shielded rooms (essential for harsh soil conditions)
7.7 Resistance-Reducing Agent
- Application Scenarios: Backfill around grounding electrodes, high soil resistivity areas, grounding grid renovation
- Functions: Reduce grounding resistance, improve soil conductivity, protect grounding electrodes
- Applicable Grades: All Basic / Standard / Advanced shielded rooms (widely used in Standard & Advanced tiers)
7.8 Power SPD
- Application Scenarios: Main power distribution cabinets, UPS input/output terminals, precision air conditioners, row cabinets, front end of servers
- Functions: Graded discharge of lightning current and induced overvoltage to protect equipment from surge damage
- Applicable Grades: All Basic / Standard / Advanced shielded rooms (graded protection for Standard & Advanced tiers)
7.9 Signal Lightning Arrester
- Application Scenarios: Switches, servers, storage equipment, monitoring equipment, network ports
- Functions: Protect signal lines from induced overvoltage damage to network equipment
- Applicable Grades: Standard & Advanced shielded rooms (essential for network-dense scenarios)
7.10 Insulation Pad / Insulation Board
- Application Scenarios: Bottom of shielding enclosures, equipment bases, isolation between metal components and foundations
- Functions: Insulation isolation, block stray current, realize suspended grounding of shielding enclosures
- Applicable Grades: Standard & Advanced shielded rooms (essential for interference isolation)
7.11 Equipotential Connector
- Application Scenarios: Connection between shielding ground and lightning protection ground, isolation/conductivity of different grounding systems, equalization of fault potential
- Functions: Isolate under normal conditions, conduct under fault conditions to prevent ground potential counterattack
- Applicable Grades: Standard & Advanced shielded rooms (essential for combined grounding systems)
7.12 Grounding Resistance Monitor
- Application Scenarios: High-grade classified computer rooms, military laboratories, critical data centers
- Functions: Real-time grounding resistance monitoring, abnormal alarm, ensure stable operation of grounding system
- Applicable Grades: Advanced shielded rooms (essential for safety monitoring)
8. Full Product Advantages
8.1 Universal Core Advantages of Full Series
- Customized Design: Customizable product specifications and solutions based on room size, soil conditions and shielding grade to match diverse scenario demands.
- OEM & ODM Service: Support OEM/ODM customization including brand, specification and function to flexibly adapt to project requirements.
- Strict Confidentiality Mechanism: Strict confidentiality of project data, design drawings and technical parameters; non-disclosure agreements available to secure classified project information.
- In-Stock Supply: Regular specifications stocked in warehouse, delivery within 72 hours to shorten project cycles and meet urgent construction demands.
- Full-Series Supporting Products: Independent R&D and production covering equipotential connection, grounding main lines, grounding electrodes, lightning protection and insulation isolation; one-stop procurement with high compatibility.
- High-Performance Materials: Core components adopt high-purity copper, 316 stainless steel, superconducting graphite and other premium materials with excellent conductivity and long anti-corrosion service life.
- Low-Impedance Design: Short, straight and thick layout for grounding products to achieve low high-frequency impedance, efficiently discharge high-frequency interference current and guarantee shielding effectiveness.
- Standardized Production: Manufactured in compliance with ISO9001 quality management system and national standards, ensuring consistent and reliable product quality.
8.2 Functional Characteristics of Each Product
- Equipotential Copper Busbar: High-purity pure copper with superior conductivity; tin-plated anti-corrosion treatment for long service life; modular design for easy installation; M-type grid delivers excellent equipotential performance.
- Grounding Terminal Box: Stainless steel construction for water and dust resistance; multi-terminal design for convenient wiring; equipped with disconnection card for easy testing; Advanced tier integrated with monitoring module for real-time status tracking.
- Copper Braided Strap: Flexible multi-strand tin-plated copper wire; low high-frequency impedance for superior discharge performance; crimped copper lugs for reliable connection; wide temperature resistance for harsh environments.
- Yellow-Green Ground Cable: Flame-retardant material for safety; multi-strand oxygen-free copper with high conductivity; yellow-green dual-color complying with international safety standards; shielded type (Advanced tier) with strong anti-interference capability.
