10kV Outdoor Intelligent Ring Main Unit (RMU) — Technical Design Solution
Brand Series: KITOZER
Prepared by: Guangzhou Lain Intelligent System Development Co., Ltd.
Version: V2.0
—
Table of Contents
- Company Profile
- Project Overview
- User Requirements Analysis
- Overall Design Description
- Equipment Configuration List
- Core Product Technical Parameters
- Solution Advantages & Features
- Technical Q&A
- Construction Schedule Plan
- Construction Organization Plan
- After-Sales Service System
- Operation & Maintenance Personnel Training Plan
- Typical Engineering Cases
- SEO Optimization System & Keywords
- Contact Information
—
1. Company Profile
Founded in 2002, Guangzhou Lain Intelligent System Development Co., Ltd. is a high-tech enterprise specializing in the R&D, production, and sales of computer room construction, high/low-voltage power distribution equipment, intelligent enclosures, and environmental monitoring systems. The company operates under its core brand “KITOZER” (Pioneer) .
With more than two decades of deep industry expertise, the company has mastered core technologies in green, high-efficiency data center and power distribution equipment. KITOZER delivers tailored solutions for diverse application scenarios, with a full product portfolio covering modular cold-aisle containment, indoor integrated cabinets, outdoor intelligent enclosures, shielded rooms and shielded cabinets, containerized data centers, environmental monitoring systems, and UPS power supplies. These products are widely deployed across the power industry, municipal infrastructure, industrial parks, data centers, healthcare, and education sectors.
The company is built on four core strengths: Rapid Response, Quality First, Custom Design, and Worry-Free After-Sales:
- Speed: Manufacturing lead time and support hours are confirmed on the quotation.
- Quality Assurance: Products strictly comply with national and industry standards; third-party testing agencies provide full-process quality control, and every unit undergoes factory acceptance testing before shipment.
- Custom Design: Three tailored design proposals are provided free of charge, precisely matched to on-site working conditions and customer requirements, with full support for non-standard customization.
- Premium After-Sales: Full life-cycle service with dedicated project follow-up, rapid on-site response, and guaranteed stable equipment operation.
Holding multiple product patents and qualification certifications, the company has earned the trust of numerous domestic and international enterprises and users through superior product quality and a comprehensive service system. KITOZER is committed to becoming China’s leading total-solution provider for intelligent power distribution and data center infrastructure.
—
2. Project Overview
2.1 Project Background
With the ongoing upgrade of urban distribution networks, the development of industrial parks, and the advancement of commercial infrastructure construction, the 10kV outdoor ring-main power supply model has become the core node equipment of medium-voltage distribution networks, thanks to its high supply reliability, flexible switching configurations, convenient operation and maintenance, and compact footprint. The outdoor ring main unit (RMU) performs the critical functions of power distribution, line protection, fault isolation, and ring-network interconnections — its performance directly determines the supply reliability and operational safety of the entire distribution network.
Conventional outdoor distribution equipment commonly suffers from inadequate ingress protection, susceptibility to environmental degradation, heavy maintenance workloads, and low intelligence levels, making it difficult to meet the modern distribution network’s demands for high reliability and unattended operation. In response to the distribution requirements of complex outdoor conditions, this project designs a complete 10kV outdoor intelligent RMU solution featuring high reliability, intelligent control, and minimal maintenance.
2.2 Construction Objectives
- High-Reliability Power Supply: A dual-source ring-network architecture achieves N-1 supply redundancy, dramatically reducing the scope and duration of fault-related outages.
- Strong Environmental Adaptability: Fully sealed insulation structure combined with high-protection enclosures withstands harsh outdoor conditions including high temperature, high humidity, condensation, dust, and corrosive atmospheres.
- Comprehensive Protection Functions: Integrated relay protection and fault detection rapidly isolate faults, safeguarding equipment and downstream loads.
- Intelligent Operation & Maintenance: Integrated remote measurement, remote signaling, and remote control functions support connection to distribution automation systems for fully unattended operation.
- End-to-End Service: Integrated solution from design and manufacturing through installation, commissioning, training, and after-sales support, ensuring successful project delivery.
2.3 Applicable Scenarios
This solution is suitable for a wide range of 10kV outdoor distribution applications, including:
- Urban distribution network upgrades
- Industrial park power distribution
- Commercial complex power supply
- Municipal infrastructure projects
- Data center external power lines
- Residential community distribution
- New energy grid interconnection
—
3. User Requirements Analysis
3.1 Basic Functional Requirements
- Ring-network connection configuration with 2 incoming lines and 4 outgoing lines (6 circuits total), enabling dual-source interconnection and power distribution.
- Load switching, short-circuit protection, overload protection, and earth-fault protection as standard distribution functions.
- Compliance with high-voltage equipment “five-prevention” interlock requirements — preventing misoperation of circuit breakers, disconnectors, earthing switches, and unauthorized entry into live compartments, ensuring the safety of operation and maintenance personnel.
- Outdoor ground-mounted installation with rainproof, dustproof, anti-corrosion, anti-condensation, and anti-theft protection.
- Complete earthing system with reliable grounding of the equipment enclosure and all metal frameworks.
3.2 Performance Specifications
| Parameter | Value |
| — | — |
| Rated voltage | 12 kV |
| Rated frequency | 50 Hz |
| Rated current of main busbar | 630 A |
| Rated current of branch circuits | 630 A |
| Rated short-time withstand current | 20 kA / 4 s |
| Rated peak withstand current | 50 kA |
| Enclosure ingress protection | ≥ IP54 |
| Main switch gas tank ingress protection | ≥ IP67 |
| Load switch mechanical life | ≥ 10,000 operations |
| Ambient temperature range | −30 °C to +70 °C |
The environmental temperature range covers the climatic conditions of most regions worldwide, including continental climates across China, the Middle East, and parts of Africa.
3.3 Intelligence & Communication Requirements
- Each circuit is equipped with a microprocessor-based integrated protection device featuring instantaneous overcurrent, overcurrent, zero-sequence, overvoltage, and undervoltage protection functions.
- Multi-function power meters provide real-time monitoring of voltage, current, power, energy, harmonic distortion, and other electrical parameters.
- Standard communication interfaces supporting Modbus and IEC 60870-5-103/104 protocols, enabling seamless integration with distribution automation systems.
- Local/remote operation mode switching; remote close/open control and operational data viewing.
- Fault recording and event logging functions for fault analysis and traceability.
3.4 Operation, Maintenance & Safety Requirements
- Maintenance-free or low-maintenance design to minimize routine workload and lifecycle costs.
- Clear status indication and fault alarm functions for rapid problem identification.
- Visible disconnection points and clearly identifiable earthing positions to ensure safe maintenance operations.
- Anti-tamper locking mechanisms on cabinet doors to prevent unauthorized operation.
- Complete technical documentation, operation & maintenance manuals, and spare parts support.
—
4. Overall Design Description
4.1 Design Basis
This solution strictly conforms to the following national and industry standards and specifications:
| Standard | Title |
| — | — |
| GB 3906-2020 | 3.6 kV – 40.5 kV AC Metal-Enclosed Switchgear and Controlgear |
| GB/T 11022-2020 | Common Specifications for High-Voltage Switchgear and Controlgear Standards |
| DL/T 593-2016 | Common Technical Requirements for High-Voltage Switchgear and Controlgear |
| GB 50060-2013 | Code for Design of 3–110 kV High-Voltage Distribution Installations |
| GB 50217-2018 | Code for Design of Power Engineering Cables |
| DL/T 5352-2018 | Technical Code for the Design of High-Voltage Distribution Installations |
| GB/T 14285-2006 | Technical Code for Relay Protection and Security Automatic Equipment |
| GB 4208-2017 | Degrees of Protection Provided by Enclosures (IP Code) |
| State Grid Corporation of China | General Technical Conditions for 10kV Pole-Mounted Switchgear |
| China Southern Power Grid | Technical Specification for 10kV Outdoor Ring Main Units |
4.2 Design Principles
- Safety & Reliability: Supply safety is the primary focus. Proven technologies and components are selected, with comprehensive protection and interlock mechanisms ensuring long-term stable operation and the safety of both personnel and equipment.
- Advanced & Practical: Industry-leading gas-insulated and intelligent protection technologies are adopted, balancing technical advancement with economic practicality to meet distribution development needs for the next 5–10 years.
- Environmental Adaptation: Multi-dimensional design considerations — including material selection, structural design, and heating/dehumidification systems — ensure reliable operation under extreme temperatures, high humidity, and corrosive environments.
- Maintenance Convenience: Modular design with logical layout and user-friendly operation; visualized intelligent monitoring reduces maintenance difficulty and workload.
- Standard Compliance: All designs and equipment comply with applicable standards and pass authoritative testing, meeting grid connection requirements.
- Customization Flexibility: Circuit quantity, current ratings, communication protocols, and enclosure dimensions can be adjusted to precisely match actual site conditions.
