Table of Contents
ToggleKITOZER KTR-SP36 3-Phase Power SPD (380V Surge Protector)
Brand: KITOZER Series: KTR-SP36 Category: Lightning Protection / Power SPD
3-phase 380VClass T220kADIN railKTR-SP36
1. Overview
The KITOZER KTR-SP36 is a 3-phase 380V AC surge protective device (SPD) for protecting distribution panels, UPS inputs, AC units and sub-boards against lightning surges and switching over-voltages. The SPD is wired in parallel between phase and ground. It is high-impedance under normal operation; when a surge (microsecond high-voltage pulse) appears, the internal clamping elements (GDT/MOV) conduct in nanoseconds, clamping the voltage to a safe level and diverting current to ground.
KTR-SP36 is a Class TSP (Type 2 test) SPD with nominal discharge current In=20 kA (8/20 μs) and maximum Imax=40 kA. It has a 3-phase 5-wire (L1/L2/L3/N/PE) modular structure — failed modules can be replaced without powering off. The front panel has a status window (green OK / red fault) and a remote-signaling dry contact for EMCS integration.
Typical uses: room distribution panel input (second-stage SPD), UPS front-end, precision AC supply, outdoor equipment boxes. It works with the building’s first-stage SPD to form a multi-level protection system.
2. Key Features
3-phase 5-wire
- L1/L2/L3/N/PE full protection.
- 380V/220V system.
- Uc=385V.
- GDT between N-PE.
Class T2
- In=20 kA (8/20 μs).
- Imax=40 kA.
- Up≤1.5 kV.
- Response ≤25 ns.
Modular
- Plug-in modules.
- Hot-swap failed module.
- Status window.
- Remote-signal dry contact.
DIN rail
- 35 mm DIN rail.
- 36 mm/pole width.
- Torque 2.5 N·m.
- UL94 V-0 housing.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-SP36 |
| SPD class | T2 (Type 2 test) |
| System voltage | AC380V (3-phase 5-wire) |
| Max continuous Uc | 385V |
| Nominal In (8/20 μs) | 20 kA |
| Max Imax | 40 kA |
| Voltage protection Up | ≤1.5 kV |
| Response time | ≤25 ns |
| Remote signal | dry contact (max 250V/0.5A) |
| Mounting | 35 mm DIN rail |
| Ingress | IP20 (cabinet) |
| Operating temp | -40~85℃ |
4. Reference Prices
KTR-SP36 3-phase T2 SPD (20 kA, remote signal):Ref. USD 35~69 / unit (CNY 250~500 @7.2)
KTR-SP36 replacement module (spare):Ref. USD 11~21 / pole (CNY 80~150 @7.2)
KTR-SP36 single-phase T2 SPD (economy):Ref. USD 8~17 / unit (CNY 60~120 @7.2)
Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room distribution panel second-stage protection.
- UPS front-end surge protection.
- Precision AC power input.
- Outdoor equipment distribution boxes.
- Camera power distribution.
6. Installation & Maintenance
Installation
- Mount SPD on DIN rail in panel.
- Wire L1/L2/L3/N to incoming phase/neutral.
- Connect PE to ground bar.
- Install upstream backup breaker (NC type).
- Wire remote-signal dry contact to EMCS DI module.
- Keep ground lead short & thick (≤0.5 m, 16 mm²).
- Verify status window green.
- Power up and test remote alarm.
Maintenance
- Check status window quarterly.
- Test SPD degradation before thunder season.
- Replace module immediately when red.
- Inspect ground connections.
- Test remote alarm function.
- Check surge event logs after storms.
7. FAQ
- Q:SPD status window red — what does it mean?
A:Red means the internal MOV/GDT has degraded or failed — it no longer provides surge protection. Replace the module immediately. Do not wait for the next strike; a failed SPD is useless. The modular design allows hot-swap of that pole without affecting others. - Q:Why a backup breaker upstream of SPD?
A:A failed SPD may short-circuit; without a backup breaker, the panel trips or catches fire. An NC-type SPD-specific backup breaker reliably disconnects when the SPD shorts, without affecting normal supply. - Q:How do Type 1 and Type 2 SPDs coordinate?
A:Type 1 (building input, T1) diverts large current (Imax≥100 kA) with higher protection level; Type 2 (room panel, T2) further clamps to equipment-safe levels. Energy coordination between them requires decoupling — usually ≥10 m of cable or a decoupling inductor. - Q:Does SPD protect against induced lightning?
A:Yes. Induced lightning enters via power/signal lines; the parallel SPD diverts induced surge current. But direct strikes (hitting the building) require air terminals (lightning rods) and down conductors — SPD only protects line surges, not direct-strike protection.
8. Trend & Selection
Power SPDs are trending toward smart monitoring (leakage current, strike count, remote upload), integrated T1+T2, and combined SPD+backup breaker units. Data centers increasingly require remote SPD status monitoring, driving RS485-communicating SPD adoption.
9. Delivery & Service
KITOZER sizes KTR-SP36 by panel circuit count and system voltage, providing SPD mounting drawings and backup-breaker selection tables. Delivery includes SPD body, spare failed module, DIN rail, terminals and certificate. Warranty covers status-test guidance.
10. Additional Notes
A common pitfall is a long, thin ground lead. The SPD ground lead is the surge discharge path — over 0.5 m or below 16 mm² raises impedance and clamping voltage, still risking equipment damage. The ground lead must be short, thick and straight.
Another pitfall is omitting the N-PE GDT. In 3-phase systems, potential surges also appear between N and PE; a discharge tube must be installed there. KTR-SP36 has a built-in N-PE GDT — wire N and PE to the correct terminals.
Also coordinate SPD voltage with the system: in a TN system, N is grounded at the transformer, and the SPD Uc should match the line-to-neutral voltage. Mismatching Uc causes premature SPD failure or insufficient protection. Verify Uc=385V for a 380/220V 3-phase system.
Selection summary: T2 20 kA; 3-phase 380V; modular replaceable; remote alarm; DIN rail. The SPD is the power line’s safety valve — right location, proper ground, periodic status check, protects equipment through lightning.
Contact Us
KITOZER brand (professional data center & low-voltage equipment supplier)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com