- Vertical Grounding Electrode / Horizontal Grounding Conductor: Hot-dip galvanized anti-corrosion treatment with strong corrosion resistance; complete specifications adaptable to various soil types; optional lengths for outstanding grounding performance; easy construction and low cost.
- Grounding Module: Superconducting graphite material delivers remarkable resistance reduction effect; stable long-term performance with long service life; adaptable to high soil resistivity; easy installation with zero maintenance required.
- Resistance-Reducing Agent: Eco-friendly and non-corrosive for safe application; ultra-low resistivity for optimal resistance reduction; stable long-term performance with long valid period; acid-alkali resistant for harsh soil environments.
- Power SPD: Graded comprehensive protection; large current capacity for powerful discharge; low voltage protection level to safeguard precision equipment; remote monitoring (Advanced tier) for intelligent operation and maintenance.
- **Signal Lightning Arrester: High-speed transmission without signal attenuation; fast response time for sensitive protection; abundant interfaces compatible with various equipment; PoE support for wide application scope.
- Insulation Pad / Insulation Board: Ultra-high insulation resistance for effective isolation; high withstand voltage for safety; moisture-proof and flame-retardant for harsh environments; easy installation and maintenance-free.
- **Equipotential Connector: Large current capacity for reliable conduction under fault conditions; low trigger voltage for rapid response; ultra-high insulation resistance for effective isolation under normal conditions; intelligent monitoring & remote alarm (Advanced tier).
- **Grounding Resistance Monitor: High-precision measurement for accurate data; wide measuring range adaptable to all grounding systems; remote communication for real-time monitoring; sound-light alarm for timely abnormal warnings.
8.3 Technical Parameter Advantages
- Grounding resistance can reach as low as ≤0.5 Ω, superior to the national standard of ≤1 Ω for low-resistance discharge guarantee.
- Copper products achieve conductivity ≥58 MS/m, close to pure copper conductivity for efficient current transmission.
- Copper braided strap impedance ≤5 mΩ @ 1 GHz for effective high-frequency interference discharge and stable shielding effectiveness.
- Terminal box maximum protection grade IP67, waterproof and dustproof for humid and dusty environments.
- Wide temperature resistance range of -55℃ ~ +150℃ with stable performance under extreme temperature conditions.
9. Bid-Winning Core Parameters of All Products (* Marked as Core Bid-Winning Items)
9.1 Equipotential Copper Busbar (KT-TP Series)
- *Material: High-purity T2 pure copper, conductivity ≥58 MS/m
- *Specification (Advanced Tier): 50mm×5mm, 6m per piece
- *Surface Treatment: Tin plating with thickness ≥5 μm
- Insulating Bracket: High-strength ABS, insulation resistance ≥100 MΩ
- Flame Retardant Grade: UL94 V-0
9.2 Grounding Terminal Box (KT-DBX Series)
- *Material (Advanced Tier): 316L stainless steel
- *Protection Grade (Advanced Tier): IP67
- *Wiring Terminals (Advanced Tier): 30 positions, silver-plated pure copper, rated current ≥200 A
- Additional Functions: Grounding resistance monitoring module, disconnection card
9.3 Copper Braided Strap (KT-BZ Series)
- *Material: Multi-strand tin-plated copper wire, single wire diameter ≥0.15mm