4.3 Primary Main Connection Design
This solution employs a classic single-busbar ring-network connection scheme. Two power incoming lines are sourced from different upstream substations, and four outgoing lines supply different load zones. Under normal operation, the network operates in open-ring mode with one power source carrying the full load. When one source experiences a fault or is under maintenance, the ring-network tie switch seamlessly transfers to the alternate source, ensuring uninterrupted power supply.
- Incoming Circuits: Equipped with load switch–fuse combination units providing load switching, short-circuit protection, and overload protection.
- Outgoing Circuits: Equipped with three-position load switches plus earthing switches, enabling load switching, line isolation, and maintenance earthing.
- Main Busbar: Full copper, tin-plated busbar running through all circuits, carrying the total system current.
4.4 Enclosure Structural Design
Overall Layout: The cabinet adopts a front-operation, rear-cable-chamber layout. The front face houses the instrument compartment and operating mechanism area; the rear accommodates the cable termination chamber; the left side contains the incoming line bays and the right side the outgoing line bays. The clear layout ensures operation and maintenance activities do not interfere with one another.
Materials & Fabrication: The outer enclosure is fabricated from 2 mm thick 304 stainless steel, laser-cut and CNC-bent into shape, with a brushed surface finish providing excellent corrosion and rust resistance. The internal gas tank is laser-welded stainless steel, delivering superior sealing performance.
Compartment Design: The interior is divided by metal partitions into three independent compartments — gas tank chamber, cable chamber, and instrument chamber — each providing effective electrical isolation to prevent fault propagation.
Protection Design: Cabinet doors are fitted with EPDM (ethylene-propylene-diene monomer) waterproof sealing gaskets and three-point anti-theft locking mechanisms. The roof features a rain shield with a sloped profile to prevent water accumulation. Cable entry/exit points at the base are sealed with IP-rated cable glands, providing waterproof and dustproof sealing.
Ventilation & Heat Dissipation: Natural ventilation is adopted with dust-filtered inlet and outlet vents, balancing heat dissipation with dust protection. The internal gas tank is fully sealed and unaffected by external ambient conditions.
Ergonomic Design: Operating mechanisms and instruments are positioned at a comfortable operating height (1.2–1.5 m). Cabinet doors open to ≥120°. Interior LED lighting activates automatically upon door opening, facilitating nighttime inspection and maintenance.
4.5 Secondary Control & Monitoring System Design
The secondary system adopts a hierarchical, distributed architecture. Each circuit independently configured with protection and metering devices, centrally arranged in the instrument compartment, and interconnected to the monitoring system via communication bus.
- Protection Layer: Each circuit is equipped with an integrated microprocessor-based protection device that independently performs protection, measurement, and control functions without relying on an upper-level host — ensuring high reliability.
- Monitoring Layer: Multi-function power meters provide comprehensive electrical parameter monitoring and energy metering. Temperature and humidity controllers automatically regulate the internal cabinet environment.
- Communication Layer: Via RS485/Ethernet interfaces, all device data is uploaded to the distribution automation master station, enabling remote measurement, remote signaling, and remote control (“three-remote” functionality).
—
Contact information, equipment configuration lists, technical parameters, project schedules, after-sales service details, and case studies are provided in subsequent chapters of this solution document.
—
KITOZER — Your Trusted Manufacturer & Supplier of Intelligent Power Distribution Solutions
Guangzhou Lain Intelligent System Development Co., Ltd.
Project configuration is confirmed on the quotation
- Phone / WhatsApp / WeChat: +86 13538869979 / +86 13538869979
- Website: https://gdlain.com
- Address: Huashan Road 5, Shilou Town, Panyu District, Guangzhou, Guangdong, China
Serving overseas projects across the USA, Europe, Southeast Asia, the Middle East, Africa, and worldwide.
5. Equipment Configuration List
5.1 Cabinet Body and Structural Protection
| No. | Item Name | Specifications | Unit | Qty. | Remarks |
| :—: | — | — | :—: | :—: | — |
| 1 | Outdoor RMU (Ring Main Unit) Cabinet Body | 304 stainless steel, double-layer structure, protection rating IP54, dimensions 1800×1200×2200 mm (W×D×H) | Set | 1 | Outdoor floor-mounted, equipped with rain canopy and natural ventilation structure |
| 2 | Internal Compartment Partition Panels | 1.5mm cold-rolled steel plate, electrostatic powder coated; isolates gas tank compartment, cable compartment, and instrument compartment | Set | 1 | Physical separation, complies with five-prevention interlock requirements |
| 3 | Cabinet Door Assembly | Double-door structure with three-point anti-theft lock, EPDM waterproof sealing strip, cabinet door grounding terminal | Set | 2 | Equipped with tempered glass observation window for internal status viewing |
| 4 | Mounting Base Channel Steel | No. 10 hot-dip galvanized channel steel, welded into frame, bolted to cabinet body | Set | 1 | Civil foundation fixation and cabinet leveling |
| 5 | Main Grounding Bar | 40×4 mm hot-dip galvanized flat steel, full-length through cabinet, with M10 grounding bolts | Pcs | 2 | Main grounding circuit + auxiliary grounding circuit |
| 6 | Cable Sealing Glands | 304 stainless steel, for armored cables, suitable for 3×70~3×300 mm² cables | Pcs | 12 | 2 incoming + 4 outgoing = 6 circuits total, 1 per cable entry/exit per circuit, IP68 rated |
| 7 | In-cabinet LED Lighting System | AC220V, flat panel LED luminaire, with door-activated sensor switch | Set | 2 | One set each for cable compartment and instrument compartment, auto-illumination upon door opening |
| 8 | Anti-Condensation Temperature & Humidity Control System | Temperature/humidity controller + PTC heater, AC220V, 50W per unit | Set | 2 | One set each for cable and instrument compartments, automatic heating and dehumidification |
5.2 Primary Main Circuit — Incoming Feeder Circuits (2 Circuits)
| No. | Item Name | Specifications | Unit | Qty. | Remarks |
| :—: | — | — | :—: | :—: | — |
| 1 | SF6 Gas-Insulated Load Switch-Fuse Combination Unit | 12kV, 630A, 20kA/4s, three-position (closed/open/earthing), SF6 insulated | Unit | 2 | 1 per incoming circuit, motor-wound spring operating mechanism |
| 2 | HV Current-Limiting Fuse | 12kV, 125A, 50kA breaking capacity, with striker pin | Pcs | 6 | 1 per phase (A/B/C) per circuit; current rating adjustable per requirement |
| 3 | Zinc Oxide Surge Arrester | 10kV, composite housing, nominal discharge current 5kA, residual voltage 50kV | Pcs | 6 | 3-phase, 1 per phase per circuit, overvoltage protection |
| 4 | Wall Bushing | 10kV, epoxy resin cast, 630A current rating | Pcs | 6 | 1 per phase per circuit |
| 5 | Circuit Connection Copper Busbar | T2 oxygen-free copper, TMY-60×6 mm, tin-plated surface | Meter | 6 | 3 phases per circuit, approx. 1 meter per phase |
| 6 | Current Transformer | 10kV, type LZZBJ9, 200/5A, dual-winding class 0.5/10P10, 15VA | Pcs | 6 | 3 per circuit, metering + protection |
5.3 Primary Main Circuit — Outgoing Feeder Circuits (4 Circuits)
| No. | Item Name | Specifications | Unit | Qty. | Remarks |
| :—: | — | — | :—: | :—: | — |
| 1 | Gas-Insulated Three-Position Load Switch | 12kV, 630A, 20kA/4s, three-position (closed/open/earthing), SF6 insulated | Unit | 4 | 1 per outgoing circuit, motor-wound spring operating mechanism |
| 2 | Zinc Oxide Surge Arrester | 10kV, composite housing, nominal discharge current 5kA, residual voltage 50kV | Pcs | 12 | 3-phase, 1 per phase per circuit |
| 3 | Wall Bushing | 10kV, epoxy resin cast, 630A current rating | Pcs | 12 | 1 per phase per circuit |
| 4 | Circuit Connection Copper Busbar | T2 oxygen-free copper, TMY-60×6 mm, tin-plated surface | Meter | 12 | 3 phases per circuit, approx. 1 meter per phase |
| 5 | Current Transformer | 10kV, type LZZBJ9, 100/5A, dual-winding class 0.5/10P10, 15VA | Pcs | 12 | 3 per circuit, metering + protection |
