KITOZER
KITOZER

Workshop Temperature, Humidity and Dust Online Monitoring System

Table of Contents

1. Cover / Document Information

– Document Title: Workshop Temperature, Humidity and Dust Online Monitoring System Technical Design Solution

– Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Date: August 2026

– Version: V1.0

– Project Type: Technical design solution for Workshop Temperature, Humidity and Dust Online Monitoring System

2. Table of Contents Structure

1. Company Introduction

2. Project Overview

3. User Requirement Analysis

4. Overall Design Description

5. Detailed System Design and Product Technical Parameters

6. Project Quotation and Configuration List

7. Core Solution Advantages

8. Technical Q&A

9. Construction Schedule Plan

10. Construction Organization Plan

11. After-Sales Service System

12. Operation and Maintenance Training Plan

13. Typical Project Cases

14. SEO Optimization System and Website Backend Configuration

15. Contact Information

3. Company Introduction

3.1 Company Development Overview

Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise dedicated to the computer room construction and intelligent protection field for more than two decades, integrating R&D, production, sales, engineering implementation and after-sales service. The company focuses on innovative breakthroughs in electromagnetic shielding technology, modular computer room technology and computer room environmental monitoring technology, and has grown into a source manufacturer with core competitiveness in the domestic computer room construction field.

After more than twenty years of industry accumulation, the company has built a large-scale production and manufacturing base equipped with advanced CNC sheet metal processing equipment, automated spraying production lines and professional testing laboratories, with an annual production capacity of hundreds of sets of shielding computer rooms, integrated cabinets and micro-module products. The company’s service network covers all provinces and cities across the country, providing thousands of computer room construction and renovation services for customers in government, military, scientific research, finance and enterprise fields.

3.2 Core Business System

The company’s core business revolves around the full-lifecycle construction of computer rooms, forming four major product and service systems:

– Computer room EPC general contracting service: one-stop services from solution design, manufacturing, on-site construction to commissioning and acceptance, covering shielding computer rooms, IDC data rooms, modular computer rooms, container computer rooms and other types;

– Core equipment R&D and production: independently produces KITOZER brand series products, including shielding cabinets, shielding desks, consoles, integrated data cabinets, micro-module cold aisle cabinets, outdoor rainproof cabinets, etc., supporting non-standard customization;

– Computer room environmental monitoring system: provides full-element monitoring solutions for temperature and humidity, water leakage, access control, video, fire protection, UPS and power distribution, realizing intelligent and unattended O&M;

– Shielding and security protection products: shielding rooms, shielding doors and windows, anechoic chambers and related auxiliary materials, widely used in confidential, military and scientific research fields.

3.3 Brand and Qualification Honors

The core brand KITOZER (Pioneer) focuses on computer room equipment and shielding products, positioned as an “efficient, green, innovative and safe” solution provider. Products have passed multiple authoritative tests and comply with national and industry standards. The company holds multiple utility model patents and software copyrights, has been awarded high-tech enterprise qualification, and follows the ISO9001 quality management standard.

3.4 Core Competitive Advantages

1. Source production, controllable quality: own production base and professional processing equipment; core products independently produced with full-process quality control, providing more cost-effective solutions without intermediate links;

2. Customized design, matching needs: tailor-made solutions per site conditions, technical requirements, configuration and budget, with multiple design options provided free of charge;

3. Professional team, rich experience: a professional technical team of engineers and project managers with more than ten years of industry experience;

4. Quality after-sales, full guarantee: a 7×24 professional online service system with dedicated project follow-up from early coordination to later O&M.

4. Project Background and Objectives

4.1 Project Background

In industrial production, workshop temperature, humidity and dust concentration directly affect product quality, equipment life and employee occupational health, and are core indicators of production safety and environmental compliance. Excessive dust causes occupational health problems (pneumoconiosis) and, in hardware, wood and chemical workshops, serious dust explosion risks; abnormal temperature/humidity affects precision machining accuracy, accelerates equipment corrosion and causes raw material deterioration; traditional manual inspection suffers from data lag, incomplete coverage and no real-time warning.

This project builds three independent temperature/humidity/dust monitoring units for three separate production workshops (each about 200㎡) plus one centralized monitoring platform, achieving real-time collection, intelligent analysis, over-limit alarms and data traceability of workshop environment parameters.

4.2 Construction Objectives

– Real-time monitoring: 24-hour online monitoring of air temperature, relative humidity, PM2.5, PM10 and TSP in each workshop with accurate reliable data;

– Intelligent alarms: multi-level threshold settings; over-limit parameters trigger on-site sound/light alarms and platform alarms;

– Centralized management: unified display, storage and management of three workshops’ data in the monitoring duty room, with zone viewing and comparative analysis;

– Data traceability: history storage ≥1 year, queries by time/zone/parameter, trend curves and statistical reports with export;

– Stable and reliable: industrial-grade hardware adapting to dusty, fluctuating-temperature, electromagnetic-interference workshop environments;

– Scalability: modular design for adding points and parameters (toxic gases, noise), compatible with enterprise platforms.

