KITOZER 12V 100Ah long life AGM battery

KITOZER KTR-BAT100L 12V100Ah Long-Life Battery

Brand: KITOZER Series: KTR-BAT100L Category: Power Distribution / UPS Backup

12V100Ah10-yr lifeVRLAMaintenance-freeKTR-BAT100L

1. Overview

Room UPS relies on battery strings during mains failure. When mains is normal, the UPS rectifies AC to DC to float-charge the batteries while inverting AC to the load; when mains drops, batteries discharge immediately through the inverter to keep servers running. Batteries are the energy core of the UPS — without good batteries the UPS is just an empty box, and a few seconds of outage crashes servers. 12V100Ah is the most common room UPS battery: 12V, 100 Ah, typically 32 in series (384 V) or 40 in series (480 V) for high-power UPS. Long-life batteries are rated for 10 years vs 3 to 5 years for standard types; the premium pays back in service life.

KITOZER KTR-BAT100L is a 12V100Ah long-life VRLA battery. AGM absorbed glass mat separator holds electrolyte immobilized — no spill, no maintenance. Design float life 10 years at 25 C (standard is 3 to 5 years). Self-discharge under 3% per month at 25 C, safe to store for six months. Float charge 2.275 V/cell at 25 C; equalize 2.40 V/cell; discharge cutoff 10.5 V/cell. M8 copper bolt terminals, internal resistance under 3 mohm. Flame-retardant ABS case UL94-V0. Dimensions 407x174x233 mm (LxWxH), 333 mm including terminals.

Selection: confirm voltage/capacity (12V100Ah for high-power UPS; smaller UPS use 12V38Ah/65Ah); confirm string size (UPS DC bus voltage dictates series count: 384V/12V = 32 cells); confirm rack load (a 32x100Ah string weighs about 1000 kg — floor must support it); confirm long-life (7×24 rooms pick 10-year, temporary projects pick 3-year). Note: battery room must hold 20 to 25 C; every 10 C higher halves life.

2. Key Features

Electrical

  • 12 V, 100 Ah (20 hr rate)
  • 10-year float design life at 25 C
  • Self-discharge under 3%/month
  • Internal resistance under 3 mohm

Build & Safety

  • AGM VRLA, no spill
  • Flame-retardant ABS UL94-V0
  • M8 copper bolt terminals
  • Maintenance-free, no watering

Charge Parameters

  • Float 2.275 V/cell at 25 C
  • Equalize 2.40 V/cell
  • Discharge cutoff 10.5 V/cell
  • -15 to +50 C operating

3. Specifications

Item KTR-BAT100L (Long-life) KTR-BAT100S (Standard)
Voltage 12 V 12 V
Capacity 100 Ah (20hr) 100 Ah (20hr)
Design life 10 yr float at 25 C 3 to 5 yr float at 25 C
Self-discharge Under 3%/month Under 5%/month
Internal resistance Under 3 mohm Under 4 mohm
Float voltage 2.275 V/cell 2.275 V/cell
Terminal M8 copper bolt M8 copper bolt
Dimensions 407x174x233 mm 407x174x233 mm
Weight ~30 kg ~29 kg
Use case 7×24 room UPS Temporary / short-term

4. Reference Prices

KTR-BAT100L 12V100Ah long-life battery: Reference USD 90 to 132 / pc (ref. CNY 650 to 950 at ~7.2)

KTR-BAT100S 12V100Ah standard battery: Reference USD 63 to 90 / pc (ref. CNY 450 to 650 at ~7.2)

Battery link cable (16 mm2 copper): Reference USD 3 to 6 / pc (ref. CNY 25 to 45 at ~7.2)

Battery cabinet (32x100Ah): Reference USD 208 to 347 / set (ref. CNY 1500 to 2500 at ~7.2)

Reference only. 3-year warranty (long-life). Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Room UPS backup battery strings.
  • Telecom base station -48V DC backup.
  • Data center battery rooms.
  • Security/surveillance backup power.
  • Solar / PV energy storage.