| 6 | Earthing Switch | 10kV, 20kA/4s short-time withstand, mechanically interlocked with load switch | Unit | 4 | Integrated with three-position switch, satisfies maintenance earthing requirements |
5.4 Primary Main Circuit — Busbar and Common Components
| No. | Item Name | Specifications | Unit | Qty. | Remarks |
| :—: | — | — | :—: | :—: | — |
| 1 | Main Busbar | T2 oxygen-free copper, TMY-80×8 mm, fully tin-plated on all phases | Meter | 4.5 | Horizontal through cabinet, connects all circuits |
| 2 | Busbar Support Insulator | 10kV, epoxy resin cast, 4kN bending strength | Pcs | 12 | Evenly arranged across 3 phases, secures horizontal busbar |
| 3 | Busbar Expansion Joint | Copper flexible connection, suitable for 80×8 busbar | Pcs | 2 | Compensates for thermal expansion/contraction of busbar |
| 4 | In-cabinet Earthing Busbar | T2 oxygen-free copper, TMY-40×4 mm, tin-plated surface | Meter | 6 | Full-length earthing continuity inside cabinet |
| 5 | Busbar Clamp | Insulating flame-retardant material, suitable for 80×8 busbar | Set | 12 | Fixes busbar, provides phase-to-phase insulation |
5.5 Secondary Control and Measuring Circuit
| No. | Item Name | Specifications | Unit | Qty. | Remarks |
| :—: | — | — | :—: | :—: | — |
| 1 | Microcomputer Integrated Protection Device | 10kV line protection type; instantaneous overcurrent / overcurrent / zero-sequence / over-undervoltage protection; with RS485 communication | Unit | 6 | 1 per circuit, 2 incoming + 4 outgoing = 6 units total |
| 2 | Multifunction Power Meter | Three-phase four-wire; full electrical parameter measurement + energy metering + harmonic analysis; RS485 communication | Pcs | 6 | 1 per circuit |
| 3 | Close/Trip Control Pushbuttons | Red/green self-resetting type, 22mm panel cutout | Pcs | 12 | 1 trip + 1 close pushbutton per circuit |
| 4 | Position Indicator Lamps | LED type, red/green/yellow, AC/DC220V | Pcs | 18 | Closed, open, and earthing position indicators — 1 of each per circuit |
| 5 | Local/Remote Selector Switch | Universal changeover switch, two-position | Pcs | 6 | 1 per circuit |
| 6 | Secondary Wiring Terminal Block | Modular rail-mount terminal, type UK2.5B | Segments | 180 | Covers control, signaling, and power supply circuits |
| 7 | Secondary Circuit MCB | 2-pole, Type C 10A, AC230V | Pcs | 4 | 1 each for control, lighting, heating, and communication circuits |
| 8 | DC Switching Power Supply | AC220V input, DC24V/5A output | Unit | 1 | Unified power supply for sensors and communication modules |
| 9 | Switch Electric Operating Mechanism | Spring-energy storage type, AC/DC220V dual-use | Set | 6 | 1 set for each load switch |
| 10 | Auxiliary Travel Switch | Dry contact, position signal feedback | Pcs | 18 | Closed/open/earthing position — 1 of each per circuit |
| 11 | Secondary Control Cable | RVVP shielded cable, multi-core, 1.5 mm² | Meter | 120 | In-cabinet secondary wiring and signal transmission |
| 12 | Wire Numbering Sleeves | Serrated heat-shrink tube, suitable for 1.5/2.5 mm² conductors | Meter | 15 | Circuit number identification |
5.6 Auxiliary Materials and Identification
| No. | Item Name | Specifications | Unit | Qty. | Remarks |
| :—: | — | — | :—: | :—: | — |
| 1 | Nylon Cable Ties | 4×200 mm, self-locking, black | Bag | 3 | Cable bundling and organization |
| 2 | Mounting Bolt Kit | M8/M10 hot-dip galvanized bolts, incl. flat washers, spring washers, nuts | Set | 1 | Full coverage for cabinet fixing and component installation |
| 3 | Electrical Contact Grease | Conductive compound, 100g box | Box | 2 | Applied to copper busbar contact surfaces, reduces contact resistance |
| 4 | Phase Sequence Identification Labels | A-yellow / B-green / C-red, waterproof PVC material | Set | 2 | Phase identification on busbars and circuit terminals |
| 5 | Equipment Nameplate | Stainless steel etched plate, marked with model, parameters, and manufacturer info | Pcs | 1 | Mounted in a prominent position on the outer cabinet door |
| 6 | Safety Warning Labels | High-voltage danger, no closing, earthing labels, etc. | Set | 1 | Applied at corresponding positions inside cabinet and on doors |
| 7 | Secondary Circuit Identification | Circuit numbers, terminal markings | Set | 1 | Standardized secondary wiring identification |
—
6. Core Product Technical Parameters
6.1 Outdoor RMU Cabinet
| Parameter | Value |
| — | — |
| Product Model | KITOZER-HW-12/630 |
| Rated Voltage | 12kV |
| Rated Frequency | 50Hz |
| Main Busbar Rated Current | 630A |
| Branch Circuit Rated Current | 630A |
| Rated Short-Time Withstand Current | 20kA/4s |
| Rated Peak Withstand Current | 50kA |
| Protection Rating | Enclosure IP54, Gas Tank IP67 |
| Cabinet Material | Outer shell 2mm 304 stainless steel; internal partition panels 1.5mm cold-rolled steel, electrostatic powder coated |
| Installation Method | Outdoor floor-mounted |
| External Dimensions | 1800 mm (W) × 1200 mm (D) × 2200 mm (H) (customizable) |
| Cabinet Weight | Approx. 1200 kg |
| Compartments | 3 (gas tank compartment, cable compartment, instrument compartment) |
| Door Lock Type | Three-point anti-theft anti-pry lock |
| Sealing Strip | EPDM rubber, aging-resistant, wide temperature range, waterproof |
| Ambient Temperature | −30°C ~ +70°C |
| Relative Humidity | Daily average ≤95%, monthly average ≤90% |
| Altitude | ≤2000 m (reinforced insulation available for higher altitudes) |
| Seismic Resistance | Grade 8 intensity |
| Applicable Standards | GB 3906-2020, GB 4208-2017 |
6.2 Gas-Insulated Three-Position Load Switch
6.2.1 Load Switch-Fuse Combination Unit (For Incoming Feeder)
| Parameter | Value |
| — | — |
| Product Model | KITOZER-FLR-12/630 |
| Rated Voltage | 12kV |
| Rated Frequency | 50Hz |
| Rated Current | 630A |
| Rated Short-Circuit Breaking Current (fuse) | 50kA |
| Rated Short-Time Withstand Current | 20kA/4s |
| Rated Peak Withstand Current | 50kA |
| Rated Transfer Current | 1750A |
| Insulation Level | Power-frequency withstand: phase-to-phase & phase-to-earth 42kV/1min, across open contact 48kV/1min; Lightning impulse withstand: phase-to-phase & phase-to-earth 75kV (peak), across open contact 85kV (peak) |
| Arc-Extinguishing Medium | SF6 gas; capable of interrupting rated current even at zero gauge pressure |
| Gas Tank Filling Pressure | 0.04 MPa (20°C, gauge pressure) |
| Annual Gas Leakage Rate | ≤0.05% |
| Gas Tank Service Life | ≥30 years |
| Positions | Closed position, open position, earthing position |
| Operating Method | Motor-wound spring energy storage operation, manual operation as backup |
| Operating Power Supply | AC/DC 220V ±15% |
| Mechanical Life | ≥10,000 operations |
| Rated Active Load Current Interruption Cycles | ≥1,000 times |
| Short-Circuit Current Interruption Cycles | ≥50 times |
| Earthing Switch Parameters | Short-time withstand 20kA/4s, peak withstand 50kA |
| Interlock Function | Mechanical + electrical dual five-prevention interlocking to prevent misoperation |
| Installation Method | Fixed installation inside gas tank |
| Applicable Standards | GB 3804-2020, GB 16926-2009 |
6.2.2 Three-Position Load Switch (For Outgoing Feeder)
| Parameter | Value |
| — | — |
| Product Model | KITOZER-FL-12/630 |
| Rated Voltage | 12kV |
| Rated Current | 630A |
| Rated Short-Time Withstand Current | 20kA/4s |
| Rated Peak Withstand Current | 50kA |
| Rated Load Current Interruption Cycles | ≥1,000 times |
| Insulation level, gas tank parameters, operating method, mechanical life | Same as the incoming combination unit above |
| Key Difference | No fuse combination; provides load make/break, isolation, and earthing functions only, coordinated with upstream protection devices |
6.3 HV Current-Limiting Fuse
| Parameter | Value |
| — | — |
| Product Model | SDLAJ-12 |
| Rated Voltage | 12kV |
| Rated Current Range | 20A ~ 200A (selectable per requirement) |
| Rated Short-Circuit Breaking Current | 50kA |
| Cut-off Current at Rated Breaking Capacity | ≤25kA |
| Insulation Level | Power-frequency withstand 42kV/1min, lightning impulse 75kV peak |
| Protection Characteristics | Full-range protection; capable of interrupting current from overload to full short-circuit range |
| Fusing Characteristics | Conforms to GB 15166.2, gG/gL characteristics |
| Striker Function | Activates striker pin upon fuse operation, tripping the load switch for three-phase linked operation |
| Operating Temperature | −35°C ~ +55°C |
| Installation Method | Plug-in type, coordinated with load switch |
| Applicable Standards | GB 15166.2-2008, IEC 60282-1 |
6.4 Composite-Housing Zinc Oxide Surge Arrester
| Parameter | Value |
| — | — |
| Product Model | HY5WS-17/50 |