4.3 Construction Scope

Three independent workshops, each with a front-end monitoring unit, plus a centralized platform in the monitoring center: front-end sensing devices (temperature/humidity sensors, laser dust sensors); transmission and acquisition equipment (edge gateways, switches, cables); alarm and display equipment (sound/light alarms, industrial touch screens); monitoring center equipment (industrial host, platform software); supporting materials (distribution boxes, brackets, conduits, fittings); engineering services (installation, commissioning, training, acceptance, after-sales).

5. User Requirement Analysis

5.1 Basic Monitoring Requirements

– Each 200㎡ workshop fully covered, data representative of overall environment;

– Dust monitoring supporting PM2.5, PM10 and TSP simultaneously for occupational health and environmental compliance;

– Temperature/humidity range covering year-round fluctuations, industrial-grade accuracy, refresh ≥1/min.

5.2 Alarm Functional Requirements

– Local on-site alarm + remote platform alarm two-level mechanism;

– Flexibly settable thresholds per workshop process (upper, lower, rate-of-change modes);

– Alarm events fully recorded (time, location, value, handling status) for traceability and statistics;

– Alarm methods: sound/light, pop-up, sound; optional SMS/email.

5.3 Data Management Requirements

– Intuitive visualization: electronic map, data list, real-time curves;

– History queries by day/week/month/year with standardized reports (Excel/PDF export);

– Multi-user permission management for data security;

– ≥1 year full-parameter storage with expansion support.

5.4 Site Adaptation Requirements

– On-site devices dust/moisture resistant, protection ≥IP65;

– Power and signal with anti-interference for motor/welder electromagnetic environments;

– Simple installation and maintenance without affecting production;

– Mains power with power-off protection and no data loss.

5.5 Management and Expansion Requirements

– Three units operating independently or integrated into the platform;

– Future expansion of points and parameters without core equipment replacement;

– Standard data interfaces for MES/ERP integration.

6. Design Principles and Applicable Standards

6.1 Design Basis

– 《Hygienic Standards for the Design of Industrial Enterprises》GBZ 1-2010

– 《Occupational Exposure Limits for Hazardous Agents in the Workplace Part 1: Chemical Hazardous Agents》GBZ 2.1-2019

– 《Classification of Hazard Degrees in Dust Workplaces》GB/T 5817-2009

– 《Ambient Air Quality Standards》GB 3095-2012

– 《Code for Design of Low-Voltage Electrical Installations》GB 50054-2011

– 《Code for Construction and Acceptance of Cable Lines for Electrical Installation Works》GB 50168-2018

– 《Industrial Automation Networks – Modbus Protocol Specification》GB/T 19582-2008

– 《Information Security Technology – Baseline for Classified Protection of Cybersecurity》GB/T 22239-2019

– Relevant industry standards for industrial environment sensors; customer site and functional requirements

6.2 Design Principles

1. Advanced: mature laser scattering dust detection, edge computing and IoT platform technologies; industrial-grade imported chips;

2. Reliable: full-chain industrial-grade design, wide-temp wide-voltage power, photoelectric isolation, surge and ESD protection; distributed architecture (single device failure does not affect the whole); MTBF ≥30000h;

3. Practical: functions closely fit workshop management needs; simple interfaces; easy maintenance (cleaning, filter replacement by non-specialists);

4. Expandable: modular layered design, plug-and-play hardware, expandable parameters and multi-workshop cascade;

5. Economical: optimized configuration, source Manufacturer Supply, low power consumption, modular maintenance;

6. Safe: electrical safety per national standards (over-voltage/current/short-circuit/reverse protection), encrypted data transmission, graded permissions, lightning protection grounding.

7. System Architecture and Working Principle

7.1 System Architecture

Four-layer industrial IoT architecture:

– Perception layer: temperature/humidity sensors and pump-suction laser dust sensors per workshop point, RS485 Modbus-RTU digital output;

– Network transmission layer: RS485 bus (RVSP shielded twisted pair) to edge gateway per workshop → Ethernet to monitoring center switch → monitoring host;

– Platform service layer: environment monitoring platform software on the industrial host — data parsing, storage, computation, threshold comparison, alarms, permissions, reports;

– Application display layer: on-site industrial touch screens (local data view and settings) + monitoring center PC client/large screen (global monitoring, queries, management); optional mobile WEB/mini-program.

7.2 Working Principle

Sensors collect environment parameters → RS485 to edge gateway (validation, filtering, unit conversion, local cache) → Ethernet upload to monitoring center. The platform parses and displays data, stores history, compares thresholds — on over-limit, sends alarm commands to the gateway (relay triggers on-site sound/light alarm) and pops alarm windows with sound on the platform, recording alarm events. On network interruption, the gateway stores data locally and resumes upload on recovery (no data loss). Field staff view real-time data and alarm status via touch screens; managers use the platform for queries, reports and configuration.