- *Cross-section (Advanced Tier): 35 mm²
- *High-Frequency Impedance (Advanced Tier): ≤5 mΩ @ 1 GHz
- DC Resistance: ≤0.02 mΩ
- Temperature Resistance: -55℃ ~ +150℃
9.4 Yellow-Green Ground Cable (KT-GX Series)
- *Model (Advanced Tier): ZR-VVP shielded cable
- *Cross-section (Advanced Tier): 50 mm²
- *Withstand Voltage Grade (Advanced Tier): 0.6/1 kV
- Conductor: Multi-strand oxygen-free copper, conductivity ≥58 MS/m
- Flame Retardant Standard: GB/T 18380.3, self-extinguishing after flame removal
9.5 Vertical Grounding Electrode (KT-JD Series)
- *Material: Hot-dip galvanized Q235B angle steel
- *Specification (Advanced Tier): 80×80×8mm
- *Length (Advanced Tier): 3.5m
- *Galvanized Layer Thickness (Advanced Tier): ≥120 μm
- Grounding Resistance: ≤10 Ω (soil resistivity ≤100 Ω·m)
9.6 Grounding Module (KT-MK Series)
- *Material (Advanced Tier): Superconducting graphite composite
- *Dimensions (Advanced Tier): 800×600×100mm
- *Grounding Resistance (Advanced Tier): ≤2 Ω
- *Resistance Reduction Rate (Advanced Tier): ≥85%
- Service Life (Advanced Tier): ≥30 years
9.7 Resistance-Reducing Agent (KT-JZ Series)
- *Type (Advanced Tier): Superconducting ionic type
- *Resistivity (Advanced Tier): ≤1 Ω·m
- *pH Value (Advanced Tier): 7–7.5
- *Valid Period (Advanced Tier): ≥30 years
- Characteristics: Eco-friendly, non-corrosive, acid-alkali resistant
9.8 Power SPD (KT-SPD Series)
- *Model (Advanced Class I): KT-SPD120
- *Waveform: 10/350 μs
- *Current Capacity (Advanced Class I): Iimp ≥40 kA
- *Voltage Protection Level (Advanced Class I): ≤2.0 kV
- Additional Functions: Remote monitoring, failure alarm
9.9 Signal Lightning Arrester (KT-SPD-XH Series)
- *Interface (Advanced Tier): Composite RJ45 + optical fiber
- *Transmission Rate (Advanced Tier): 10 Gbps
- *Protection Level (Advanced Tier): ≤30 V
- *Response Time (Advanced Tier): ≤0.5 ns
- Compatibility: Single/multi-mode optical fiber, PoE
9.10 Insulation Board (KT-JY Series)
- *Material (Advanced Tier): High-density polyurethane
- *Dimensions (Advanced Tier): 1200×2400×10mm
- *Insulation Resistance (Advanced Tier): ≥500 MΩ
- *Withstand Voltage Strength (Advanced Tier): ≥15 kV
- Characteristics: Moisture-proof, flame-retardant, anti-aging
9.11 Equipotential Connector (KT-LJ Series)
- *Current Capacity (Advanced Tier): 200 kA
- *Trigger Voltage (Advanced Tier): ≤50 V
- *Insulation Resistance (Advanced Tier): ≥1000 MΩ
- Functions: Intelligent monitoring, remote alarm
9.12 Grounding Resistance Monitor (KT-JC-01)
- Measuring Range: 0.01 Ω – 100 Ω
- Measuring Accuracy: ±1% (0.1 Ω – 10 Ω)
- Communication Interfaces: 4G, Ethernet
- Alarm Functions: Sound-light alarm with adjustable threshold
10. Full Product Solutions
10.1 Solution for Small Non-Classified Shielded Room (Basic Tier)
- Requirements: Grounding resistance ≤4 Ω, shielding effectiveness ≥80 dB, limited budget, basic electromagnetic protection
- Configuration: 30×3mm equipotential copper busbar, IP54 grounding terminal box, 16 mm² copper braided strap, 25 mm² yellow-green ground cable, 50×50×5mm vertical grounding electrodes, Basic-tier grounding modules & resistance-reducing agent, Class II power SPD, insulation pads
- Solution Highlights: Adopt S-type star single-point grounding with ring-shaped equipotential copper busbar layout; build outdoor grounding grid with 6 vertical grounding electrodes + horizontal conductors; basic lightning protection to meet non-classified scenario demands.