| Product Type | Gapless metal-oxide surge arrester |
| Rated Voltage | 17kV |
| Continuous Operating Voltage | 13.6kV |
| Nominal Discharge Current | 5kA |
| Lightning Impulse Residual Voltage (8/20 μs) | ≤50kV |
| Switching Impulse Residual Voltage (30/60 μs) | ≤42.5kV |
| Steep-Front Impulse Residual Voltage (1/5 μs) | ≤57.5kV |
| DC Reference Voltage (U1mA) | ≥24kV |
| Leakage Current at 0.75 U1mA | ≤50 μA |
| Rectangular Impulse Current Withstand | 200A, 2000 μs, 18 times |
| High-Current Impulse Withstand | 65kA, 4/10 μs, 2 times |
| Housing Material | High-temperature vulcanized silicone rubber; strong hydrophobicity, aging-resistant, UV-resistant |
| Mechanical Strength | Withstands 1000N lateral tensile force |
| Installation Method | Vertical installation, M10 bolt fixing |
| Ambient Temperature | −40°C ~ +70°C |
| Altitude | ≤2000 m |
| Applicable Standards | GB 11032-2020, IEC 60099-4 |
6.5 Cast-Resin Current Transformer
| Parameter | Value |
| — | — |
| Product Model | LZZBJ9-10A1G |
| Rated Voltage | 10kV |
| Rated Frequency | 50Hz |
| Current Ratio | Incoming: 200/5A; Outgoing: 100/5A (customizable) |
| Winding Configuration | Dual-winding: metering winding class 0.5, protection winding class 10P10 |
| Rated Secondary Current | 5A |
| Rated Output Capacity | Metering winding 15VA, protection winding 20VA |
| Accuracy Limit Factor | 10 |
| Instrument Security Factor | ≤5 |
| Insulation Level | Power-frequency withstand 42kV/1min, lightning impulse 75kV peak |
| Rated Short-Time Withstand Current | 20kA/1s |
| Rated Peak Withstand Current | 50kA |
| Dielectric Loss Tangent (tan δ) | ≤0.005 (at rated voltage) |
| Temperature Rise Limit | ≤55K |
| Housing Material | Epoxy resin integral casting; flame-retardant, arc-resistant, anti-pollution-flashover |
| Installation Method | Busbar-type / wall-bushing type |
| Ambient Temperature | −30°C ~ +40°C |
| Altitude | ≤1000 m |
| Applicable Standards | GB 1208-2016, IEC 61869-2 |
6.6 Main Busbar
| Parameter | Value |
| — | — |
| Material | T2 oxygen-free copper, purity ≥99.95% |
| Specification | TMY-80×8 mm (W×T) |
| Rated Current | 1250A |
| Short-Time Withstand Current | 25kA/4s |
| Peak Withstand Current | 63kA |
| Surface Treatment | Full tin plating, coating thickness ≥8 μm |
| Resistivity | ≤0.017241 Ω·mm²/m (at 20°C) |
| Hardness | ≥65 HV |
| Straightness | ≤1 mm/m |
| Applicable Standard | GB/T 5585.1-2018 |
6.7 Microcomputer Integrated Protection Device
| Parameter | Value |
| — | — |
| Product Model | KITOZER-MCP-100 |
| Application Scope | Protection, measurement and control for incoming/outgoing feeder circuits, distribution transformers and other circuits at 10kV and below |
| Operating Power Supply | AC/DC 85V ~ 265V wide-range input |
| Power Consumption | Normal operation ≤5W, during tripping ≤10W |
| AC Input | Voltage: 3×100V / 3×57.7V, burden ≤0.5VA/phase; Current: 3×5A / 3×1A, burden ≤0.5VA/phase; Frequency: 50Hz ±5% |
| Protection Functions | Three-stage phase-to-phase overcurrent protection (instantaneous, definite-time, overcurrent), independently configurable; Two-stage zero-sequence overcurrent protection (earth fault protection); Overvoltage protection, undervoltage protection; Overload alarm / trip protection; Control circuit disconnection alarm; PT disconnection alarm; Spring not-charged alarm; Fault recording — stores 8 fault waveforms |
| Measurement & Control Functions | Telemetry: three-phase voltage, three-phase current, active power, reactive power, power factor, frequency; Tele-signaling: 16 digital inputs, dry contacts; Remote control: 4 relay outputs, supports close/trip control |
| Measurement Accuracy | Voltage & current: class 0.2; Power & energy: class 0.5; Frequency: ±0.01Hz |
| Communication Functions | Standard: 2× RS485 interfaces, supports Modbus-RTU and IEC 60870-5-103 protocols; Optional: Ethernet interface supporting IEC 60870-5-104 protocol; Baud rate: 1200 ~ 115200 bps, configurable |
| HMI | 128×64 dot-matrix LCD, Chinese menu, 6 operation keys, LED indicators for running, alarm, and trip status |
| Output Contact Capacity | Trip output 5A/250VAC, signal output 3A/250VAC |
| Insulation Performance | Power-frequency withstand 2kV/1min between power supply, inputs, and outputs |
| EMC Compliance | Complies with GB/T 14598 series standards, class 4 immunity level |
| Operating Environment | Temperature −20°C ~ +70°C, humidity ≤95% non-condensing |
| Installation Method | Flush-mounted, panel cutout 104×104 mm |
| External Dimensions | 120 mm (W) × 120 mm (H) × 110 mm (D) |
| Weight | Approx. 0.8 kg |
| Applicable Standards | GB/T 14285-2006, DL/T 478-2013 |
6.8 Multifunction Power Meter
| Parameter | Value |
| — | — |
| Product Model | KITOZER-PM-96 |
| Product Type | Three-phase network multifunction power meter |
| Operating Power Supply | AC/DC 85V ~ 265V |
| Power Consumption | ≤3W |
| Input Signals | Voltage: three-phase three-wire / three-phase four-wire switchable, rated 100V / 380V; Current: rated 5A / 1A, CT ratio configurable; Frequency: 45Hz ~ 65Hz |
| Measurement Functions | Basic parameters: three-phase voltage, three-phase current, zero-sequence current, active power, reactive power, apparent power, power factor, frequency; Energy metering: forward/reverse active energy, forward/reverse reactive energy, four-quadrant metering; Harmonic analysis: 2nd ~ 31st harmonic content, total harmonic distortion (THD); Demand measurement: maximum active demand, maximum reactive demand |
| Measurement Accuracy | Voltage & current: class 0.2; Active power & active energy: class 0.5; Reactive power & reactive energy: class 1; Frequency: ±0.01Hz |
| Display | 96×96 dot-matrix LCD backlit display, cycling/paging display configurable |
| Inputs/Outputs | Digital inputs: 4 dry contacts; Relay outputs: 2, capacity 5A/250VAC; Optional analog output: 4~20mA |
| Communication | 1× RS485 interface, Modbus-RTU protocol, baud rate configurable |
| Insulation Performance | Power-frequency withstand 2kV/1min between power supply, inputs, and outputs |
| Operating Environment | Temperature −10°C ~ +55°C, humidity ≤93% non-condensing |
| Installation Method | Flush-mounted, panel cutout 91×91 mm |
| External Dimensions | 96 mm × 96 mm × 85 mm |
| Weight | Approx. 0.5 kg |
| Applicable Standards | GB/T 22264.1-2008, DL/T 614-2007 |
6.9 Temperature and Humidity Controller
| Parameter | Value |
| — | — |
| Product Model | KITOZER-WSK-100 |
| Functions | Real-time temperature & humidity monitoring; automatic control of heating and ventilation; anti-condensation |
| Operating Power Supply | AC220V ±15%, 50Hz |
| Power Consumption | ≤3W |
| Sensors | NTC temperature sensor + capacitive humidity sensor |
| Measuring Range | Temperature −40°C ~ +125°C; humidity 0 ~ 100%RH |
| Measurement Accuracy | Temperature ±0.5°C; humidity ±3%RH |
| Control Outputs | Heating output: 1 relay channel, capacity 5A/220VAC; Fan output: 1 relay channel, capacity 5A/220VAC |
| Control Logic | Auto-starts heating/dehumidification when humidity exceeds set value; starts heating below low-temperature setpoint; starts fan above high-temperature setpoint |
| Parameter Setting | On-site keypad configuration of temperature/humidity thresholds; settings retained through power loss |
| Display | LED digital display, switchable between temperature/humidity |
| Alarm Function | Sensor fault alarm indication |
| Installation Method | DIN-rail / panel mounting |
| External Dimensions | 48 mm × 48 mm × 78 mm |
| Operating Environment | −20°C ~ +70°C |
| Applicable Standard | JB/T 10684-2006 |
6.10 Cable Sealing Gland
| Parameter | Value |
| — | — |
| Product Model | KITOZER-GL-M50 |
| Suitable Cable Outer Diameter | φ30 mm ~ φ42 mm |
| Thread Specification | M50×1.5 |
| Protection Rating | IP66 / IP68 |
| Body Material | 304 stainless steel |
| Seal Material | NBR (nitrile rubber); silicone rubber optional |
| Explosion-Proof Rating | Exd II CT6 (optional) |
| Temperature Range | −40°C ~ +120°C |
| Protection Performance | Waterproof, dust-proof, corrosion-resistant, vibration-resistant, pull-out resistant |
| Installation Method | Panel hole mounting, thread-locking |
| Applicable Standards | GB 4208-2017, IEC 60529 |
—
7. Solution Advantages and Features
7.1 High Reliability with Maintenance-Free Operation
- Core switching devices feature a fully sealed SF6 gas tank structure with IP67 protection — internal components are completely isolated from the external environment, unaffected by dust, moisture, or corrosive agents, ensuring stable operation.
