1. Overview

The KITOZER KTR-BTAGM100 is a 12 V 100 Ah AGM valve-regulated sealed lead-acid battery using Absorbent Glass Mat separators; electrolyte is absorbed in the mat with no free acid, allowing placement in any orientation except inverted. The valve-regulated sealed structure emits no acid mist in normal use and is maintenance-free with no water topping-up. Floating design life 10 years at 25 C, suitable for UPS, DC panels, telecom sites and security systems as backup power.

KTR-BTAGM100 rated voltage 12 V, rated capacity 100 Ah at 20-hour rate, end voltage 10.5 V. Float charge 13.5 to 13.8 V at 25 C, equalize charge 14.4 to 14.8 V. Self-discharge below 3 percent per month at 25 C. Dimensions about 330 long by 171 wide by 215 high mm (220 mm including terminals), weight about 30 kg. M8 bolt terminals. Operating temperature -15 to 50 C, recommended 25 C.

Typical uses: UPS backup battery strings; DC panel operating power; telecom site backup; security system backup; solar energy storage. 12 V batteries can be series-connected into 24, 48 or 192 V strings (e.g., 16 in series for 192 V). AGM vs gel: AGM has high power density for short high-current UPS discharge; gel has better deep-cycle for long solar discharge.

2. Key Features

AGM VRLA

  • Absorbent glass mat separator.
  • No free acid.
  • Valve-regulated sealed.
  • Maintenance-free no topping.

Performance

  • 12 V 100 Ah at 20-hour rate.
  • 10-year float life at 25 C.
  • Self-discharge below 3 percent per month.
  • -15 to 50 C operating.

Charging

  • Float 13.5 to 13.8 V.
  • Equalize 14.4 to 14.8 V.
  • End voltage 10.5 V.
  • M8 bolt terminals.

Safety

  • Pressure relief valve.
  • Flame-retardant ABS case.
  • Leak-proof design.
  • Horizontal mountable.

3. Specifications

Item Parameter
Model KTR-BTAGM100
Rated voltage 12V
Rated capacity 100Ah(20SmallHour Rate)
End voltage 10.5V
Float voltage 13.5~13.8V(25℃)
Equalize voltage 14.4~14.8V(25℃)
Self-discharge <3%/Month(25℃)
Float design life 10Year(25℃)
Operating temp -15~50℃
Housing material ABSFlame Retardant
Terminal M8Bolt
Dimensions Approx.330×171×215mm
Height incl. terminal Approx.220mm
Weight Approx.30kg

4. Reference Prices

KTR-BTAGM100 12V100Ah AGM battery:Ref. USD 83~125 / pc (CNY 600~900 at 7.2)

Battery cable 50 mm2, 30 cm:Ref. USD 4~7 / pc (CNY 30~50 at 7.2)

Battery rack 19 inch 4-tier comparison:Ref. USD 42~69 / rack (CNY 300~500 at 7.2)

Battery monitoring module comparison:Ref. USD 28~56 / pc (CNY 200~400 at 7.2)

Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • UPS backup power.
  • DC panel operating power.
  • Telecom site backup.
  • Security system backup.
  • Solar energy storage.

6. Installation & Maintenance

Installation

  • Level battery rack on floor.
  • Place batteries on rack per design.
  • Series-connect batteries with 50 mm2 cables.
  • Torque M8 terminals to 12 N·m.
  • Connect main positive and negative to UPS or DC panel.
  • Check polarity plus to minus.
  • Apply petroleum jelly to terminals.
  • Initial charge at equalize voltage.

Maintenance

  • Measure terminal voltage monthly.
  • Check terminal torque and oxidation quarterly.
  • Perform verification discharge half-yearly.
  • Record battery temperature (recommended 25 C).
  • Adjust float voltage if deviation above 0.05 V.
  • Replace failed batteries with capacity below 80 percent.

7. FAQ

  • Q:AGM vs gel battery?
    A:AGM electrolyte is absorbed in glass mat, with high power density and strong high-current discharge (ideal for UPS surge), lower price, but fewer deep cycles about 300 at 80 percent DOD. Gel electrolyte is jelly-like, longer deep-cycle life about 600 at 80 percent DOD, wide temperature tolerance, but weaker high-current and higher price. UPS uses AGM; solar long discharge may prefer gel.
  • Q:How long does a 12V100Ah battery last?
    A:Backup time depends on load power. Formula: hours = capacity times voltage times efficiency divided by load power. Example: 100 Ah times 12 V times 0.8 divided by 1000 W equals about 0.96 hours or 58 minutes. At 50 percent UPS load, about 1.5 hours. Parallel strings extend runtime.
  • Q:How many batteries in series?
    A:By UPS or DC panel DC bus voltage. Common UPS DC bus 192 V (16 x 12 V in series), 240 V (20 pcs), 48 V (4 pcs). Series total voltage = single voltage times count. Series does not add capacity, only voltage. Parallel adds capacity (same voltage, Ah sums).
  • Q:What causes battery case bulging?
    A:Common causes: overcharge (float voltage too high, gassing pressure), high ambient temperature above 30 C accelerating aging, internal short. Bulged batteries must be replaced immediately (leak and rupture risk). Verify float voltage 13.5 to 13.8 V after install; keep room around 25 C with AC in summer.

8. Trend & Selection

Lead-acid batteries trend toward long life (15-year float), high power (improved AGM) and smart monitoring (cell voltage and temperature). Meanwhile LiFePO4 lithium is gradually replacing lead-acid in UPS and storage for smaller size and longer life (10 plus years). AGM lead-acid remains mainstream short-to-medium term for low cost and proven reliability.

9. Delivery & Service

KITOZER sizes KTR-BTAGM100 by UPS DC bus voltage and backup time, providing string series diagram and capacity calculation. Delivery includes battery, connecting bars and certificate. Warranty covers monitoring and replacement guidance.

10. Additional Notes

A common pitfall is mixing old and new batteries. Old batteries have high internal resistance, dragging down the whole string; new cells are compromised by old ones, and string capacity depends on the weakest cell. Replace the whole string at once with same-batch same-model cells. In emergencies, mixing is only a short-term transition; mark old cells for priority retirement.

Another pitfall is no petroleum jelly on terminals. M8 bolt terminals exposed to room air oxidize, increasing contact resistance and heating under high current. After install, coat terminals with a layer of petroleum jelly or conductive grease to seal air. Inspect yearly; brush blackened terminals with a wire brush and re-coat.

Selection summary: 12 V 100 Ah, AGM VRLA, float 13.5 to 13.8 V, M8 terminals, 10-year life. The AGM battery is the UPS energy warehouse; correct series connection, accurate float voltage, and 25 C temperature keep backup time on target.

Additional tip: when installing the battery string, leave 5 mm gaps between adjacent cells for heat dissipation; do not pack them tightly. Rack layers should be well ventilated and away from heat sources such as AC vents and distribution boxes. Perform a verification discharge 3 months after commissioning, record the capacity baseline, and repeat annually.