KITOZER KTR-2V500G Battery / 2V 500Ah Gel Battery

KITOZER KTR-2V500G Battery / 2V 500Ah Gel Battery

Brand: KITOZER Series: KTR-2V500G Category: Power Distribution / Battery bank

2V 500AhGel electrolyte15-year design lifeDeep cycleVRLA sealed

[Product image: ktr-2v500g-gel-battery.jpg]

1. Overview

UPS and DC bus systems rely on battery banks for backup during mains failure. Batteries are the last line of defense; their capacity and lifetime directly determine how long a data center survives an outage. 2 V cells are the mainstream for medium-to-large UPS and telecom power because they offer low voltage, high capacity and flexible series/parallel strings. Gel batteries, with gelled electrolyte, are leak-proof, low self-discharge and deep-cycle friendly, and are widely used in long-backup rooms.

The KITOZER KTR-2V500G is a 2 V 500 Ah VRLA gel battery. Positive plates are pasted, negative grids are lead-calcium alloy, and electrolyte is silica gel. Internal pressure is regulated by a valve-controlled safety vent. Float design life is 15 years at 25 C; deep-cycle count is >=1200 at 50% DOD; self-discharge <=3% per month. Cell size is about 240x170x230 mm and weight about 31 kg. Cells can be series-connected into 48 V or 220 V banks for UPS, DC panels and solar storage.

Selection confirms: cell voltage (2 V), capacity (500 Ah), backup time (minutes/hours), string redundancy (N+1), rack/cabinet size, and ambient temperature (ideal 20-25 C). For example, a 100 kVA UPS with 30-minute backup needs about 40 series-connected 2 V 500 Ah cells to form a 480 V bank. Install in a dedicated battery room or cabinet, well ventilated, away from direct sun; perform a capacity discharge test annually.

2. Key Features

Gel electrolyte

  • Silica gel, leak-proof.
  • Self-discharge <=3%/month.
  • >=1200 cycles at 50% DOD.
  • VRLA starved-electrolyte, mountable any way.

Long-life design

  • Lead-calcium grids, corrosion-resistant.
  • 15-year float life at 25 C.
  • Valve-regulated vent.
  • High vent pressure, explosion-safe.

Structure

  • Flame-retardant ABS case.
  • Copper terminals.
  • Size ~240x170x230 mm.
  • Stackable on racks.

3. Specifications

Item Specification
Nominal voltage 2 V
Rated capacity (C10) 500 Ah
Float design life 15 years at 25 C
Deep cycles >=1200 at 50% DOD
Self-discharge <=3% / month
Equalize voltage 2.30 to 2.35 V/cell
Float voltage 2.25 to 2.27 V/cell
Operating temp -15 to 50 C (best 20-25 C)
Dimensions ~240x170x230 mm
Weight ~31 kg

4. Reference Prices

KTR-2V500G 2V500Ah gel battery (each): USD 125~180 (ref. CNY 900~1300 at ~7.2)

Inter-cell connector (spare): USD 4~8 (ref. CNY 30~60 at ~7.2)

Battery cabinet (with terminals): USD 210~485 (ref. CNY 1500~3500 at ~7.2)

Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Medium/large UPS backup.
  • Telecom -48 V DC panels.
  • Data center VRLA banks.
  • Off-grid solar and storage.
  • Emergency lighting and fire power.

6. Installation & Maintenance

Installation

  • Keep battery room at 20-25 C.
  • Level and ground the rack.
  • Arrange cells by number with correct polarity.
  • Tighten connectors diagonally to torque.
  • Connect the main +/- to the UPS last.
  • Equalize charge for 24-48 h after install.

Maintenance

  • Measure cell voltage monthly.
  • Capacity discharge test annually.
  • Apply petroleum jelly on terminals yearly.
  • Life halves for every 10 C rise.
  • Dispose of dead batteries as hazardous waste.

7. FAQ

  • Q: Gel vs AGM?
    A: Gel has gelled electrolyte, better deep-cycle and lower self-discharge, slightly higher cost. AGM absorbs electrolyte in glass mat, better high-current discharge. Long backup favors gel; short high-current favors AGM.
  • Q: Why series of 40+ cells?
    A: UPS DC bus is 384 V or 480 V; with 2 V cells, you need many in series. 480 V needs about 240 cells.
  • Q: How long do they last?
    A: 15-year float design at 25 C; real rooms at 30+ C see 8-12 years; rely on capacity tests.
  • Q: Do new batteries need initial charge?
    A: Yes. Ships charged, but loses ~5% in transit; equalize 24-48 h before service.

8. Trend & Selection

Data center batteries are moving toward longer life, smart monitoring and lithium, but gel VRLA will remain mainstream for 5+ years thanks to maturity, low cost and recycling. Size capacity by load x time; keep under 25 C; add string redundancy; test annually.

9. Delivery & Service

KITOZER ships the KTR-2V500G charged, with test report, certificate and manual; bulk orders include racks and connectors.

10. Notes

A common mistake is a hot battery room. Life halves every 10 C, so air-conditioning or placing batteries near cold aisles matters.

Another pitfall is under-torqued connectors. Loose links overheat during high-current discharge and can melt; torque diagonally.

Selection summary: 2V500Ah; gel; 15-year float; 1200 deep cycles; 3%/month self-discharge. It is the core storage of UPS backup.

Systemically, one weak cell drags down the whole string; monthly cell-voltageInspection is essential.

Cost-wise, a 480 V bank costs about 100k CNY; a failure can drop the whole room, so selection and maintenance cannot be skimped.

From a battery-management standpoint, add a BMS cell-monitoring module to track per-cell voltage and temperature in real time, alerting on weak cells before they drag down the string. The BMS connects to the DCIM over RS485.