- The gas tank is manufactured with stainless steel laser welding; annual gas leakage rate ≤0.05% — well below national standard requirements. Normal service life ≥30 years with no routine gas refilling required.
- Proven SF6 arc-extinguishing technology delivers reliable interruption performance with a mechanical life of ≥10,000 operations and consistently low failure rates over extended service periods.
- A comprehensive five-prevention interlock mechanism — with both mechanical and electrical dual interlocking — eliminates the risk of misoperation at the source.
7.2 Strong Environmental Adaptability for All Scenarios
- 304 stainless steel enclosure with IP54 overall protection: rain-proof, dust-proof, anti-rust, and corrosion-resistant — engineered for harsh coastal, chemical, and industrial environments.
- Wide-temperature design ensures stable operation from −30°C to +70°C, accommodating both extreme northern cold and southern tropical heat.
- Dual anti-condensation design: the double-layer cabinet structure minimizes temperature differentials, while the intelligent temperature/humidity control system automatically heats and dehumidifies to prevent insulation failures caused by internal condensation.
- Cable entries/exits use IP68-rated sealed glands, blocking moisture infiltration from cable trenches.
7.3 High-Level Intelligence for Distribution Automation
- Each circuit is independently equipped with a microcomputer protection device featuring comprehensive protection functions, precise and rapid operation, and fault clearing time ≤40 ms.
- Multifunction power meters deliver full electrical parameter, harmonic, and energy monitoring — complete distribution status visualization.
- Standard communication interfaces and protocols enable seamless integration with distribution automation systems, providing remote measurement (telemetry), remote signaling (tele-indication), and remote control (tele-control) — the full “Three Remote” functionality.
- Fault recording and event logging capture complete pre-fault and post-fault waveforms and operational events, facilitating thorough fault analysis and traceability.
- Supports both local and remote operation modes — field manual operation and remote monitoring/control — meeting unattended substation requirements.
7.4 Safe and Convenient O&M with Lower Lifecycle Costs
- Modular design with independent circuits: maintenance on a single circuit does not interrupt other circuits, minimizing outage scope.
- Integrated three-position design provides clear visible disconnection points and earthing points, ensuring safe maintenance working conditions.
- Well-organized internal layout with ergonomic operating heights, adequate illumination, and clearly labeled wiring terminals for easy inspection and maintenance.
- The core gas tank is maintenance-free — only routine visual inspection and simple cleaning are required, significantly reducing O&M workload and costs.
- Full lifecycle service support: manufacturer-direct spare parts availability and responsive technical assistance.
7.5 Customization Services for Flexible Requirement Matching
- Configuration options include circuit quantity, current ratings, protection levels, materials, and external dimensions can all be customized to actual project requirements.
- Free solution design, electrical schematic diagrams, and 3D layout drawings — tailor-made optimal solutions for each project.
- Flexible production capacity with short delivery lead times, capable of meeting urgent project supply demands.
- Deep customization support for communication protocols, protection logic, and secondary circuits — easily adapted to existing monitoring systems.
—
8. Technical Q&A
8.1 Product Technology
Q1: What is the difference between an outdoor RMU cabinet and an RMU switchgear?
A: The core function is the same — both are ring-main distribution devices. The main differences lie in application scenarios and protection ratings. RMU switchgear generally refers to indoor-installed switchgear with lower protection ratings (typically IP20/IP3X), requiring installation within a dedicated electrical room. An outdoor RMU cabinet is specifically designed for exposed outdoor environments — offering higher protection (IP54 and above), corrosion resistance, condensation prevention, and rain protection — and can be directly floor-mounted outdoors without the need for a separate switchgear building, saving significant civil construction costs and space.
Q2: What is a three-position load switch, and what is the function of each position?
A: The three-position load switch integrates the functions of a load switch, disconnector, and earthing switch into a single device, switching between three working positions via one operating mechanism:
- Closed position: the main circuit is energized and supplying power normally; load current can be made and broken.
- Open position: the main circuit is interrupted, forming a visible disconnection point — fulfilling the function of a disconnector and ensuring maintenance safety.
- Earthing position: the outgoing side is reliably connected to the earthing bar, discharging any residual charge to ground and protecting maintenance personnel.
The three positions are mechanically interlocked so that it is physically impossible to occupy two positions simultaneously. The design structurally guarantees the safe operating sequence of “open first, then earth” and “disconnect earthing first, then close.”
Q3: What exactly does the “five-prevention” interlocking refer to in an RMU cabinet?
A: The five-prevention function is a mandatory safety requirement for HV switchgear — a cornerstone of electrical safety. It specifically includes:
- Prevention of mis-tripping or mis-closing of the load switch;
- Prevention of making/breaking the disconnector under load;
- Prevention of closing the earthing switch while the circuit is energized;
- Prevention of closing the circuit while the earthing switch is in the closed position;
- Prevention of unauthorized access to energized compartments.
This solution implements all five functions through dual mechanical + electrical interlocking: the inherent mechanical structure of the three-position switch naturally addresses the first four items; the cabinet door is interlocked with the earthing switch — the cable compartment door can only be opened when the earthing switch is closed — achieving the fifth, preventing access to live compartments.
Q4: Is the SF6 gas in the gas-insulated RMU toxic? Will it leak?
A: Pure SF6 gas is colorless, odorless, non-toxic, non-flammable, and chemically inert — inherently harmless to humans. Only under the extreme conditions of a high-temperature arc does it decompose into small amounts of toxic low-fluoride compounds, which does not occur in normal operation.
Regarding leakage: the gas tank in this equipment is fabricated using laser-welded stainless steel plates with mature, proven sealing technology. The annual leakage rate is ≤0.05% — far below the national standard requirement of 0.5%. Within the normal service life (30 years), no gas refilling is required — this is a maintenance-free design. The equipment is fitted with a gas pressure gauge for real-time pressure monitoring, with automatic alarms in the event of any anomaly.
Q5: Can the RMU cabinet support remote control? Which communication protocols are supported?
A: Yes, remote control is fully supported. The microcomputer protection devices and power meters configured in this solution come standard with communication interfaces, enabling full “Three Remote” functionality:
- Remote measurement (Telemetry): remotely view voltage, current, power, energy, and other operational data;
- Remote signaling (Tele-indication): remotely receive switch status, fault alarms, protection operations, and other signals;
- Remote control (Tele-control): remotely issue close/trip commands to control switch operation.
Communication protocols support standard Modbus-RTU and IEC 60870-5-103, with an optional IEC 60870-5-104 Ethernet protocol — directly interfacing with the user’s distribution automation system, power monitoring system, or energy management system.
Q6: What do the “0.5 class” and “10P10” ratings on the current transformer mean?
A: These are accuracy classifications for the two different windings of the current transformer, each serving a distinct purpose:
- Class 0.5: the accuracy class of the metering winding. It means the ratio error does not exceed ±0.5% at rated current — a high level of accuracy used for energy metering, current monitoring, and other applications requiring precise measurement.
- 10P10: the accuracy class of the protection winding. “10” indicates the composite error does not exceed 10%; “P” denotes protection class; and the second “10” represents the accuracy limit factor — meaning when the primary current reaches 10 times the rated current, the composite error still remains within 10%. The protection winding does not require high precision under normal measurement conditions, but it must accurately transform the signal during short-circuit fault currents to ensure correct protection device operation.
—
8.2 Installation and Construction
Q1: What are the requirements for the installation foundation of an outdoor RMU cabinet?