8. Detailed Technical Design

8.1 Front-End Perception Layer Devices

#### 8.1.1 Industrial Temperature/Humidity Sensor (LA-WS100)

Parameter Value
Temperature -40℃~+120℃ (standard -20℃~+70℃); ±0.1℃ (0-50℃), ±0.3℃ full; 0.01℃ resolution; PT1000 Class A
Humidity 0-100%RH; ±1.5%RH (10-90%RH, 25℃), ±2%RH full; capacitive polymer film element
Response Temp T90 ≤5s; humidity T90 ≤8s; condensation recovery ≤30min
Electrical DC9-36V wide voltage, ≤0.5W; RS485 Modbus-RTU (03H/06H/10H); 1200-38400bps; 32 devices/bus; 1200m
Protection Surge ±2KV, ESD ±8KV contact/±15KV air, reverse protection; insulation ≥100MΩ; 1500VAC 1min
Mechanical ABS V0 housing, IP65, 110×85×42mm, ~180g, wall mount with 304 bracket, louvered vent probe
Environment -40℃~+85℃, 0-95%RH; vibration 10-500Hz 2g; EMC industrial level 3 (GB/T 17626)
Standards JB/T 7484-1994, GB/T 15768-1995; CE/ROHS/ISO9001; third-party calibration available

#### 8.1.2 Pump-Suction Laser Dust Sensor (LA-FC200)

– Principle: laser scattering with built-in micro diaphragm pump for active sampling — stable airflow, unaffected by external wind, far more accurate and consistent than diffusion sampling; detects PM2.5/PM10/TSP simultaneously;

– Measurement: PM2.5/PM10 0-10mg/m³ standard (custom to 100/1000mg/m³), TSP 0-20mg/m³ (custom to 500/1000mg/m³); accuracy ±10%FS; resolution 1μg/m³; indication error ≤±8%; repeatability ≤3%; zero drift ≤±2%FS/24h; particle range 0.3-100μm; T90 ≤10s; sampling flow 1.0L/min ±5%;

– Optics/air path: imported semiconductor laser 650nm 5mW (life ≥50000h), high-sensitivity silicon photodiode, blackened optical cavity, brushless diaphragm pump (life ≥10000h), PM10 cutter + primary dust filter, φ6mm quick-fit ports, detachable air path for cleaning;

– Electrical: DC12-24V, ≤2W sampling/≤0.5W standby; RS485 Modbus-RTU (or 4-20mA optional); TVS ±2KV on power/signal; ESD ±8KV/±15KV; over/under-voltage, over-current, reverse protection;

– Mechanical: aluminum die-cast housing, IP65, 160×110×60mm, ~650g, wall mount at 1.2-1.5m height;

– Environment: -20℃~+60℃; MTBF ≥30000h; filter replacement 3-6 months; annual calibration; CE/ROHS; optional explosion-proof (Ex ib IIC T4 Gb); GB/T 18204.2-2014, HJ 653-2013.

8.2 Data Acquisition and Transmission Layer

#### 8.2.1 Industrial Edge Gateway (LA-GW300)

– Per workshop: collects sensor data via RS485, performs validation, filtering and unit conversion, local cache storage, Ethernet upload with breakpoint resume; relay outputs for alarm control; supports Modbus-RTU/TCP; industrial-grade wide-temp operation.

#### 8.2.2 Industrial Gigabit Switch (LA-SW05)

– 5-port industrial gigabit switch at the monitoring center aggregating gateway data to the monitoring host; DIN-rail/wall mount, wide-temp, surge protection.

8.3 Alarm and On-Site Display Layer

#### 8.3.1 Industrial Sound/Light Alarm (LA-SG400)

– High-decibel buzzer + red strobe; relay triggered by gateway on over-limit; IP65; one per workshop at the entrance.

#### 8.3.2 7-Inch Industrial Touch Display (LA-DP500)

– One per workshop at the entrance: local real-time data view (temperature, humidity, PM2.5/PM10/TSP), alarm status, parameter settings; Ethernet to gateway; industrial touch screen.

#### 8.3.3 On-Site Distribution Box

– 400×300×200mm per workshop: centralized power supply with breaker, terminals and SPD for sensors, gateway and alarm.

8.4 Central Monitoring Center

#### 8.4.1 Industrial Monitoring Host (LA-IPC-610)

– Industrial PC (i5/8G/256G SSD + 2T HDD), fanless/low-noise, industrial chassis, wide-temp, MTBF high — running the platform software.

#### 8.4.2 Environment Monitoring Platform Software (V1.0 Enterprise)

– Real-time display (electronic map, lists, curves), threshold alarms (local + platform), history storage ≥1 year with reports (daily/weekly/monthly, Excel/PDF), multi-user permissions, system configuration, expansion interfaces (Modbus/TCP, API for MES/ERP); optional mobile WEB/mini-program.

8.5 Installation Auxiliaries

– 304 stainless sensor brackets (12); RVSP 2×1.0mm² RS485 shielded cable (300m); RVV 2×1.5mm² power cable (300m); PVC conduits Φ20mm (300m); weak-current auxiliaries.