10.2 Solution for Medium-Sized Classified / Financial Shielded Room (Standard Tier)
- Requirements: Grounding resistance ≤1 Ω, shielding effectiveness ≥100 dB, classified scenarios, medium-grade electromagnetic protection, graded lightning protection
- Configuration: 40×4mm equipotential copper busbar, IP65 grounding terminal box, 25 mm² copper braided strap, 35 mm² yellow-green ground cable, 60×60×6mm vertical grounding electrodes, Standard-tier grounding modules & resistance-reducing agent, Class I + Class II power SPDs, signal lightning arresters, insulation boards, equipotential connectors
- Solution Highlights: S-M hybrid grounding balancing single-point reference and multi-point redundancy; grid-shaped equipotential copper busbar laid around room perimeter and under raised floor; outdoor grounding grid with 8 vertical electrodes + pure copper horizontal conductors; resistance reduction via grounding modules and resistance-reducing agent; graded power & signal lightning protection; full insulation at shielding enclosure bottom, combined grounding to prevent ground potential counterattack.
10.3 Solution for Large Military / High-Precision Shielded Room (Advanced Tier)
- Requirements: Grounding resistance ≤0.5 Ω, shielding effectiveness ≥120 dB, military/high-precision test scenarios, advanced electromagnetic protection, intelligent monitoring
- Configuration: 50×5mm equipotential copper busbar, IP67 monitoring-type grounding terminal box, 35 mm² high-frequency copper braided strap, 50 mm² shielded yellow-green ground cable, 80×80×8mm vertical grounding electrodes, Advanced-tier superconducting grounding modules & ionic resistance-reducing agent, Class I + II + III graded power SPDs, 10 Gbps signal lightning arresters, high-grade insulation boards, intelligent equipotential connectors, grounding resistance monitor
- Solution Highlights: M-type mesh grounding for low high-frequency impedance; six-sided full-grid equipotential copper busbar; closed-loop pure copper outdoor grounding grid with 12 vertical electrodes; powerful resistance reduction via superconducting modules and ionic agent; three-level refined power lightning protection + 10 Gbps signal lightning protection; suspended insulation of shielding enclosures; real-time grounding resistance monitoring with remote alarm to guarantee long-term stable system operation.
11. Full Product Application Cases
11.1 Classified Government Computer Room Project of Provincial Government (Standard Tier)
- Project Scale: 200 ㎡ shielded room, Class B classified level
- Core Requirements: Grounding resistance ≤1 Ω, shielding effectiveness ≥100 dB, combined grounding, graded lightning protection
- Configuration Scheme: KITOZER Standard-tier grounding system (40×4mm copper busbar, IP65 terminal box, 25 mm² braided strap, Class I + II SPDs, signal lightning arresters, insulation boards, equipotential connectors)
- Implementation Effect: Measured grounding resistance 0.8 Ω (meeting ≤1 Ω standard); shielding effectiveness 105 dB compliant with classified standards; stable system operation for 3 years without electromagnetic leakage or interference faults.
11.2 Electromagnetic Shielding Laboratory Project of Military Research Institute (Advanced Tier)
- Project Scale: 500 ㎡ military-grade shielding laboratory, shielding effectiveness ≥120 dB
- Core Requirements: Grounding resistance ≤0.5 Ω, low high-frequency impedance, intelligent monitoring, stable performance under extreme environments
- Configuration Scheme: KITOZER Advanced-tier grounding system (50×5mm copper busbar, IP67 monitoring terminal box, 35 mm² high-frequency braided strap, three-level SPDs, 10 Gbps signal lightning arresters, high-grade insulation boards, intelligent equipotential connectors, grounding resistance monitor)
- Implementation Effect: Measured grounding resistance 0.3 Ω (exceeding ≤0.5 Ω standard); impedance ≤5 mΩ @ 1 GHz; shielding effectiveness 125 dB meeting military standards; stable real-time monitoring system without abnormal alarms.
11.3 Shielded Computer Room Project of Bank Data Center (Standard Tier)
- Project Scale: 300 ㎡ financial data center shielded room, Tier III grade
- Core Requirements: Grounding resistance ≤1 Ω, anti-static & anti-electromagnetic interference, guarantee financial data security
- Configuration Scheme: KITOZER Standard-tier grounding system (40×4mm copper busbar, IP65 terminal box, 25 mm² braided strap, Class I + II SPDs, signal lightning arresters, insulation boards)
- Implementation Effect: Measured grounding resistance 0.9 Ω complying with standards; reliable anti-static grounding without static accumulation; significant electromagnetic interference suppression for stable equipment operation without data transmission errors.