A: Outdoor RMU cabinets require a cast concrete foundation. Specific requirements are as follows:
- Foundation dimensions: length and width should be 100~200 mm larger than the cabinet footprint; height raised 200~300 mm above ground level to prevent water accumulation;
- Foundation material: C25 or higher grade reinforced concrete, with structural strength meeting the load-bearing requirements;
- Embedded channel steel: a No. 10 hot-dip galvanized channel steel base should be embedded at the foundation top, leveled and fixed, with the cabinet body bolted to it;
- Grounding requirements: an earthing grid should be laid around the foundation, with grounding resistance ≤4Ω; the base must have no fewer than 2 reliable connection points to the earthing grid;
- Cable provisions: cable conduits should be pre-embedded in the foundation, with diameters determined by cable quantity, and pipe openings sealed and waterproofed.
Q2: What tests are required after installation of the RMU cabinet?
A: Commissioning tests must be completed after installation before the equipment is energized. The main test items include:
- Insulation resistance test: primary circuit phase-to-phase and phase-to-earth insulation resistance ≥1000 MΩ; secondary circuit ≥1 MΩ;
- Power-frequency withstand voltage test: primary circuit 42kV/1min with no breakdown or flashover; secondary circuit 2kV/1min;
- Circuit resistance test: main circuit contact resistance meets product technical requirements, with no poor contacts;
- Mechanism operation test: 5 manual and 5 electric close/trip operations each — smooth operation, no sticking, correct position indication;
- Interlock function test: verify correct five-prevention interlock logic and reliable operation;
- Protection trip test: simulate fault quantities to verify correct protection operation, proper output/exit, and accurate signal transmission;
- Communication function test: integrate with the backend system, verify accurate data upload and reliable remote control;
- Grounding resistance test: equipment grounding resistance ≤4Ω.
Q3: What are the grounding requirements for an outdoor RMU cabinet?
A: Grounding is critical to protecting both equipment and personnel safety. The following requirements must be met:
- A dedicated earthing grid must be installed, with grounding resistance ≤4Ω;
- The metal enclosure, base, and earthing busbar must be reliably connected to the earthing grid at no fewer than 2 connection points;
- Grounding conductors shall be 40×4 mm hot-dip galvanized flat steel or stranded copper conductors of ≥16 mm², with hot-dip galvanized connection bolts and electrical contact grease applied to contact surfaces;
- Cabinet doors must be bridged to the cabinet body using braided copper straps to ensure electrical continuity;
- Clear grounding markings must be provided at grounding points, with grounding bolt size no smaller than M10.
—
Guangzhou Lain Intelligent System Development Co., Ltd. (KITOZER)
Phone/WhatsApp/WeChat: +86 13538869979 / +86 13538869979
Website: https://gdlain.com
Address: Huashan Road 5, Shilou Town, Panyu District, Guangzhou, Guangdong, China
8.3 Operation & Maintenance FAQs
Q1: What routine maintenance does an outdoor Ring Main Unit (RMU) require, and how often?
A: This solution features a hermetically sealed, maintenance-free gas-insulated design, requiring minimal routine maintenance. The key maintenance tasks and intervals are as follows:
Daily/Routine Inspection (Once per Month)
- Visual inspection of the enclosure for deformation, corrosion, or damage
- Check that door locks and sealing gaskets are intact
- Verify the gas pressure gauge is within the normal operating range
- Confirm indicator lights and meter displays are functioning correctly
- Listen for any abnormal noises or detect any unusual odors
Quarterly Maintenance (Every 3 Months)
- Clean the enclosure surface and ventilation dust filters
- Verify the anti-condensation heater is operating correctly
- Check that earth connections are secure
- Confirm cable sealing integrity
Annual Overhaul (Once per Year)
- Operating mechanism test: manual and electric open/close operations
- Secondary circuit tightening and insulation resistance checks
- Protection device functional verification
- Online arrester testing (live-line)
- Earth resistance measurement
The core gas-insulated tank requires no maintenance under normal operation. Gas humidity and purity may be tested once every 3–5 years.
Q2: What should be done if condensation occurs in the Ring Main Unit? How can it be prevented?
A: Condensation is a common issue for outdoor equipment, typically caused by large temperature differences between day and night and high ambient humidity. This solution incorporates multiple preventive design measures. If condensation occurs during operation, follow these steps:
- Check that the temperature and humidity controller and heater are operating normally, and verify that the humidity threshold settings are appropriate
- Inspect the enclosure sealing integrity — check door gaskets and cable glands for gaps and repair any seal breaches
- Check the ventilation dust filters for blockage to ensure proper airflow and heat dissipation
- If water accumulates in cable trenches, seal the cable duct openings to prevent moisture from rising into the enclosure
- Install auxiliary dehumidifying devices or desiccant at appropriate locations inside the enclosure to assist with moisture reduction
Q3: What should be done if the load switch operating mechanism becomes stiff or jammed?
A: Mechanism jamming is rare under normal conditions. If it occurs, troubleshoot using the following steps:
- First verify that the operating power supply is normal and the voltage is within the allowable range
- Check for interlocking conditions — e.g., earth switch not fully engaged, cabinet door not closed — release interlocks before attempting operation
- Try manual operation to determine whether the issue is mechanical binding or an electrical circuit fault
- If mechanically jammed, apply appropriate lubricating grease to the transmission parts and check for foreign object obstruction
- If an electrical issue, inspect the closing coil, tripping coil, and auxiliary switch contacts
- If the issue cannot be resolved on-site, contact the manufacturer’s after-sales service promptly. Do not force the mechanism, as this may cause damage
—
8.4 Selection & Procurement FAQs
Q1: How are the number of circuits and current ratings for a Ring Main Unit determined?
A: The number of circuits and current ratings are determined by the actual power supply requirements:
Number of Circuits: Determined by the number of incoming power feeder lines and outgoing feeder circuits. Common configurations include 1-in/2-out, 2-in/2-out, 2-in/4-out, 3-in/3-out, etc. Ring main configurations generally require at least 2 incoming lines to establish a tie/loop connection. The number of outgoing circuits is based on downstream load circuits, with provision for spare/reserve circuits.
Current Rating: The main busbar current is calculated based on total load; branch circuit current is determined by the maximum load current of each individual circuit, with an appropriate design margin. For 10kV Ring Main Units, the standard rated current is typically 630A — for heavier loads, 1250A is available.
Short-Circuit Rating: Determined by the upstream source short-circuit capacity. The standard rating is 20kA; for areas with higher short-circuit capacity, 25kA is available.
Selection and design are confirmed per project based on user-provided single-line diagrams or load specifications.
Q2: What are the differences between gas-insulated (SF6) and air-insulated Ring Main Units?
A: Each type has distinct characteristics — the choice depends on the application environment:
| Comparison Aspect | Gas-Insulated (SF6) RMU | Air-Insulated RMU |
| — | — | — |
| Footprint | Compact, space-saving design | Larger physical footprint |
| Protection & Environmental Adaptability | Fully sealed construction; excellent adaptability for outdoor, humid, dusty environments | Lower protection rating; requires clean, dry indoor environments |
| Maintenance | Hermetically sealed tank — maintenance-free; minimal overall maintenance | Bare contacts exposed; regular cleaning and inspection required; higher maintenance demand |
| Service Life | Extended lifespan — 30+ years | Relatively shorter; susceptible to environmental degradation |
| Initial Cost | Slightly higher initial investment | Lower initial cost |
| Environmental Considerations | SF6 gas recovery required at end-of-life | No greenhouse gas concerns |
Selection Recommendation: For outdoor installations, harsh environmental conditions, and applications requiring minimal maintenance, the gas-insulated Ring Main Unit is the preferred choice. For indoor substation installations with controlled environments, air-insulated switchgear is a suitable alternative.
—
9. Construction Schedule & Project Timeline
| Phase | Work Item | Duration (Days) | Responsible Party | Cooperating Party | Remarks |
| — | — | — | — | — | — |
| 1 | Project coordination & design confirmation | 2 | Project Manager | Client | Confirm final technical scheme, parameters, delivery schedule |
| 2 | Raw material procurement & production preparation | 3 | Production Dept. | Procurement Dept. | Core components, sheet metal, auxiliary materials bought & stored |
| 3 | Enclosure fabrication & assembly | 7 | Production Dept. | Quality Control Dept. | Sheet metal processing, painting, component assembly, busbar fabrication |
| 4 | Secondary wiring & factory commissioning | 3 | Electrical Dept. | Quality Control Dept. | Secondary circuit wiring, power-on test, protection settings, factory inspection |
| 5 | Packaging & transportation | 2 | Logistics Dept. | Client | Moisture-proof & shock-proof packaging; dedicated transport to site |
| 6 | On-site arrival inspection | 1 | Project Manager | Client | Open-box acceptance; verify quantity, appearance, documentation |
| 7 | Foundation works & earth grid installation | 5 | Construction Crew | Client | Concrete foundation pouring, channel steel embedding, earth grid (can run in parallel with production) |
| 8 | Unit positioning & fixing | 1 | Installation Team | Client | Hoisting, leveling, anchoring, earth connection |
| 9 | Primary cable laying & termination | 3 | High-voltage Electricians | Client | Cable termination fabrication, connection, phase sequence verification |
| 10 | Secondary wiring & inspection | 2 | Secondary Electricians | Technical Dept. | Control, signaling, power, communication circuit wiring & inspection |
| 11 | Handover tests & commissioning | 2 | Commissioning Engineers | Client | Insulation, withstand voltage, operation, protection, communication tests |
| 12 | Live run / trial operation | 3 | Commissioning Engineers | Client | 72-hour energized trial run; record operating data |
| 13 | Completion acceptance & documentation handover | 1 | Project Manager | Client | Joint acceptance sign-off; complete documentation handover |
Total Duration (including manufacturing): 30 days
Note: Foundation construction can proceed in parallel with production — fastest delivery in 20 days where site conditions permit.