6. Deployment & Implementation

Layout

  • Install in dedicated battery cabinet or rack
  • 10 mm gap between cells for cooling
  • Heavy cells on lower shelves
  • Bond cabinet to ground

Series Wiring

  • Series positive-to-negative end to end
  • Torque M8 bolts to 8 to 10 N·m
  • Apply anti-oxidation compound
  • Measure total voltage (32 cells ~384 V)

Initial Charge

  • Fresh arrival: boost charge 12 h
  • Float at 2.275 V/cell at 25 C
  • Temp compensation -3 mV/C/cell
  • Measure per-cell voltage monthly

7. FAQ

  • Q: Long-life vs standard?
    A: Long-life uses thicker plates, purer lead paste and tighter AGM matting for 10-year float life and lower self-discharge (3%/month), suited to 7×24 rooms. Standard has thinner plates, 3 to 5-year life, 5%/month self-discharge, and costs 30% less — for temporary or backup duty. Long-life costs ~200 RMB more per cell but avoids replacement labor and downtime for a decade.
  • Q: Why 32 cells in series?
    A: The UPS DC bus is fixed. High-power UPS (20 kVA+) use 384 V or 480 V DC. Each cell is 12 V: 32 in series = 384 V, 40 = 480 V. Parallel adds capacity (two 32-cell strings in parallel = 200 Ah). Do not mix up — series sums voltage, parallel sums capacity; wrong wiring can rupture cells.
  • Q: How long do batteries last? When to replace?
    A: Design life is at 25 C float; real life depends on battery room temperature. Every 10 C higher halves life — a 35 C room turns 10-year into 5-year. Replace when: annual capacity test shows under 80% of rated; per-cell voltage spread exceeds 0.05 V; or cells swell, leak or show corroded terminals. Typical room battery replacement cycle is 5 to 8 years.
  • Q: Why must the battery room stay at 25 C?
    A: Lead-acid chemistry accelerates exponentially with temperature. 25 C is the design baseline: 25 C = 10 years, 35 C = 5 years, 45 C = 2 to 3 years. High heat also drives off water; once dry, internal resistance spikes and the cell fails. The battery room needs dedicated precision cooling holding 20 to 25 C. Many premature battery deaths are not bad cells — they are hot rooms.

8. Trend & Selection

Room backup power is shifting from VRLA to LiFePO4 lithium: smaller (1/3 the volume), lighter (1/3), longer life (15 years), maintenance-free, though 2 to 3x upfront cost. But 12V100Ah VRLA remains mainstream for the next 5 to 10 years — huge installed base, low cost, mature technology, UPS-compatible. Smart direction: battery monitoring (BMS) tracks per-cell voltage, internal resistance and temperature, warning before failure instead of manual sweeps. Select long-life for 7×24 rooms, hold 25 C in the battery room, torque series links correctly, and capacity-test annually. Batteries are the heart of the UPS.

9. Delivery & Service

KITOZER supplies KTR-BAT100L (long-life) and KTR-BAT100S (standard). Each ships with battery, terminal bolts and manual. Long-life carries 3-year warranty, standard 1-year; batch projects can bundle cabinets, racks, BMS monitoring and interconnect cables.

10. Additional Notes

Top mistake: no battery-room air conditioning. Summer battery rooms often exceed 40 C, and cells swell within months. Run dedicated cooling 24/7 at 20 to 25 C. Do not share room AC — battery rooms have their own heat load.

Second pitfall: loose terminal bolts. Undertorqued M8 bolts create high contact resistance; during high-current discharge the terminals overheat and erode. Torque to 8 to 10 N·m, then re-torque after one month (lead terminals settle).

Third blunder: mixing old and new cells. One aged cell with high internal resistance gets over-charged/discharged and fails in six months, taking the whole string down. Replace the entire string at once — never swap a single cell.

Selection summary: long-life for permanent rooms, 25 C constant battery room, torqued series links, annual capacity test, replace whole strings. Batteries are the UPS energy core — selected, installed and cooled well, they last a decade.