Table of Contents
ToggleI. System Introduction
1.1 System Overview
Tower UPS is an independently floor-standing uninterruptible power supply system, designed to deliver high-quality and non-stop power protection for server rooms, data centers and critical equipment. Adopting online double-conversion topology, KITOZER Tower UPS realizes seamless switching between mains power and battery power (0ms) via core modules including rectifier, inverter, energy storage and static bypass. It supplies pure, stable and continuous power to IT devices, precision instruments and control systems, and effectively isolates power grid anomalies such as voltage fluctuation, harmonic interference, transient voltage and power outage.
1.2 Working Principle
The core operating process of KITOZER Tower UPS is as follows:
- Normal Mains Mode: Utility AC power is converted into DC power by the rectifier. Part of the DC power maintains float charging of the battery bank, while the rest is inverted into pure sine-wave AC power to supply loads.
- Battery Discharge Mode: Once mains power fails, the battery bank immediately feeds power to loads through the inverter. The switching time is less than 2ms, ensuring imperceptible power change for connected devices.
- Bypass Mode: The system automatically switches to static bypass when the UPS malfunctions or overloads, so loads are powered directly by mains to sustain normal operation.
- Maintenance Bypass: Manual switch to maintenance bypass is supported to facilitate UPS servicing without cutting power to loads.
1.3 System Features
- Fully digital control: Equipped with DSP digital signal processor for precise control and intelligent management.
- Wide input voltage range: Adaptable to harsh power grid conditions, reducing frequent battery discharge and extending battery service life.
- High efficiency & energy saving: Efficiency reaches up to 95% under mains mode, and over 98% under ECO mode.
- Intelligent monitoring: Built-in LCD display, remote monitoring, fault early warning and automatic protection functions.
- Flexible expansion: Battery bank expansion is available to meet different backup runtime requirements.

II. System Composition
The KITOZER Tower UPS system consists of the following core components to build a comprehensive power guarantee system:
| Component Name | Function Description | Core Technical Features |
|---|---|---|
| UPS Main Unit | Core of the system, realizes power conversion and uninterrupted power supply | Online double-conversion topology, full DSP digital control, IGBT power devices |
| Battery Bank | Energy storage unit, provides power when mains fails | VRLA lead-acid batteries or lithium batteries; hot-swap expansion supported |
| Battery Cabinet | Mounting and protection device for battery bank | Designed with ventilation, heat dissipation, fire prevention and short-circuit protection |
| Input & Output Power Distribution | Power distribution and protection | Circuit breakers, surge protectors and contactors; provides overcurrent, short circuit and surge protection |
| Monitoring System | Real-time monitoring and remote management | Supports RS232/RS485, SNMP and Modbus protocols; Web/SNMP monitoring available |
| Environment Monitoring | Monitors server room temperature, humidity, smoke and access control | Linked with UPS system to issue early warnings for environmental anomalies |
| Cables & Connection Accessories | Power transmission and signal connection | Flame-retardant cables and aviation connectors for safe and reliable connection |

III. System Classification
3.1 Classification by Power Rating
| Power Level | Application Scenarios | Typical Models |
|---|---|---|
| Low Power (1–10kVA) | Small server rooms, server cabinets, network devices | KITOZER KT1K–KT10K Series |
| Medium Power (10–40kVA) | Medium-sized data centers, enterprise server rooms, precision laboratories | KITOZER KT10K–KT40K Series |
| High Power (40–200kVA) | Large data centers, cloud computing centers, industrial control systems | KITOZER KT40K–KT200K Series |
3.2 Classification by Circuit Topology
- High-Frequency Tower UPS
- No output transformer; compact size, light weight and high efficiency (above 95%).
- Ideal for space-limited server rooms with stable loads.
- The full KITOZER series adopts high-frequency design for energy conservation and environmental friendliness.
- Power-Frequency Tower UPS
- Built-in output isolation transformer with strong anti-impact capability and high reliability.
- Suitable for industrial environments and scenarios with high proportion of inductive and non-linear loads.