—
10. Construction Organization Plan
10.1 Construction Organization Structure
To ensure high-quality and timely project delivery, a dedicated project team is established with the following personnel:
| Role | Qty | Responsibilities |
| — | — | — |
| Project Manager | 1 | Overall project coordination, schedule control, quality supervision, client liaison; accountable for schedule, quality and safety |
| Technical Lead | 1 | Technical disclosure, on-site technical guidance, commissioning plan preparation, resolution of technical issues; ensures construction complies with design and code requirements |
| Construction Crew Leader | 1 | On-site personnel deployment, work sequencing, site safety management; implements schedule and workmanship requirements |
| High-voltage Electricians | 2 | Certified; primary equipment installation, cable laying, cable termination fabrication, primary wiring, HV testing |
| Secondary Electricians | 2 | Certified; secondary circuit wiring, instrument installation, communication wiring, secondary circuit inspection & commissioning |
| Safety Officer | 1 | On-site safety management, safety briefings, safety inspections, safety documentation; eliminates safety incidents |
| Quality Inspector | 1 | Quality inspection at all construction stages, concealed works inspection, test record compilation, completion quality inspection |
10.2 Pre-Construction Preparation
10.2.1 Technical Preparation
- Organize construction personnel to study the construction drawings, design documentation, and applicable standards and codes; conduct detailed technical disclosure
- Prepare specialized construction plans and work instructions defining process requirements, quality standards, and safety precautions for each work stage
- Prepare construction record sheets, test report templates, and acceptance documentation templates
10.2.2 Materials & Tools Preparation
- Deliver equipment, primary materials, and auxiliary materials to site in advance; arrange by category with rain, moisture, and theft protection measures
- Perform open-box acceptance of equipment; verify model, specification, and quantity; inspect for transport damage; collect certificates, manuals, and test reports
- Prepare construction tools and instruments: HV voltage detectors, insulation resistance testers, earth resistance testers, contact resistance testers, torque wrenches, electrician’s tools, PPE, etc. Ensure tools are in good condition and instruments are within calibration validity
10.2.3 Site Preparation
- Confirm on-site construction conditions: civil foundation completed, ground leveled, temporary power connected, access roads clear
- Designate construction zones with safety warning signs and barricades to prevent unauthorized entry
- Arrange temporary material storage and tool storage areas in an orderly manner
10.3 Major Construction Procedures & Workmanship Requirements
10.3.1 Foundation & Earthing Works
- Excavate foundation pit per drawing dimensions, compact the base, pour C25 concrete foundation
- Embed 10# hot-dip galvanized channel steel base on foundation top; level with surveyor’s level, horizontal tolerance ≤ 2mm/m
- Install 40×4mm hot-dip galvanized flat steel earth grid around foundation perimeter; drive ∠50×5×2500mm galvanized angle steel earth electrodes; earth resistance ≤ 4Ω
- Connect channel steel base to earth grid at minimum 2 points with hot-dip galvanized bolts; apply conductive compound on contact surfaces
10.3.2 Unit Installation
- Use crane or manual handling for positioning; protect enclosure surfaces from impact or scratching
- Verify verticality with spirit level and plumb line; tolerance ≤ 1.5‰
- Secure unit to base with bolts; ensure firm anchoring without movement
- Connect unit earth terminal to earth busbar reliably; bond doors to frame with braided copper straps
10.3.3 Primary Cable Termination & Connection
- Perform insulation test on cables before laying; proceed only after passing
- Route cables through bottom cable entry; secure and seal with compression cable glands with waterproofing
- Fabricate cold-shrink/heat-shrink cable terminations in accordance with industry standards
- Use copper-tinned lugs for termination; crimp securely, apply conductive compound, torque bolts to specified values
- Verify phase sequence: A-phase yellow, B-phase green, C-phase red; phase identification markings complete and legible
10.3.4 Secondary Circuit Wiring
- Use stranded copper-core insulated flexible wire; voltage circuits 1.5mm², current circuits 2.5mm²
- Wiring neat, secure, and orderly; cable bundles tied evenly with horizontal and vertical routing
- Wire number sleeves clear, legible, correctly matched, and uniformly oriented
- Terminal block connections firm; no more than 2 wires per terminal; spare cores left with adequate length
- Shielded cables: ground shield at single end only; ensure reliable earthing
- After wiring completion, perform continuity checks and insulation testing; secondary circuit insulation resistance ≥ 1MΩ
10.3.5 Commissioning & Testing
- Before energizing, comprehensively verify wiring correctness; confirm no short circuits or misconnections
- Perform insulation and power-frequency withstand voltage tests per applicable standards
- Conduct mechanism operation tests — manual and electric open/close operations smooth with correct position indication
- Perform interlock tests to verify five-prevention logic functions are correct
- Conduct protection trip tests — simulate fault quantities, verify protection operates accurately with correct output and signaling
- Perform communication commissioning — integrate with supervisory system, verify data upload accuracy and remote control reliability
10.4 Quality Control Measures
- Strictly implement the “Three-Inspection” system: self-inspection, peer-inspection, and dedicated inspection; non-conforming work from a previous process shall not proceed to the next process
- All raw materials and equipment must have certificates of conformity and test reports; only materials passing incoming inspection may be used
- Critical processes and concealed works must be inspected and signed off by the client before covering
- Strictly follow construction drawings, workmanship standards, and code requirements; no unauthorized design changes
- Maintain complete and traceable construction and test records
- Perform comprehensive completion inspection upon project close-out; issue completion report
10.5 Safety Management Measures
- All construction personnel must hold valid work permits and wear safety helmets on site; safety harnesses required for elevated work
- Strictly implement work permit system and de-energization procedures — isolate, verify de-energized, ground, tag, and install barriers to ensure safe work on de-energized systems
- High-voltage testing requires safety barriers, dedicated supervision, and verbal call-and-response confirmation that the test zone is clear before energization
- On-site temporary power supply complies with regulations; distribution boxes fitted with residual current devices; cables elevated or conduit-protected; no unauthorized wiring
- Fire-fighting equipment provided; hot work requires a hot work permit with dedicated supervision
- Pre-shift safety briefings conducted daily; post-shift safety inspections performed; hazards eliminated promptly
- Emergency response plan established; contingency situations handled per plan
—
11. After-Sales Service Plan
11.1 Warranty Service Commitment
| Item | Commitment |
| — | — |
| Warranty Period | 2-year comprehensive warranty on equipment, effective from the date of completed acceptance and sign-off |
| Warranty Coverage | Free repair, free replacement of components, and free on-site service for failures caused by equipment quality or manufacturing process defects during the warranty period |
| Software Upgrades | Free software upgrade services for protection devices and monitoring systems during the warranty period |
| Exclusions | Damage caused by intentional misuse, force majeure events, or improper operation is not covered under the free warranty; only cost-price charges apply |
11.2 Response Time Commitment
| Service Type | Response Standard |
| — | — |
| Technical Consultation | Telephone technical support hours are confirmed on the quotation |
| General Faults | On-site response time is confirmed on the quotation |
| Major Faults | Senior engineer dispatched within 2 hours of report; problem resolved within 48 hours |
| Extended Repairs | Where on-site repair is not immediately possible, backup equipment or emergency solutions provided to minimize power supply interruption |
11.3 Regular Inspection Service
- During the warranty period, a free on-site inspection is provided every six months for a comprehensive equipment status check
- Inspection coverage: visual inspection, mechanism operation testing, insulation testing, protection function verification, communication checks, anti-condensation device inspection, grounding checks, hardware tightening, etc.