9. Recommended Configuration and Preliminary Budget

9.1 Configuration List (3 workshops)

I. Front-End Sensing (3 workshops total):

No. Item Model Unit Qty Note
1 Industrial temp/humidity sensor LA-WS100 unit 6 2 per workshop, diagonal
2 Pump-suction laser dust sensor LA-FC200 unit 6 2 per workshop, core work areas
3 Sensor mounting bracket 304 SS set 12 One per sensor

II. Data Acquisition and Transmission:

No. Item Model Unit Qty
1 Industrial edge gateway LA-GW300 unit 3
2 Industrial gigabit switch LA-SW05 5-port unit 1
3 RS485 shielded cable RVSP 2×1.0mm² m 300
4 Power cable RVV 2×1.5mm² m 300
5 PVC conduit and fittings Φ20mm m 300

III. Alarm and Display:

No. Item Model Unit Qty
1 Industrial sound/light alarm LA-SG400 pc 3
2 7-inch industrial touch display LA-DP500 unit 3
3 On-site distribution box 400×300×200mm set 3

IV. Central Monitoring Center:

No. Item Model Unit Qty
1 Industrial monitoring host LA-IPC-610 (i5/8G/256G+2T) unit 1
2 Platform software V1.0 Enterprise set 1
3 Weak-current auxiliaries — lot 1

V. Engineering and Service:

No. Item Unit Qty
1 Installation and commissioning item 1
2 Transport item 1
3 Training item 1
4 1-year warranty service item 1

9.2 Quotation Notes

The list is standard configuration for three 200㎡ workshops; quantities and models adjustable per site conditions. For flammable/explosive workshops, sensors can be replaced with explosion-proof types; wireless transmission upgrade available if wiring is impractical. The quotation includes equipment, installation, commissioning, training and 1-year warranty; tax itemized. All reference prices in this solution are in RMB (CNY) only and are for reference purposes; a formal quotation is issued after configuration confirmation.

10. Technical Specifications

10.1 Overall System Specifications

Item Specification
Monitoring scope 3 workshops × 200㎡, temperature/humidity + PM2.5/PM10/TSP
Temperature accuracy ±0.1℃ (0-50℃), PT1000 Class A
Humidity accuracy ±1.5%RH (10-90%RH, 25℃)
Dust measurement Laser scattering, pump suction, 1μg/m³ resolution, ±10%FS
Dust range PM2.5/PM10 0-10mg/m³, TSP 0-20mg/m³ (custom up to 1000mg/m³)
Refresh ≥1/min configurable
Communication RS485 Modbus-RTU → edge gateway → Ethernet
Alarms Local sound/light + platform, multi-level thresholds
Storage ≥1 year, reports Excel/PDF
Device protection IP65; MTBF ≥30000h
Standards GBZ 1/2.1, GB/T 5817, GB 3095, GB/T 19582

10.2 Key Equipment Specifications

Equipment Key Parameters
LA-WS100 -40~+120℃, 0-100%RH, DC9-36V, ≤0.5W, IP65
LA-FC200 0.3-100μm, 1.0L/min pump, laser 650nm, ≤2W, IP65, MTBF 30000h
LA-GW300 RS485→Ethernet, local cache, breakpoint resume, relay outputs
LA-SG400 High-decibel + red strobe, relay triggered, IP65
LA-DP500 7-inch touch, local data/alarm/settings
LA-IPC-610 i5/8G/256G+2T, industrial chassis

11. Key Advantages and Customer Value

11.1 Advanced Technology, Precise Measurement

Laser scattering + pump suction dust detection is more accurate and faster than traditional diffusion measurement, with 40%+ data stability improvement; imported Class A sensing chips with multi-point temperature compensation for full-range temperature accuracy; edge gateway with data filtering and outlier rejection for higher data reliability.

11.2 Industrial Quality, Stable and Durable

Full-chain industrial-grade design with wide-temp wide-voltage, IP65 protection, adapting to dusty and fluctuating workshop environments; multiple electrical protections against strong electromagnetic interference from motors and welders; fanless, solid-state storage design with MTBF far exceeding commercial devices for 7×24 continuous operation.

11.3 Reasonable Architecture, Strong Scalability

Layered IoT architecture with decoupled modules — single-point failure does not affect the whole; modular design: adding points or parameters (gas, noise) only requires front-end devices; multi-workshop, multi-factory unified platform with smooth expansion protecting investment.

11.4 Complete Functions, Scenario-Fit

Local sound/light alarm + remote platform alarm dual mechanism; on-site touch screens let workshop staff view data and handle alarms without going to the control room; rich reporting directly meets safety supervision, environmental and occupational health data archiving requirements.

11.5 Source Factory, Service Guarantee

Self-developed production with controllable quality and high cost performance, custom development available; 20-year industry experience with full-process service from design, survey, installation to O&M; 7×24 support, 4-hour on-site response in urban areas.

11.6 Compliance and Management Efficiency

Monitoring indicators and accuracy comply with national occupational health, environmental and safety standards; replaces manual inspection with automatic recording and alarming, reducing management costs and improving efficiency; digital environment data supports process optimization, energy management and employee health protection.

12. Technical Q&A (50+ Items)

12.1 Product Principle Questions

Q1: What is the laser scattering principle? Difference from gravimetric method?