- Power-frequency models are optional for KITOZER KT series.
3.3 Classification by Phase
| Phase Type | Input & Output | Application Scenarios |
|---|---|---|
| Single-Phase Input / Single-Phase Output | 220VAC | Low-power UPS (1–10kVA), office server rooms, small network devices |
| Three-Phase Input / Single-Phase Output | 380VAC input, 220VAC output | Medium-power UPS (10–20kVA), server clusters, precision instruments |
| Three-Phase Input / Three-Phase Output | 380VAC | High-power UPS (above 20kVA), data centers, industrial control systems |

IV. System Configuration List (KITOZER)
4.1 Standard Configuration (10kVA Example)
| No. | Device Name | Model | Specifications | Qty | Remarks |
|---|---|---|---|---|---|
| 1 | Tower UPS Main Unit | KITOZER KT10K | 10kVA/8kW, online double-conversion, 380V input, 220V output | 1 Unit | With LCD display and RS485 communication port |
| 2 | Valve-Regulated Lead-Acid Battery | KITOZER KTB12100 | 12V/100Ah, maintenance-free | 16 Cells | Approx. 30-minute backup runtime |
| 3 | Battery Cabinet | KITOZER KTC16 | 19-inch standard cabinet, holds 16pcs 12V batteries | 1 Set | Equipped with battery cables and ventilation system |
| 4 | Input Distribution Cabinet | KITOZER KTP-100A | 100A input circuit breaker, surge protection module | 1 Unit | Matches 10kVA UPS |
| 5 | Output Distribution Cabinet | KITOZER KTP-80A | 80A output circuit breaker, 4 output circuits, overload protection | 1 Unit | Matches 10kVA UPS |
| 6 | Monitoring Module | KITOZER KTM-01 | Supports RS232/RS485 and SNMP protocols | 1 Set | With monitoring software for remote management |
| 7 | Connecting Cables | KITOZER KTC-350+125 | Copper core, flame-retardant, 350mm²+125mm² | 1 Set | For input and output connection |
| 8 | Installation Accessories | KITOZER KTA-01 | Brackets, screws and user manual | 1 Set | Complete installation fittings |
4.2 Optional Configuration
| No. | Device Name | Model | Function | Application Scenarios |
|---|---|---|---|---|
| 1 | Lithium Battery Bank | KITOZER KTL12100 | 12V/100Ah lithium battery, long cycle life | Scenarios requiring long backup runtime and frequent discharge |
| 2 | Environment Monitoring Unit | KITOZER KTE-01 | Monitors temperature, humidity, smoke and access status | Server room environment monitoring and linked alarm |
| 3 | Remote Management Card | KITOZER KTR-01 | Supports Web/SNMP remote monitoring | Unattended server rooms and centralized management |
| 4 | Parallel Module | KITOZER KTP-02 | Enables parallel operation of multiple UPS units | High-reliability requirements, N+1 redundant design |
| 5 | Battery Inspection Tester | KITOZER KTB-01 | Real-time status monitoring for each single battery | Long battery strings requiring refined management |
V. System Schematic Diagram
Mains Input (380V/220V) ────┐
│
Input Circuit Breaker
│
Surge Protection Module
│
Input Filter
│
┌───────────────────────────┴───────────────────────────┐
│ KITOZER Tower UPS Main Unit │
│ ┌─────────┐ ┌─────────┐ ┌─────────────┐ │
│ │ Rectifier│─────▶│ Inverter│─────▶│ Output Filter│ │
│ └─────────┘ └─────────┘ └─────────────┘ │
│ │ ▲ │
│ │ │ │
│ ▼ │ │
│ ┌─────────┐ ┌─────────┐ ┌─────────────┐ │
│ │ Charger │─────▶│Battery │─────▶│Static Bypass │ │
│ └─────────┘ └─────────┘ └─────────────┘ │
│ ▲ ▲ │
│ │ │ │
│ Battery Cabinet Maintenance Bypass Switch │
└───────────────────────────┬───────────────────────────┘
│
Output Circuit Breaker
│
Load Distribution Cabinet
│
┌──────────┬──────────┬──────────┬──────────┐
│Server Racks│Network Devices│Storage Devices│Precision Instruments│
└──────────┴──────────┴──────────┴──────────┘
5.1 Operating Modes
- Normal Mode: Mains → Rectifier → Inverter → Load; the battery is float-charged simultaneously.
