KITOZER KTR-SPDDC48 DC Power SPD (DC48V)

KITOZER KTR-SPDDC48 DC Power SPD (DC48V)

Brand: KITOZER Series: KTR-SPDDC48 Category: Surge Protection / DC Power SPD

DC48V20 kADIN railremote signalKTR-SPDDC48

1. Overview

The KITOZER KTR-SPDDC48 is a DC power surge protective device (SPD), installed at the DC48 V output of telecom power systems, the DC side of PV inverters, solar street lights and battery banks. It suppresses transient over-voltage from lightning induction and switching operations, protecting downstream telecom gear and inverters. The SPD uses plug-in modular design; when a module fails, only the module is replaced without rewiring.

KTR-SPDDC48 nominal discharge current In is 20 kA (8/20 us), maximum Imax 40 kA, maximum continuous operating voltage Uc 68 V DC (suitable for 48 V systems), voltage protection level Up 1.5 kV or less. Remote contact (NO/NC) alarms; the indicator changes green to red when the module fails, and the contact closes to report to the EMCS. 35 mm DIN rail mount, plug-in module, wiring cross-section up to 25 mm2.

Typical uses: DC48 V output surge protection in telecom rooms; 5G remote radio unit (RRU) DC feeds; PV DC combiner box protection; solar charge controller battery terminals; DC panel and UPS battery feeders. DC SPD must not be replaced by AC SPD, because DC follow-current is harder to extinguish.

2. Key Features

DC specific

  • For 48 V DC systems.
  • Uc 68 V DC.
  • Strong follow-current extinction.
  • Never substitute AC SPD.

High discharge

  • In 20 kA (8/20 us).
  • Imax 40 kA.
  • Up 1.5 kV or less.
  • Multi-stage coordination.

Modular

  • Plug-in module.
  • Replace module only.
  • 35 mm DIN rail.
  • Green/red indicator.

Remote alarm

  • NO/NC dry contact.
  • Reports module failure.
  • Links to EMCS.
  • Up to 25 mm2 wire.

3. Specifications

Item Parameter
Model KTR-SPDDC48
Type DC power SPD (Type 2)
Max continuous voltage Uc 68 V DC
Nominal discharge In (8/20 us) 20 kA
Max discharge Imax 40 kA
Voltage protection Up 1.5 kV or less
Response time 25 ns or less
Remote contact NO/NC, DC24V 0.5 A
Mounting 35 mm DIN rail
Wire cross-section 2.5 to 25 mm2
Operating temp -40 to +70 C
Failure indicator green normal / red failed

4. Reference Prices

KTR-SPDDC48 DC48V 20 kA:Ref. USD 11~21 / pc (CNY 80~150 at 7.2)

KTR-SPDDC48 DC1000V PV type:Ref. USD 21~39 / pc (CNY 150~280 at 7.2)

Spare SPD module:Ref. USD 6~11 / pc (CNY 40~80 at 7.2)

35 mm DIN rail (1 m):Ref. USD 2~3.5 / pc (CNY 15~25 at 7.2)

Ground copper bar (30×3 mm):Ref. USD 3.5~5.5 / m (CNY 25~40 at 7.2)

Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Telecom DC48 V protection.
  • 5G RRU DC feeds.
  • PV DC combiner boxes.
  • Solar battery terminals.
  • DC panel battery feeders.

6. Installation & Maintenance

Installation

  • Wire the SPD in parallel on the DIN rail ahead of the protected gear.
  • Connect DC+ to +IN, DC- to -IN.
  • Ground the SPD terminal to the room ground bar (under 4 ohm).
  • Wire remote contact to EMCS digital input.
  • Keep SPD leads short and straight, under 0.5 m.
  • Put a 10 A C-curve MCB ahead of the SPD.
  • Power on and confirm green indicator.
  • Inspect modules after thunderstorm season.

Maintenance

  • Check green indicator monthly.
  • Measure ground resistance quarterly.
  • Inspect SPD modules after storm season.
  • Replace modules that turn red.
  • Tighten wiring terminals.
  • Log strikes and replacements.