- A formal inspection report is issued after each visit, including maintenance recommendations and optimization proposals; a complete equipment operation file is established
11.4 Spare Parts Service
- A comprehensive spare parts inventory is maintained, including load switch mechanisms, microprocessor-based protection devices, heaters, indicator lights, fuses, terminals, and other consumable/wear parts
- Faulty spare parts are replaced free of charge during the warranty period; after warranty, genuine original parts are supplied at cost price for the equipment’s lifetime
- Emergency spare parts can be delivered to site within 48 hours to ensure repair efficiency
11.5 Lifetime Maintenance Service
- After warranty expiration, lifetime technical support and maintenance services are available; annual maintenance agreements can be signed at preferential service rates
- Equipment upgrade and retrofit services available — protection functions, communication systems, and intelligent features can be upgraded per user requirements
- Technical guidance and construction services for equipment relocation and capacity expansion projects
—
12. Operator Training Plan
12.1 Training Objectives
Through systematic theoretical and hands-on training, client operations personnel will:
- Become familiar with the RMU structure, operating principles, and primary/secondary system composition
- Master proper equipment operating methods, operational procedures, and safety standards
- Understand the content and methods for routine inspection and preventive maintenance
- Be able to identify common faults, handle simple faults, and follow emergency response procedures
- Correctly read operational data, review fault records, and cooperate with specialist maintenance personnel
12.2 Training Participants
Target participants: Client power distribution operations & maintenance personnel, electricians, and management staff — recommended 3–5 persons with basic electrical knowledge and safety awareness.
12.3 Training Content
12.3.1 Theoretical Training
- 10kV RMU structure, operating principles, and primary main connection configurations
- Principles and functions of primary components: load switches, fuses, surge arresters, instrument transformers
- Principles and functions of secondary equipment: microprocessor-based protection devices, power meters, temperature/humidity controllers
- Five-prevention interlock principles and safe operation standards
- Electric power safety work regulations and high-voltage operation safety precautions
12.3.2 Hands-On Operational Training
- Local manual open/close and earthing operations of load switches
- Electric open/close operations of load switches
- Local/remote mode selection operation
- Protection device menu navigation, parameter viewing, and event record retrieval
- Power meter reading and operation
- Safe de-energization work sequence: isolate, verify de-energized, ground, tag
12.3.3 Maintenance & Fault Handling Training
- Routine inspection content, frequency, and methods
- Equipment maintenance precautions
- Common fault identification: alarm signal interpretation, fault symptom analysis
- Simple fault handling methods
- Emergency response procedures and escalation mechanisms
12.4 Training Format & Duration
| Item | Details |
| — | — |
| Training Format | On-site face-to-face training: theoretical presentation + hands-on demonstration + trainee practice + Q&A session |
| Duration | 1 full day total: half-day theory, half-day practical; schedule flexible to accommodate client requirements |
| Training Materials | Operation manuals, maintenance manuals, and training presentation provided in both electronic and printed formats |
12.5 Assessment & Certification
- Written Examination: Assesses fundamental principles, safety regulations, and O&M knowledge
- Practical Assessment: Evaluates standard operation procedures, fault identification, and simple fault handling
- Trainees who pass receive a training completion certificate; those who do not pass receive free retraining until competency is achieved
—
13. Reference Project Case Studies
13.1 Industrial Park 10kV Ring Main Power Supply Project
Project Background: A newly constructed standardized factory complex within a provincial economic development zone, totaling 200,000m² of building area. A 10kV outdoor ring main distribution system was required to provide dual-power supply, ensuring production supply reliability while meeting distribution network automation requirements.
Solution Configuration: A total of 8 units of KITOZER series outdoor Ring Main Units, all in 2-in/4-out configuration, with SF6 gas-insulated 3-position load switches, 630A rated current, 20kA short-circuit withstand. Each circuit configured with a microprocessor-based integrated protection device and multifunction power meter; fiber-optic communication integrated with the park’s distribution automation system. 304 stainless steel enclosure with IP54 protection rating and intelligent anti-condensation design.
Project Outcome: Commissioned in 2023 with stable, reliable operation; power supply reliability achieved 99.99%. Remote monitoring and rapid fault location enabled — fault isolation time reduced from hours to minutes. Substantially reduced the park’s O&M workload, earning high praise from both the park management committee and resident enterprises.
13.2 Urban Old-District Distribution Network Upgrade Project
Project Background: Municipal road renovation project in an older city district. Existing pole-mounted switchgear had severely aged, with low protection ratings, high failure rates, and frequent outages disrupting residents. Full replacement with outdoor Ring Main Units was required to improve distribution network reliability and intelligence.
Solution Configuration: 12 floor-standing outdoor Ring Main Units in 1-in/3-out configuration, 630A rated current. 304 stainless steel enclosures suited to outdoor rain, snow, and dusty conditions. Equipped with intelligent section switches featuring automatic fault isolation. Temperature/humidity control systems installed to resolve winter condensation issues.
Project Outcome: Completed and commissioned in 2022. Equipment withstood summer storms and winter low temperatures without water ingress or condensation failures. Equipment failure rate reduced by 90%; power outage frequency and duration significantly reduced. Resident satisfaction improved notably, with favorable recognition from the local power supply company.
13.3 Data Center External Line Ring Network Project
Project Background: A Tier III data center project with extremely high power supply reliability requirements. The external power infrastructure required a ring network architecture with dual-power redundancy and rapid fault switching to ensure uninterrupted power to the data center.
Solution Configuration: 4 high-voltage RMU switchgear units forming a ring network. Incoming feeders protected by load switch-fuse combination units. High-precision microprocessor-based protection devices for rapid fault clearance. Dual redundant communication configuration integrated with the data center’s environment monitoring system (DCIM). Fully sealed gas-insulated construction for maximum reliability.
Project Outcome: In operation since 2024 with zero equipment failures. Protection operation accuracy achieved 100%. Power source transfer times meet all data center requirements, providing reliable distribution assurance for the data center’s safe and stable operation.
—
14. SEO Optimization Framework
14.1 Keyword Classification
Core Primary Keywords
| Keyword |
| — |
| 10kV Ring Main Unit |
| Outdoor Ring Main Unit |
| High-voltage Ring Main Switchgear |
| RMU Manufacturer |
High-Conversion Long-Tail Keywords
| Keyword |
| — |
| 10kV outdoor floor-standing RMU |
| Gas-insulated RMU manufacturer |
| Stainless steel outdoor RMU |
| Smart RMU price |
| 2-in/4-out RMU |
| Custom outdoor RMU |
| HV RMU technical specifications |
| RMU configuration checklist |
Industry Traffic Keywords
| Keyword |
| — |
| 10kV distribution RMU |
| Outdoor high-voltage ring main switchgear |
| Pole-mounted ring main unit |
| Ring-type cable branch box |
| Distribution automation RMU |
| 3-position load switch RMU |
| Anti-condensation RMU |
| Outdoor sectioning station |
Brand-Specific Keywords
| Keyword |
| — |
| KITOZER RMU |
| KITOZER ring main switch |
| Lain RMU |
| Guangzhou Lain ring main switchgear |
Suggestion / Related Search Keywords
| Keyword |
| — |
| Difference between RMU and ring main switchgear |
| Function of RMU |
| RMU protection rating |
| RMU five-prevention interlock |
| RMU installation and construction plan |
| RMU operation and maintenance |
| RMU price per unit |
| RMU manufacturer ranking |
14.2 SEO Tag Configuration
| Element | Content |
| — | — |
| Page Title | 10kV Outdoor RMU_HV Smart Ring Main Switchgear Manufacturer_Custom 2-in/4-out RMU Solution – KITOZER |
| Meta Keywords | 10kV RMU, outdoor RMU, HV ring main switchgear, smart RMU, 2-in/4-out RMU, gas-insulated RMU, RMU manufacturer, KITOZER |
| Meta Description | KITOZER is a professional manufacturer of 10kV outdoor Ring Main Units and high-voltage smart ring main switchgear. Featuring gas-insulated 3-position switches, 304 stainless steel enclosures with IP54 protection, microprocessor protection, and remote communication. Configuration is confirmed per project. |
| H1 Tag | 10kV Outdoor Smart Ring Main Unit Technical Design Solution |
| H2 Tags | Project Overview, User Requirements, Design Description, Equipment Configuration List, Product Technical Parameters, Solution Advantages, Technical FAQs, Construction Plan, After-Sales Service |
14.3 Internal Link Anchor Text Strategy
| Anchor Type | Anchor Text |
| — | — |
| Core Anchor Text | Outdoor RMU, 10kV ring main switchgear, high-voltage RMU |
| Long-Tail Anchor Text | Outdoor floor-standing RMU, gas-insulated 3-position RMU switchgear, smart distribution RMU |
| Related Anchor Text | Microprocessor-based protection device, zinc oxide surge arrester, outdoor distribution cabinet, distribution automation system |
—
16. Contact Information
| Item | Details |
| — | — |
| Company Name | Guangzhou Lain Intelligent System Development Co., Ltd. |
| Brand | KITOZER |
| Telephone | +86 13538869979 (WhatsApp & WeChat) / +86 13538869979 (WhatsApp & WeChat) |
| Official Website | https://gdlain.com |
| Company Address | Huashan Road 5, Shilou Town, Panyu District, Guangzhou, Guangdong, China |
For project inquiries, contact KITOZER. Configuration and support scope are confirmed on the quotation.