A: When laser light irradiates airborne dust particles, scattering light is generated whose intensity is proportional to dust mass concentration within a range; a photodetector receives the scattering light and converts it to a concentration value. Gravimetric is the laboratory reference method (filter collection, drying, weighing) — accurate but slow and offline. Laser scattering is online, fast and continuous, calibrated/traced via the gravimetric method.

Q2: Pump-suction vs diffusion sensors? Which for workshops?

A: Pump-suction actively draws air samples via a built-in pump — stable flow, fast response, accurate, unaffected by external wind; suitable for high-dust, poor-airflow industrial workshops and grinding stations. Diffusion relies on natural airflow — simple, low power, low cost, but slow response and fluctuating data; suitable for light monitoring of general environments.

Q3: Why measure PM2.5, PM10 and TSP simultaneously?

A: Different particle sizes correspond to different health and compliance indicators: PM2.5 (respirable, deep lung), PM10 (inhalable), TSP (total suspended particles). Occupational health and environmental supervision require different indicators; simultaneous measurement meets all requirements with one device.

Q4: How is measurement accuracy ensured?

A: Imported laser and photodetector, blackened optical cavity reducing stray light, digital filtering algorithms, factory calibration with gravimetric traceability, and annual recalibration — ensuring ±10%FS accuracy and stability.

Q5: Why is the dust sensor pump-suction rather than diffusion?

A: The pump provides constant 1.0L/min sampling flow regardless of external wind, ensuring representative samples and stable readings — critical in workshops where airflow varies; also enables longer maintenance intervals with the pre-filter.

Q6: What is the dust sensor’s measurement range?

A: Standard PM2.5/PM10 0-10mg/m³, TSP 0-20mg/m³; custom ranges up to 100/1000mg/m³ for high-dust environments.

Q7: How does temperature compensation work in the humidity sensor?

A: The capacitive polymer element’s response is temperature-dependent; the built-in PT1000 provides temperature data for multi-point compensation algorithms, maintaining ±1.5%RH accuracy across the operating range.

12.2 Installation and Deployment Questions

Q8: Where should sensors be installed?

A: Temperature/humidity sensors diagonally arranged for representative coverage; dust sensors in core work areas at 1.2-1.5m height (breathing zone); avoid direct heat/cold sources, vents and vibration.

Q9: How is wiring done?

A: RS485 shielded twisted pair (RVSP) from sensors to the workshop edge gateway; gateway to monitoring center via Ethernet; power via on-site distribution box; cables in PVC conduits separated from power cables.

Q10: How long does installation take?

A: Per workshop typically 1-2 days (cabling, mounting, commissioning); the whole 3-workshop system about 5-7 working days; adjustable per site conditions and production windows.

Q11: Does installation affect production?

A: Minimal — installation is surface-mounted with short cable runs; work can be scheduled in production gaps; no production shutdown required.

Q12: What are the power requirements?

A: AC220V at each workshop’s distribution box (sensors DC9-36V via power supplies); monitoring center AC220V; UPS optional for the center.

Q13: Can sensors be installed outdoors?

A: The standard sensors are IP65 for indoor/ sheltered use; outdoor installation requires weatherproof enclosures or outdoor-grade variants — consult engineers.

Q14: How many sensors per workshop are recommended?

A: For 200㎡: 2 temperature/humidity + 2 dust sensors provide representative coverage; larger workshops or multi-zone layouts may require more — calculated per area and process layout.

12.3 Operation and Usage Questions

Q15: How do I view data?

A: On-site touch screens per workshop; monitoring center PC client with electronic map, lists and curves; optional mobile WEB/mini-program for remote viewing.

Q16: How are alarm thresholds set?

A: Per workshop process requirements via the platform: upper/lower limits, rate-of-change alarms; each parameter independently configured; multi-level thresholds supported.

Q17: What happens on over-limit?

A: The gateway relay triggers the on-site sound/light alarm; the platform pops up alarm windows with sound, records the event (time, location, value, status); optional SMS/email notification.

Q18: Can thresholds be changed by workshop staff?

A: Threshold changes are permission-controlled on the platform (administrator/operator levels); on-site touch screens allow viewing but parameter changes are typically restricted to authorized roles.

Q19: How is the system started/stopped?

A: The system runs 7×24 automatically; the monitoring host auto-starts the platform; gateways auto-connect; no daily manual operation required beyond alarm handling.

Q20: What do the numbers mean on the touch screen?

A: Current temperature, humidity, PM2.5/PM10/TSP values with status colors; alarm state and history; per-point identification labels.

12.4 Maintenance Questions

Q21: What daily maintenance is needed?

A: Monthly: sensor surface cleaning, check for dust accumulation on louvered probes. Quarterly: dust sensor filter inspection/replacement (3-6 months per site dust levels), cable and connection checks. Annual: calibration, comprehensive system check.

Q22: How is the dust sensor filter replaced?

A: The front filter and PM10 cutter are accessible/detachable; replacement takes minutes without special tools; keep spares on site per maintenance guidance.

Q23: How often should sensors be calibrated?

A: Recommended annually by qualified metrology institutions or factory; on-site comparison with standard instruments during inspections; calibration certificates available.

Q24: What if a sensor shows abnormal values?

