KITOZER KTR-BT150 12V150Ah Gel Battery (UPS Energy Storage)

KITOZER KTR-BT150 12V150Ah Gel Battery (UPS Energy Storage)

Brand: KITOZER Series: KTR-BT150 Category: Energy Storage / Battery

12V150AhGeldeep cycleUPS backupKTR-BT150

1. Overview

The KITOZER KTR-BT150 is a 12V 150 Ah gel (GEL) valve-regulated lead-acid battery, designed for UPS, telecom base stations, solar storage and emergency lighting. Compared with standard lead-acid, gel batteries have gelled electrolyte (silica thickened), no free acid, no leakage, good thermal stability, and long deep-cycle life (up to 600 cycles @50% DoD) — ideal for long float charge and frequent discharge storage.

KTR-BT150 is rated 12V, 150 Ah (C20), weighing ~45 kg. Terminals are M8 copper bolt posts for series/parallel. Internally it uses AGM separators with gelled electrolyte; oxygen recombination efficiency ≥98%, no acid mist under normal use. Self-discharge is low (≤3%/month @25℃), allowing 6-month storage without recharge. Design life: 12 years float (25℃), 600~1500 deep cycles.

Typical uses: room UPS battery strings (multi-series to 48V/240V/384V), telecom backup, off-grid PV storage, EPS emergency power, railway signaling. Strings are series-connected to match the UPS DC bus (e.g., 12V×20=240V).

2. Key Features

Gel electrolyte

  • SiO₂ thickened gel.
  • No free acid / no leak.
  • Good thermal stability.
  • 600~1500 deep cycles.

VRLA sealed

  • AGM separator.
  • O₂ recombination ≥98%.
  • No acid mist.
  • Safety relief valve.

Long life

  • 12-year float @25℃.
  • Self-discharge ≤3%/month.
  • 6-month storage.
  • Low-antimony grid.

Terminal & build

  • M8 copper bolt terminals.
  • Flame-retardant ABS case.
  • Can lie on side.
  • Explosion-proof vent plug.

3. Specifications

Item Parameter
Model KTR-BT150
Nominal voltage 12V
Rated capacity (C20) 150 Ah
Weight ~45 kg
Dimensions ~485×170×240 mm (incl. terminals)
Terminal M8 copper bolt
Grid alloy low-Sb Pb-Ca
Self-discharge ≤3%/month (25℃)
Float voltage 13.5~13.8V (25℃)
Equalize voltage 14.4~14.9V (25℃)
Design life 12 yr float / 600~1500 cycles
Operating temp -20~50℃ discharge / 0~40℃ charge

4. Reference Prices

KTR-BT150 12V150 Ah gel battery:Ref. USD 125~208 / unit (CNY 900~1500 @7.2)

KTR-BT150 12V150 Ah (rack + cables kit):Ref. USD 167~250 / unit (CNY 1200~1800 @7.2)

KTR-BT150 old battery recycling credit:Ref. USD 14~28 / unit (per lead price)

Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Room UPS battery string.
  • Telecom base station backup.
  • Off-grid PV storage.
  • EPS emergency lighting.
  • Railway / metro signaling backup.

6. Installation & Maintenance

Installation

  • Install batteries in dedicated cabinet/rack.
  • Determine series count by UPS DC voltage.
  • Connect between cells with copper bars/cables.
  • Torque terminals per manual (typically 8~10 N·m).
  • Finally connect UPS DC bus +/-.
  • Measure string voltage (e.g., 240V).
  • Connect string to float charger.
  • Charge 24~48 h before loading.

Maintenance

  • Measure per-cell float voltage quarterly.
  • Annual capacity discharge test.
  • Inspect terminals for corrosion (apply Vaseline).
  • Keep battery room 20~25℃.
  • Record per-cell internal resistance.
  • Replace failed cells promptly (same model/batch).

7. FAQ

  • Q:Gel vs AGM — choose?
    A:AGM (starved electrolyte) suits high-frequency shallow cycles (UPS), lower cost; gel suits deep cycles and wide temps (PV/solar), longer life but pricier. Room UPS usually AGM suffices, but high-temp rooms (>30℃) recommend gel.
  • Q:How long do batteries last?
    A:Design float life 12 years at 25℃, but actual life depends on temp and depth of discharge. Every 10℃ rise halves life; frequent deep discharge (>50% DoD) also shortens it. Room UPS batteries are typically replaced every 5~8 years.
  • Q:Can I mix old and new batteries?
    A:No. Old and new cells differ in internal resistance and capacity; in series, the old cell over-charges and over-discharges, accelerating failure. Replace the whole string with same model/batch — mixed strings shorten overall life.
  • Q:Battery bulging — what to do?
    A:Bulging means internal gas over-pressure, likely over-charge or high temp. Stop use immediately, disconnect, ventilate. Bulged batteries cannot be reused — replace them. Check float voltage (>13.8V indicates over-charge).

8. Trend & Selection

Batteries are shifting toward lithium (LFP) replacement — higher energy density, longer cycle life (>6000), smaller size, but higher cost. VRLA gel remains widely used for cost-effectiveness and safety (no thermal runaway). Hybrid strings (lead+Li) and smart BMS are trends.

9. Delivery & Service

KITOZER sizes KTR-BT150 strings by UPS power and backup time, providing string-count calculation and rack dimension advice. Delivery includes batteries (per qty), connecting copper bars, insulation sleeves, certificate and install manual. Warranty covers first discharge test guidance.

10. Additional Notes

A common pitfall is uncontrolled battery-room temperature. Temperature is the #1 factor in battery life — above 25℃, every 10℃ rise halves life. The battery room must have AC, kept at 20~25℃.

Another pitfall is omitting Vaseline on terminals. Copper terminals oxidize in humid air, increasing contact resistance and causing over-charge. Apply Vaseline or conductive grease after installation.

Also size the string for the actual backup time, not the UPS rated kVA. A 20 kVA UPS with 10-min backup needs a different string than one with 30-min backup. Calculate required Ah from load watts × backup hours / battery voltage, plus a 20% margin.

Selection summary: 12V150 Ah gel; 12-yr float; M8 terminals; 600+ deep cycles; low self-discharge. The battery is the UPS’s energy warehouse — right capacity, controlled temp, periodic voltage checks, holds through outages.