11.4 Precision Test Laboratory Project of University (Basic Tier Upgrade)
- Project Scale: 100 ㎡ precision test laboratory, aging original grounding system requiring renovation
- Core Requirements: Grounding resistance ≤1 Ω, low-cost renovation, rapid implementation
- Configuration Scheme: KITOZER Basic-tier grounding system (30×3mm copper busbar, IP54 terminal box, 16 mm² braided strap, Class II SPDs, grounding modules, resistance-reducing agent)
- Implementation Effect: Measured grounding resistance 0.9 Ω after renovation meeting standards; 7-day short renovation cycle with low cost; stable 2-year operation satisfying electromagnetic environment demands for precision testing.
12. Product Faults & Maintenance Plan
12.1 Common Faults & Solutions
12.1.1 Excessive Grounding Resistance (>4 Ω / >1 Ω / >0.5 Ω)
- Fault Causes: Corroded grounding electrodes, dry soil, leached resistance-reducing agent, loose grounding connections
- Solutions: Inspect and replace severely corroded electrodes; water soil and supplement resistance-reducing agent; fasten all grounding connection points and remove oxide layers.
12.1.2 Declined Shielding Effectiveness
- Fault Causes: Broken copper braided strap, loose cross-connections, damaged insulation, ground loop interference
- Solutions: Replace broken braided straps; re-fasten cross-connection points for reliable contact; repair damaged insulation boards/pads; optimize equipotential connections to eliminate ground loops.
12.1.3 Frequent SPD Alarms / SPD Damage
- Fault Causes: Frequent surge overvoltage, aging SPD, poor grounding, mismatched model selection
- Solutions: Replace aging SPDs; inspect grounding system to ensure reliable grounding; recalculate surge level and replace with matched SPD models.
12.1.4 Static Interference to Equipment
- Fault Causes: Loose anti-static grounding, undersized grounding cable cross-section, damaged insulation
- Solutions: Fasten anti-static grounding connections; replace large cross-section grounding cables; repair damaged insulation components.
12.1.5 Water Infiltration / Corrosion of Grounding Terminal Box
- Fault Causes: Insufficient protection grade, low installation position, aging sealing strips
- Solutions: Replace terminal boxes with higher protection grade; relocate to dry areas; replace sealing strips and reinforce waterproof treatment.
12.2 Maintenance Schedule
12.2.1 Daily Maintenance (Monthly)
- Inspect grounding terminal box: Intact appearance, tight sealing, no water ingress or corrosion, loose/oxidized terminals prohibited
- Inspect grounding cables: No damage or aging, reliable connections, clear yellow-green color marking
- Inspect SPDs: Normal indicator light, no alarms or burn marks
- Inspect insulation components: No damage, aging or moisture.
12.2.2 Quarterly Maintenance (Every 3 Months)
- Measure grounding resistance with tester, record data and compare with standard values; resolve over-limit issues promptly
- Fasten all connection points (copper busbars, braided straps, grounding cables, terminal lugs), remove oxide layers for reliable contact
- Excavate and inspect corrosion of grounding electrodes; replace severely corroded electrodes
- Check resistance-reducing agent and replenish leached material to maintain resistance reduction performance.
12.2.3 Annual Maintenance (Once per Year)
- Comprehensive testing: Grounding resistance, shielding effectiveness, SPD protection level, insulation resistance; issue official test report
- In-depth maintenance: Replace aging components (SPDs, braided straps, insulation boards); conduct anti-corrosion treatment on grounding electrodes and grid; clean dust and debris inside terminal boxes
- System optimization: Adjust grounding system configuration based on test results to improve performance.
12.2.4 Long-Term Maintenance (Every 5 Years)
- Grounding Grid Renovation: Replace aging vertical/horizontal grounding conductors; re-lay resistance-reducing agent; optimize grounding grid layout
- Equipment Upgrade: Update SPDs, lightning arresters and grounding resistance monitors to comply with latest technical standards
- Comprehensive Performance Evaluation: Assess overall grounding system performance and formulate 5-year follow-up maintenance plan.