A: First check installation environment (dust accumulation, condensation, blockage), verify cable connections and power, compare with a portable standard instrument; if drift confirmed, calibrate or replace.

Q25: How is the gateway maintained?

A: Minimal — industrial design with no moving parts; check power and network indicators periodically; restart rarely needed (watchdog auto-recovery).

Q26: What is the system’s MTBF?

A: ≥30000h for field devices and gateway; the industrial host has high MTBF with solid-state storage — long-term reliable operation.

Q27: Are spare parts available?

A: Sensors, filters, alarms, gateways and accessories stocked for fast replacement; 7×24 support with urban 4-hour on-site response.

12.5 Alarm Function Questions

Q28: Can different workshops have different thresholds?

A: Yes — thresholds are set per point/workshop independently, adapting to different process requirements.

Q29: What alarm modes are supported?

A: Upper-limit, lower-limit and rate-of-change alarms; multiple thresholds (e.g., warning and alarm levels) per parameter.

Q30: How are alarms acknowledged?

A: Platform alarm management: acknowledge, record handling status, close; alarm history queryable with statistics (frequency reports).

Q31: What if the network fails during an alarm?

A: The gateway stores data locally and the on-site alarm still triggers (local relay logic); on network recovery, data and alarm events upload automatically.

Q32: Can alarms trigger external devices (ventilation, dust collectors)?

A: Yes — gateway relay outputs can drive ventilation fans, dust collectors or other equipment via the on-site distribution box per configuration.

12.6 Data Management Questions

Q33: How long is history stored?

A: ≥1 year for all parameters on the 2T HDD; expandable storage for longer retention.

Q34: What reports are available?

A: Daily/weekly/monthly/yearly reports per zone/parameter; trend curves; Excel/PDF export for archiving and compliance submission.

Q35: Who can access the platform?

A: Multi-level user permissions (administrator, operator, visitor) with operation logs — data security per classified protection baseline.

Q36: Can data be exported for regulatory submission?

A: Yes — standard reports and raw data export formats satisfy safety supervision, environmental and occupational health submission needs.

Q37: Can the platform integrate with MES/ERP?

A: Yes — standard data interfaces (Modbus/TCP, API) allow integration with enterprise management systems for data interconnection.

Q38: What happens during a power failure?

A: Field data is cached in gateways; on power restoration the system auto-resumes and uploads buffered data — no data loss; optional UPS for the monitoring center.

12.7 System Expansion Questions

Q39: Can more workshops be added?

A: Yes — each new workshop needs its front-end devices and gateway, connected to the monitoring center switch; the platform adds the new points directly.

Q40: Can gas, noise or vibration parameters be added?

A: Yes — modular architecture supports adding compatible sensors (toxic gas, noise, vibration) to existing gateways without replacing the platform.

Q41: Can the wireless solution be used?

A: Yes — for sites where cabling is impractical, wireless transmission upgrade is available for sensors and gateways.

Q42: Can the system monitor outdoor areas?

A: With outdoor-grade sensors/enclosures, the system can extend to outdoor measurement points via the same platform.

Q43: How many points can one gateway support?

A: Each gateway supports up to 32 RS485 devices; multiple gateways expand capacity per workshop/factory scale.

Q44: Is multi-factory centralized management possible?

A: Yes — the platform supports multi-factory, multi-site architecture; remote sites connect via network with permission-controlled access.

Q45: Can the platform be accessed remotely?

A: Yes — mobile WEB/mini-program options provide remote viewing; access security via accounts and permissions.

12.8 Project and Service Questions

Q46: What is the warranty?

A: 1-year free warranty with free on-site inspection and technical support; after warranty, lifetime cost-price maintenance.

Q47: What training is provided?

A: On-site training covering system operation, software use, alarm handling, maintenance and calibration — with hands-on practice and assessment; free repeat training for new staff.

Q48: What documentation is delivered?

A: As-built drawings, configuration lists, device certificates and calibration options, commissioning records, operation manual, platform user guide and after-sales card.

Q49: What is the delivery time?

A: Standard configuration about 15-20 working days from order (production + installation + commissioning); customized or explosion-proof variants extend accordingly.

Q50: Are explosion-proof sensors available for hazardous workshops?

A: Yes — LA-FC200 optional Ex ib IIC T4 Gb explosion-proof certification; explosion-proof temperature/humidity sensors also available for flammable/explosive environments.

Q51: How is data security ensured?

A: Graded permissions, operation logs, encrypted transmission; local deployment keeps data in-house; classified protection baseline compliance per GB/T 22239.

Q52: What is the total cost composition?

A: Equipment (sensors, gateways, displays, host, software), installation and commissioning, transport, training and warranty; quantity adjustments and options (explosion-proof, wireless, UPS) affect the total — formal quotation after configuration confirmation.

13. Construction Schedule

13.1 Overall Period

The total project period is approximately 15-20 working days for the 3-workshop scope, covering design confirmation, production, installation, commissioning and acceptance; adjustable per site conditions and production windows.