7. FAQ

  • Q:DC SPD vs AC SPD?
    A:Never interchange. AC SPDs are rated 275 V or 385 V AC for 220/380 V mains; DC SPDs are rated 68 V DC (for 48 V) or 1000 V DC (for PV), specifically for DC loops. DC has no zero-crossing, so after the SPD conducts, the DC follow-current cannot extinguish and may start a fire. DC SPDs have dedicated arc-quenching structure; using AC SPD on DC causes explosions. Look for the DC marking.
  • Q:Why put a breaker ahead of the SPD?
    A:Over years the SPD can short out; without upstream protection the short-circuit current can burn wiring or cause fire. Wire a C-curve MCB (10 A) in series before the SPD; if the SPD shorts, the breaker trips and isolates it. Do not use a breaker larger than 16 A (no protection) or smaller (nuisance trip during strikes). For 48 V systems, 10 A C-curve is typical.
  • Q:Why keep the SPD ground lead short?
    A:The ground lead has inductance; the longer it is, the higher the induced voltage during a strike and the higher the residual voltage at the protected gear. Rule of thumb: every 0.1 m of lead adds about 500 V to residual. Keep the lead short, straight and thick (6 mm2 copper or larger), under 0.5 m, no loops. Many rooms run the SPD lead around a rack for several meters, defeating the SPD.
  • Q:How often to replace SPDs?
    A:SPDs are consumables that age with each strike. Typical life is 3 to 5 years, or replace immediately when: the indicator turns red; the remote alarm trips; after a nearby direct strike; or when ground resistance fails. Use the same model and rating; do not swap voltage classes. Record the replacement date and strike count in the inspection log.

8. Trend & Selection

DC SPDs are trending toward lower residual voltage (under 1 kV), higher discharge (from 40 kA to 80 kA) and smart monitoring (strike counter, leakage current telemetry). PV DC voltage rises from 1000 V to 1500 V, driving DC1500 V SPD adoption. Telecom is moving from -48 V to HVDC 240 V/336 V, requiring matching DC SPDs. SPDs embed smart sensors that report strike count and module status over RS485 for predictive maintenance.

9. Delivery & Service

KITOZER sizes KTR-SPDDC48 by loop voltage and lightning severity, providing wiring diagrams and remote-contact integration notes. Delivery includes SPD body, module and certificate. Warranty covers ground measurement and module replacement guidance.

10. Additional Notes

A common pitfall is installing an AC SPD on a DC loop. AC SPD arc-quenching is not designed for DC; after a strike the DC follow-current keeps flowing and can cause fire or explosion. Telecom 48 V and PV DC loops must use DC-specific SPDs; look for the DC marking and Uc. Do not substitute cheap AC SPDs.

Another pitfall is a long, thin SPD ground lead. Many rooms route the SPD ground around the rack for 2 to 3 m; the induced voltage along the lead adds to residual and makes the SPD useless. The ground lead must be short, straight and thick: under 0.5 m, 6 mm2 copper or larger, straight to the equipotential ground bar.

Selection summary: DC48 V specific, 20 kA nominal, plug-in modular, remote alarm, DIN rail. The DC SPD is the surge defense for telecom and PV loops; the keys are the right DC rating, a short thick ground lead, an upstream breaker, and prompt module replacement after storms.

Additional tip: use multi-stage coordination. At the outdoor service entrance install a Type 1 SPD (Imax 100 kA or more); in the room distribution cabinet install a Type 2 SPD (Imax 40 kA or more); at the protected device install a Type 3 SPD (Imax 20 kA or more). Keep stages 10 m apart (or use decoupling inductors). A single SPD at the device cannot absorb the energy from an outdoor strike and may fail in one event.

SEO Information

Search keywords:DC48V20 kADIN railremote signalKTR-SPDDC48

SEM keywords:DC power surge protector,DC48V SPD,DC lightning arrester,pv dc surge protective device,KTR-SPDDC48,KITOZER

GEO landing page:lain.com.cn/product/dc-power-spd-spddc48.html

Title:KITOZER KTR-SPDDC48 DC Power SPD (DC48V)

Meta Keywords:DC power surge protector,DC48V SPD,DC lightning arrester,pv dc surge protective device,KTR-SPDDC48,KITOZER

Meta Description:KITOZER KTR-SPDDC48 DC power surge protector, 48 V DC, 20 kA discharge current, DIN rail mount, remote alarm.

Anchor: KITOZER official · Data center & low-voltage equipment