13. Factory Strength & After-Sales Service
13.1 Factory Strength
- Production Base: KITOZER owns two production bases in Guangzhou and Jiangsu with total area of 20,000 ㎡, including 15,000 ㎡ modern workshops, annual output exceeding 1,000 sets of shielded room grounding systems.
- R&D Team: 20+ professional R&D personnel including 5 senior engineers and 3 electromagnetic protection experts focusing on shielded room grounding and electromagnetic protection equipment, holding over 10 national patents.
- Production Equipment: Import advanced German copper busbar processing equipment, automatic welding machines and precision testing instruments to realize automated refined production with consistent reliable product quality.
- Quality System: Certified by ISO9001 Quality Management System, ISO14001 Environmental Management System and CE; manufactured strictly in accordance with national standards GB50174, GB/T50719 for full compliance.
- Supply Chain: Core raw materials (high-purity copper, 316 stainless steel, superconducting graphite) sourced from well-known domestic & overseas brands for stable quality and sufficient supply to guarantee product performance and delivery schedule.
- Project Experience: Over 10 years of industry experience serving military, classified government, financial, education and medical sectors; completed more than 1,000 projects with rich experience in design, construction and operation & maintenance.
13.2 After-Sales Service
Pre-Sales Service
- Free on-site survey; customized personalized solutions based on room size, soil conditions and shielding grade
- Provide complete technical parameters, configuration lists and construction drawings
- Dedicated technical team to answer all technical inquiries throughout the project cycle.
In-Sales Service
- Professional construction team provides on-site installation guidance to guarantee construction quality
- Strictly implement construction drawings and technical specifications to ensure system performance
- Real-time communication during construction to resolve on-site problems timely.
After-Sales Service
- Warranty Period: All products covered under 3-year full warranty; free repair & replacement of non-artificially damaged components within warranty; core components (grounding modules, resistance-reducing agent) covered by 10-year warranty.
- Response Time: 7×24-hour technical support hotline; response within 1 hour, solution provided within 4 hours, on-site service within 24 hours nationwide.
- Regular Return Visits: Quarterly follow-up visits during warranty period to track system operation and provide maintenance suggestions; free annual on-site inspection with test report issuance.
- Lifetime Maintenance: Lifetime maintenance service after warranty expiration with only material cost charged; technical upgrade and system renovation available for long-term stable system operation.
- Training Service: Free operation & maintenance training for customers covering system principles, operation methods, fault handling and maintenance standards to enable independent operation and troubleshooting.
14. Conclusion
The grounding system of shielded computer rooms serves as core infrastructure to guarantee electromagnetic shielding performance, stable equipment operation and data security. Its design, construction and maintenance quality directly determine the overall performance of shielded rooms.
KITOZER series shielded room grounding systems are developed based on over 10 years of industry experience and advanced technologies, complying with national standards and launching three tiers of customized solutions for diverse scenarios. The products feature high performance, reliability, stability and easy maintenance.
Manufactured with premium materials and advanced craftsmanship under strict quality control, the products fully comply with GB50174 and GB/T50719 national standards, achieving minimum grounding resistance ≤0.5 Ω and maximum shielding effectiveness ≥120 dB to meet high-security demands of military, classified government, financial, education and medical industries.
Comprehensive pre-sales, in-sales and after-sales services are provided covering solution design, construction guidance, after-sales maintenance and technical training to fully support customers and ensure long-term stable system operation.
In the future, KITOZER will continue to focus on shielded room grounding and electromagnetic protection fields, increase R&D investment, optimize product performance and upgrade service quality to deliver more high-quality, efficient and reliable grounding system solutions, supporting the digital and informatization security construction of all industries.
15. Search Keywords, SEO & Tags
15.1 Search Keywords
- Core Keywords: Shielded Computer Room Grounding System, KITOZER Grounding System, Shielded Room Grounding Solution, Classified Computer Room Grounding, Military Shielded Room Grounding