13.2 Detailed Schedule

Stage Work Content Days Responsible Acceptance Node
1. Preparation Site survey, point confirmation, material incoming inspection, technical/safety disclosure 2 Project manager Materials accepted
2. Cabling Conduit laying, RS485/power cable pulling, distribution box installation 4 Team leader Continuity tested
3. Device installation Sensor mounting, gateway/switch/alarm/touch screen installation, wiring 3 Engineer Installation checked
4. Commissioning Gateway configuration, sensor communication, platform deployment, point mapping, alarm tests 3 Engineer Functions verified
5. Joint debugging Cross-workshop data verification, alarm linkage, report generation 2 Engineer Linkage verified
6. Acceptance 72h trial run, documentation, training, client acceptance 2 PM + engineer Acceptance passed

13.3 Schedule Assurance Measures

– Experienced team, fixed personnel; advance stocking; daily plan review;

– Installation scheduled in production gaps to avoid disruption;

– Spare devices available; overtime arrangements for schedule recovery.

14. Construction Organization and Quality/Safety Measures

14.1 Organization Structure

– Project manager: overall responsibility for progress, quality, safety and cost; client interface;

– Technical leader: solution deepening, disclosure, commissioning, training;

– Construction team: cabling, device installation;

– QC/safety officer: quality inspection, safety supervision.

14.2 Pre-Construction Preparation

1. Technical: survey and confirm points, routes and monitoring center location; technical and safety disclosure;

2. Materials: incoming inspection (certificates, appearance, quantity); sensors with calibration options;

3. Site: coordinate access and work areas with the client; protect existing facilities; arrange power.

14.3 Key Construction Processes

– Cabling: conduit laying → cable pulling (RS485 shielded, power separated) → labeling and continuity tests;

– Device installation: sensors on 304 brackets at design positions (dust sensors at 1.2-1.5m); gateway/switch/alarm/touch screen installed and wired per diagrams;

– Distribution box: breakers, terminals and SPD installed; power verified;

– Monitoring center: host installed, platform deployed, points mapped, alarms configured.

14.4 Quality Control

– Three-level inspection; hidden work acceptance with records;

– Key control points: sensor calibration certificates, communication stability, alarm triggering accuracy, data storage integrity, report correctness;

– Acceptance per design and relevant standards; as-built documentation.

14.5 Safety and Civilized Construction

– Safety education, PPE, safe temporary power, no hot work without approval;

– Compliance with workshop management rules; work in production gaps;

– Materials stacked neatly, daily cleaning, finished product protection;

– Emergency plans for injury and equipment damage.

14.6 Finished Product Protection

– Installed devices protected during other works; sensors and displays covered against dust; cables labeled and protected; dedicated guarding before handover.

15. After-Sales Service

15.1 Warranty Commitment

1-year free warranty from acceptance: free on-site inspection, technical support and repair/replacement of non-artificial quality problems; after warranty, lifetime cost-price maintenance.

15.2 Response Mechanism

7×24 hotline; remote guidance within 1 hour; urban on-site within 4 hours; general faults resolved within 4 hours on site; dedicated follow-up per project.

15.3 Periodic Inspection

Semi-annual inspection during warranty: sensor cleaning, filter check, calibration comparison, communication and alarm function tests; inspection reports issued.

15.4 Spare Parts Supply

Sensors, filters, alarms, gateways and accessories stocked for fast replacement; emergency logistics within 48h; genuine parts with corresponding warranty.

15.5 Training and Upgrade Support

On-site training at handover with free repeat training; free lifetime technical consultation; preferential expansion (new points, parameters, workshops) and upgrade services.

15. After-Sales Service

15.1 Warranty Commitment

The overall project warranty period is 2 years from the date of completion acceptance; core equipment has a 3-year warranty. During the warranty period, all failures and damage caused by product quality or construction process problems are repaired and parts replaced free of charge. After the warranty period, lifetime cost-price maintenance is provided, charging only parts cost and basic labor, ensuring long-term stable system operation.

15.2 After-Sales Response Mechanism

– A 7×24 after-sales hotline receives fault reports and technical consultations at any time;

– Within the urban area: respond within 2 hours, technicians on site within 4 hours;

– Suburban and surrounding areas: respond within 4 hours, personnel on site within 8 hours;

– General faults resolved on the spot; complex faults solved within 24 hours with a solution;

– Emergency faults get a green channel with priority dispatch of personnel and parts.

15.3 Periodic Inspection and Maintenance

During the warranty period, a free on-site inspection is provided every six months, with a comprehensive maintenance inspection annually. Inspection contents include equipment operating status, connection firmness, sealing and rust conditions, filtering/grounding performance and safety devices. After each inspection, a formal inspection report is issued recording equipment status and maintenance content with optimization suggestions.

15.4 Spare Parts Supply Guarantee

A local spare parts warehouse is established, stocking common wearing parts for quick replacement to shorten fault handling time. For uncommon special parts, a fast supply channel with the factory ensures availability within 48 hours. During warranty, non-artificial-damage spare parts are replaced free; after warranty, parts are charged at cost price without markup.

15.5 System Upgrade and Technical Support

– Free lifetime technical consultation services by phone or online at any time;

– If the customer later needs upgrades or expansions, preferential upgrade solutions and construction services are provided;

– Industry new technology and standard information is regularly pushed to customers.