- Battery Discharge Mode: Battery → Inverter → Load; automatic switchover within 2ms when mains fails.
- Bypass Mode: Mains → Static Bypass → Load; activated automatically upon UPS fault or overload.
- Maintenance Mode: Mains → Maintenance Bypass → Load; manual switchover for UPS maintenance.
- Parallel Operation Mode: Multiple UPS units connected via parallel modules for load sharing and redundant backup.

VI. Product Technical Parameters (KITOZER KT Series)
6.1 Basic Parameters
| Parameter | KT1K–KT10K (Single-Phase) | KT10K–KT40K (Three-Phase) | KT40K–KT200K (Three-Phase) |
|---|---|---|---|
| UPS Type | Tower, Online Double-Conversion | Tower, Online Double-Conversion | Tower, Online Double-Conversion |
| Rated Capacity | 1–10kVA | 10–40kVA | 40–200kVA |
| Rated Power | 0.8–8kW | 8–32kW | 32–160kW |
| Input Voltage | 220VAC±25% | 380VAC±20% | 380VAC±15% |
| Input Frequency | 50Hz±10% | 50Hz±5% | 50Hz±3% |
| Input Power Factor | ≥0.98 | ≥0.98 | ≥0.99 |
| Input Current THD | ≤5% | ≤3% | ≤2% |
| Output Voltage | 220VAC±1% | 380VAC±1% | 380VAC±0.5% |
| Output Frequency | 50Hz±0.1% | 50Hz±0.05% | 50Hz±0.01% |
| Output Waveform | Sine wave, THD<2% (Linear Load) | Sine wave, THD<2% (Linear Load) | Sine wave, THD<1% (Linear Load) |
| Switching Time | 0ms (Double-Conversion) | 0ms (Double-Conversion) | 0ms (Double-Conversion) |
| Efficiency (Mains Mode) | ≥93% | ≥94% | ≥95% |
| Efficiency (ECO Mode) | ≥97% | ≥98% | ≥98.5% |
| Overload Capability | 125% load for 10 mins, 150% load for 1 min | 125% load for 10 mins, 150% load for 1 min | 125% load for 10 mins, 150% load for 1 min |
| Battery Type | VRLA Lead-Acid / Lithium Battery | VRLA Lead-Acid / Lithium Battery | VRLA Lead-Acid / Lithium Battery |
| Backup Runtime | Standard 5–15 mins, expandable | Standard 10–30 mins, expandable | Standard 15–60 mins, expandable |
| Communication Ports | RS232/RS485, SNMP optional | RS232/RS485, SNMP | RS232/RS485, SNMP, Modbus |
| Display | LCD, Chinese Interface | LCD, Chinese Interface | Color LCD Touch Screen, Chinese Interface |
| Dimensions (W×D×H) | 450×600×800mm | 600×800×1000mm | 800×1000×1200mm |
| Weight | 50–150kg | 150–300kg | 300–800kg |
| Operating Environment | 0–40℃, 20%–90% RH (Non-condensing) | 0–40℃, 20%–90% RH (Non-condensing) | 0–40℃, 20%–90% RH (Non-condensing) |
| Noise | <55dB @ 1m | <60dB @ 1m | <65dB @ 1m |
6.2 Protection Parameters
| Protection Type | Protection Standard | Protection Action |
|---|---|---|
| Overvoltage Protection | Output >115% rated voltage | Switch to bypass and trigger alarm |
| Undervoltage Protection | Output <85% rated voltage | Switch to bypass and trigger alarm |
| Overload Protection | 105%–125% load: 10 mins125%–150% load: 1 min>150% load: 0.5 sec | Alarm first, then switch to bypass |
| Short Circuit Protection | Output short circuit | Immediately cut off output and alarm |
| Overtemperature Protection | Internal temp. >85℃ | Derate operation; shut down if temperature keeps rising |
| Battery Overcharge Protection | Battery voltage >13.8V per cell | Stop charging and alarm |
| Battery Overdischarge Protection | Battery voltage <10.5V per cell | Cut off output and alarm |
| Surge Protection | Compliant with IEC 61000-4-5 | Discharge surge current to protect devices |
VII. Application Scope
KITOZER Tower UPS provides reliable power protection for critical equipment in the following scenarios:
7.1 Data Centers & Server Rooms
- Enterprise data centers: Servers, storage devices, network switches and other core IT equipment
- Cloud computing centers: Large-scale server clusters requiring high reliability and availability
- Edge computing nodes: Distributed small server rooms with independent power demand
- Financial institution server rooms: Core business systems of banks, securities and insurance industries requiring zero-interruption power supply
7.2 Government & Public Sectors
- Government cloud platforms: E-government systems to ensure continuous public services
- Medical institutions: Operating room devices, ICU monitoring systems and medical imaging equipment
- Education & Research: University laboratories, research equipment and supercomputers
- Energy industry: Power dispatching centers, substation automation systems and new energy monitoring platforms
7.3 Industry & Manufacturing
- Automated production lines: PLC systems, robots and precision processing equipment
- Petrochemical industry: DCS and Safety Instrumented Systems (SIS)
- Semiconductor manufacturing: Cleanroom control and wafer processing equipment
- Automotive manufacturing: Body welding, painting and assembly line control systems
7.4 Commerce & Service Industry
- Hotel chains: Hotel management, guest room control and security monitoring systems
- Shopping malls: POS systems, central air conditioning and security systems
- Radio & Television: Broadcasting, transmitting and editing room equipment
- Transportation: Dispatching systems and security inspection devices at airports, railway stations and metro stations
VIII. Product Advantages
8.1 Performance Advantages
- Zero-interruption power supply: Online double-conversion design with 0ms switching time for transparent power changeover.
- Pure power output: Voltage stability ±1%, frequency stability ±0.1%, THD<2%, ideal for precision devices.
- Wide input range: Tolerates severe grid fluctuations, reduces battery discharge frequency and extends service life.
- High efficiency & energy saving: Up to 95% efficiency in mains mode and over 98% in ECO mode to cut operational costs.
8.2 Reliability Advantages
- Full digital control: DSP chip ensures precise control and self-diagnosis to improve system reliability.
- Redundant key components: Redundant design for power modules and fans eliminates single points of failure.
- Intelligent battery management: Supports charge-discharge management, temperature compensation and overcharge/overdischarge protection.
- Comprehensive protection: Full-range safeguards against overvoltage, undervoltage, overload, short circuit and overtemperature.
8.3 Management Advantages
- Intelligent monitoring: LCD displays real-time operating data; remote monitoring and fault warning available.
- Multiple communication ports: RS232/RS485, SNMP, Modbus for connection with DCIM systems.
- Remote operation: Web access and mobile APP monitoring support unattended O&M.
- Event recording & analysis: Historical data storage for fault tracing and performance evaluation.
8.4 Deployment Advantages
- Floor-standing installation: No cabinet required, flexible for various server room layouts.
- Easy installation: Modular structure shortens deployment cycle.
- Convenient maintenance: Front access design for easy component replacement.
- Flexible expansion: Battery bank expandable to meet different backup runtime demands.