16. Training Plan

16.1 Training Objectives and Audience

Training objectives: through systematic training, enable management personnel to fully understand the system structure, working principles and performance characteristics, master daily operation methods and inspection/maintenance essentials, identify common faults and handle simple problems, ensuring safe, stable and long-term operation.

Training audience: management and O&M personnel designated by the client, recommended 2-3 persons with basic electrical and equipment knowledge.

16.2 Tiered Training Content System

Level 1: Basic operation training (1 day)

– Basic principles: system concepts, structure composition, performance indicators;

– Daily operation standards: correct operation of equipment, control and safety systems;

– Daily inspection contents: daily/weekly/monthly check items;

– Safety precautions: usage prohibitions and emergency handling procedures.

Level 2: Maintenance training (1 day)

– Detailed structure of each subsystem and working principles;

– Daily maintenance methods: cleaning, fastening checks, routine care;

– Common fault identification and simple handling;

– Emergency handling procedures for power failure, fire and equipment faults.

Level 3: Advanced management training (as needed)

– Performance influencing factors and how to avoid degradation;

– Upgrade and expansion knowledge and specification requirements;

– Relevant national standards interpretation.

16.3 Training Methods and Schedule

– Methods: combination of “theory explanation + on-site practice + Q&A interaction”;

– Schedule: training arranged at the completion acceptance stage, synchronized with handover, 2 days of intensive training total; time flexibly adjustable; a free repeat training session is provided for newly assigned personnel.

16.4 Training Assessment and Documentation Delivery

– Assessment: theory written test plus practical operation; training qualification certificates issued upon passing; supplementary training for those who fail;

– Documentation delivery: complete O&M documentation, including operation and maintenance manual, equipment manuals and certificates, completion drawings and hidden work records, test reports and after-sales service contact card, all bound into volumes.

17. Anonymous Typical Project Scenarios

All project scenarios below are anonymous, generalized examples compiled from typical industry deployments; no real customer names, addresses or confidential information are disclosed.

17.1 Workshop Environment Monitoring for a Hardware Processing Enterprise

A hardware processing enterprise with grinding and polishing workshops needed real-time dust monitoring for occupational health compliance. Three workshops (about 200㎡ each) were equipped with temperature/humidity sensors and pump-suction laser dust sensors (PM2.5/PM10/TSP), edge gateways, on-site sound/light alarms and touch screens, plus a centralized platform. Dust over-limit alarms triggered ventilation linkage, protecting worker health; monthly reports satisfied safety supervision submissions; the system operated stably with quarterly filter maintenance.

17.2 Precision Manufacturing Workshop Monitoring for an Electronics Factory

An electronics factory required strict temperature/humidity control in precision assembly workshops to protect components from moisture and static. Temperature/humidity sensors (±0.1℃/±1.5%RH) with centralized platform monitoring and threshold alarms enabled proactive environment control; historical data supported process quality analysis; the system integrated with the factory’s MES via standard interface for unified data management.

17.3 Multi-Workshop Expansion Project for a Wood Processing Plant

A wood processing plant with dust explosion risk upgraded its workshops with explosion-proof dust sensors (Ex ib IIC T4 Gb) and temperature/humidity monitoring, with local alarms and platform monitoring at the safety office. The system detected abnormal dust accumulation early, triggering ventilation and process adjustments; explosion-proof certification met safety acceptance; the modular architecture allowed adding new workshops without platform replacement.

18. SEO Optimization Section

All reference prices in this technical solution are in RMB (CNY) only and are for reference purposes; final quotation is subject to the confirmed configuration.

18.1 Keyword System

– Core keywords: technical design solution, system configuration, technical parameters, construction and O&M services;

– High-conversion long-tail keywords: design solution, configuration list, technical parameters, construction plan, after-sales service;

– Industry traffic keywords: system architecture, applicable standards, technical Q&A, project cases;

– Brand keywords: KITOZER, Guangzhou Lain.

18.2 SEO Tag System

– Title tag: the article title — Guangzhou Lain KITOZER;

– Meta description: Guangzhou Lain professionally provides complete technical design solutions with detailed configuration list, full-system product technical parameters, construction organization plan and after-sales service — source manufacturer customization, compliant performance, third-party testing supported;

– H1 tag: the article title;

– H2 tags: system design and product parameters, construction organization plan, after-sales service and training, engineering cases.

18.3 Internal Link Anchor Text

– Core anchor text: technical design solution, system construction;

– Long-tail anchor text: configuration list, technical parameters, construction plan;

– Related anchor text: shielding cabinet, micro-module cold aisle, integrated computer room, outdoor cabinet.

19. Official Contact Information

– Company Name: Guangzhou Lain Intelligent System Development Co., Ltd.

– Brand: KITOZER (Pioneer)

– Official Website: https://gdlain.com

– Tel: +86 139 2228 9957 (WeChat available), +86 185 2066 8845 (WeChat available)

– Address: No. 5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China

For any inquiries about this technical design solution, configuration customization, quotation or construction services, please contact us through the information above. We provide free design consultation and tailored solutions for your specific requirements.

Scroll to Top