IX. Bid Specification Parameters
9.1 Core Technical Parameters (★ Mandatory Items)
| Bid Item | Technical Requirement | Remarks |
|---|---|---|
| ★ UPS Type | Tower type, online double-conversion topology; high-frequency model (no output transformer) or power-frequency model (with output transformer) | Product manual required for verification |
| ★ Rated Capacity | No less than [XX]kVA/[XX]kW | Fill according to project demands |
| ★ Input Voltage Range | 380VAC±20% (Three-Phase) / 220VAC±25% (Single-Phase) | Test report required |
| ★ Output Voltage Stability | ±1% (Steady load), ±3% (Dynamic load) | Test report required |
| ★ Switching Time | 0ms (Double-conversion mode); bypass switching time <2ms | Technical white paper required |
| ★ Efficiency | ≥94% in mains mode, ≥97% in ECO mode | Third-party test report required |
| ★ Output THD | ≤2% for linear loads, ≤5% for non-linear loads | Test report required |
| ★ Overload Capability | 125% load for 10 minutes, 150% load for 1 minute | Technical datasheet required |
| ★ Battery Management | Equipped with battery temperature compensation, overcharge/overdischarge protection and cell inspection function | Function description required |
| ★ Communication Ports | At least RS485 and SNMP ports; Web monitoring supported | Port list required |
| ★ Protection Functions | Multiple protections including overvoltage, undervoltage, overload, short circuit, overtemperature and surge protection | Protection list required |
| ★ Certifications | CE, UL, ISO9001, ISO14001 | Copies of certificates required |
9.2 Commercial Bid Requirements
| Bid Item | Requirement | Remarks |
|---|---|---|
| Brand Qualification | Bidder brand has more than [XX] years of UPS manufacturing experience; business license and project references required | Relevant documents required |
| After-sales Service | [XX] years warranty; on-site response within [XX] hours and arrival within [XX] hours | After-sales commitment letter required |
| Local Service | Local service center and spare parts warehouse available at project location | Address and contact information required |
| Training | Free technical training covering installation, commissioning and maintenance | Training plan required |
X. Product Solutions
10.1 Solution for Small & Medium Enterprise Server Rooms (10kVA)
Solution Overview
KITOZER KT10K Tower UPS (1+0 configuration) is recommended for small and medium enterprise server rooms with 30-minute backup runtime, meeting the demands of core business systems.
Configuration
- UPS Main Unit: KITOZER KT10K (10kVA/8kW), online double-conversion
- Battery Bank: 16pcs KITOZER KTB12100 (12V/100Ah), 30-minute backup
- Battery Cabinet: KITOZER KTC16, 19-inch standard cabinet
- Power Distribution: KITOZER KTP series distribution cabinets with surge protection
- Monitoring System: KITOZER KTM-01 monitoring module for remote management
Features
- Cost-effective, matching SME budget with reliable power guarantee.
- Fast deployment: Installation completed within 1–2 days.
- Intelligent remote monitoring reduces O&M workload.
- Expandable batteries or parallel UPS for business growth.
10.2 Solution for Large Data Centers (100kVA)
Solution Overview
KITOZER KT100K Tower UPS with 3+1 N+1 redundant configuration and 60-minute backup runtime is adopted for large data centers, complying with Tier III standards.
Configuration
- UPS Main Unit: 4pcs KITOZER KT100K (100kVA/80kW), 3+1 redundancy
- Battery Bank: 4 groups × 40pcs KITOZER KTB12200 (12V/200Ah)
- Battery Cabinet: 4pcs KITOZER KTC40 standard cabinets
- Power Distribution: KITOZER KTP series cabinets supporting parallel operation
- Monitoring System: KITOZER KTM-02 advanced monitoring module, connected to DCIM
- Environment Monitoring: KITOZER KTE-01 for temperature, humidity and smoke detection
Features
- N+1 redundancy eliminates single points of failure, meets Tier III requirements.
- Parallel operation realizes automatic load sharing and high system efficiency.
- Full monitoring for predictive maintenance.
- High efficiency lowers PUE and complies with green data center standards.
10.3 Solution for Industrial Control Systems (50kVA)
Solution Overview
KITOZER KT50K power-frequency Tower UPS is selected for industrial control systems. With built-in isolation transformer, it delivers strong anti-interference capability for harsh industrial environments.
Configuration
- UPS Main Unit: KITOZER KT50K power-frequency model (50kVA/40kW) with output isolation transformer
- Battery Bank: 32pcs KITOZER KTB12150 (12V/150Ah), 45-minute backup
- Battery Cabinet: 2pcs KITOZER KTC32, IP54 protection class
- Power Distribution: Industrial-grade KITOZER KTP cabinets with EMI/RFI filters
- Monitoring System: KITOZER KTM-01, Modbus protocol for SCADA connection
Features
- Output isolation transformer effectively isolates grid interference.
- Wide temperature adaptability (-10℃~50℃) and high protection grade.
- Compatible with inductive loads such as motors and inverters.
- Seamless connection with SCADA for industrial automatic management.
XI. Application Cases
11.1 Case 1: Data Center Renovation Project of XX Bank
Project Background
The existing UPS system of XX Bank’s data center was aging and needed upgrading to ensure continuous operation of core trading and credit systems.
Solution
- 3pcs KITOZER KT80K Tower UPS with 2+1 redundant configuration
- KITOZER KTB12200 battery banks for 60-minute backup runtime
- Connected to DCIM system for remote monitoring and management
- Deployed environment monitoring system for real-time temperature, humidity and smoke detection
Project Effects
- Stable operation for 2 years with zero faults, ensuring uninterrupted core business.
- System efficiency increased by 15%, saving about 800,000 RMB on electricity annually.
- Remote monitoring cuts on-site inspection workload by 70%.
- Complies with Level 3 Information Security Protection standards for banking systems.
11.2 Case 2: Automotive Production Line Automation Project of XX Automobile Manufacturer
Project Background
A new body welding production line required reliable power for PLC systems, robots and testing equipment to avoid shutdown caused by voltage fluctuations.
Solution
- 2pcs KITOZER KT50K power-frequency Tower UPS with 1+1 redundant configuration
- KITOZER KTB12150 battery banks for 45-minute backup runtime
- Installed KITOZER KTE-01 environment monitoring unit
- Connected to factory SCADA system for linkage with production line controls
Project Effects
- Production line operates stably without power-related shutdowns.
- Effectively isolates grid harmonics and transients, extending equipment service life.
- Equipment maintenance cost reduced by 30% and production efficiency improved.
- Fully meets high-reliability requirements of automotive automated production lines.
11.3 Case 3: Power Guarantee Project for ICU Wards of XX Hospital
Project Background
The newly built ICU ward required zero-interruption power for ventilators, patient monitors and infusion pumps to protect patients’ lives.
Solution
- 2pcs KITOZER KT20K Tower UPS with 1+1 redundant configuration
- KITOZER KTB12100 battery banks for 30-minute backup runtime
- KITOZER KTM-01 monitoring module with remote alarm function
- Linked with hospital emergency power system for automatic generator switchover
Project Effects
- 24-hour uninterrupted power supply for ICU critical devices.
- Zero switching interruption prevents medical accidents caused by power cuts.
- Remote monitoring enables timely fault handling and faster response.
- Complies with medical industry power supply specifications.
XII. Keywords, SEO & Tags
12.1 Search Keywords
Server room tower UPS solution, KITOZER tower UPS, online double-conversion UPS, data center UPS system, uninterruptible power supply solution, tower UPS configuration list, UPS system schematic, UPS bid parameters, green data center UPS, industrial UPS solution
12.2 SEO Optimization
- Title: Tower UPS Solution for Server Rooms (KITOZER) – Complete Technical Solution
- Description: KITOZER tower UPS solution including system introduction, composition, classification, configuration, schematic, parameters and application cases, providing reliable power protection for server rooms.
- Core Keywords: Server room UPS, tower UPS, KITOZER, uninterruptible power supply, data center power supply
12.3 Tags
#ServerRoomUPS #TowerUPS #KITOZER #UninterruptiblePowerSupply #DataCenter #PowerProtection #UPSSolution #BidParameters #GreenDataCenter #IndustrialUPS