KITOZER 12V 100Ah standard battery

KITOZER KTR-BAT100 12V100Ah VRLA Sealed Lead-Acid Battery

Brand: KITOZER Series: KTR-BAT100 Category: Power Distribution / UPS Battery

12V100AhVRLA sealed10-yr lifeDeep cycleKTR-BAT100

1. Overview

The 12V100Ah VRLA (Valve-Regulated Lead-Acid) battery is the most common energy-storage cell in UPS, EPS and DC panels. The UPS unit itself does not store power; the battery bank inverts 220 V AC from the DC bus during mains failure (typically 15-30 minutes at full load, enough to start the generator or shut down gracefully). VRLA features: valve-regulated sealed (no leaks or acid mist in normal use, can sit in the room without a dedicated battery room), maintenance-free (no watering), 12 V units series-wired into a DC bus (e.g. a 384 V DC bus means 32 x 12 V in series). Design life is 5-10 years, but temperature cuts it sharply (every 10 C rise halves life), so room AC holding the battery area at 25 C is the key to longevity.

KITOZER KTR-BAT100 is a 12V100Ah VRLA battery. Positive: pasted-plate lead-calcium grid (low gassing); negative: sponge lead; electrolyte absorbed in an AGM glass-mat separator (starved electrolyte); valve-regulated safety vent (releases at 2-3 psi, sealed otherwise). Nominal 12 V (six 2 V cells); 100 Ah (20-hour rate – 5 A to 10.5 V over 20 h); float 13.5-13.8 V (2.25-2.30 V/cell); equalize 14.4-14.7 V; size about 330 x 170 x 215 mm incl. terminals; weight about 30 kg. Models: KTR-BAT100 standard (5-8 yr design life, general UPS); KTR-BAT100L long-life (thicker plates, lower calcium gassing, 10-12 yr, for unattended rooms); KTR-BAT100G gel (electrolyte as gel, non-flowing, deep-cycle, wide temp -30 to +50 C, for outdoor/hot/cold sites); KTR-BAT65 is a 12V65Ah smaller unit (small UPS, fire backup).

Selection: capacity (100 Ah is mainstream, but size by backup time – 384 V DC bus, 10 kVA UPS, 30 min backup needs about two 100 Ah banks in series; bigger is not always better – rack space and weight matter); life (standard for ordinary projects; long-life for unattended sites where replacement is hard); environment (25 C room -> AGM standard; wide temperature/outdoor -> gel); series count (DC bus / 12 V – 384 V = 32 units, neither more nor less); temperature (battery area must hold 20-25 C; every 10 C rise halves life). Note: do not parallel multiple banks (different internal resistance and age cause current imbalance); coat terminals with Vaseline against oxidation; torque series connections to spec (typically 9-11 Nm); equalize for 12-24 h before first use.

2. Key Features

Electrical

  • 12V100Ah
  • AGM starved
  • Low self-discharge <=3%/mo
  • Deep cycle

Structure

  • Safety vent
  • Pb-Ca grid
  • ABS case
  • Sealed, no leak

Life

  • Std 5-8 yr
  • Long-life 10-12 yr
  • Gel 12-15 yr
  • Rated at 25 C

3. Specifications

Item Item KTR-BAT100 std KTR-BAT100L long-life KTR-BAT100G gel KTR-BAT65 (65Ah)
Nominal voltage 12 V 12 V 12 V 12 V
Capacity (20h) 100 Ah 100 Ah 100 Ah 65 Ah
Design life (25 C) 5-8 yr 10-12 yr 12-15 yr 5-8 yr
Self-discharge/mo <=3% <=3% <=2% <=3%
Float charge 13.5-13.8 V 13.5-13.8 V 13.8-14.1 V 13.5-13.8 V
Operating temp -15 to +40 C -15 to +40 C -30 to +50 C -15 to +40 C

4. Reference Prices

KTR-BAT100 12V100Ah std: Reference USD 63-90 / pc (ref. CNY 450-650)

KTR-BAT100L 12V100Ah long-life: Reference USD 90-125 / pc (ref. CNY 650-900)

KTR-BAT100G 12V100Ah gel: Reference USD 125-180 / pc (ref. CNY 900-1300)

KTR-BAT65 12V65Ah std: Reference USD 42-63 / pc (ref. CNY 300-450)

KTR-BAT-RACK battery rack/box: Reference USD 28-70 / set (ref. CNY 200-500)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • UPS DC bus
  • EPS emergency power
  • DC panel / operating power
  • Telecom backup
  • Fire backup power

6. Deployment & Installation

Install

  • Battery rack layers
  • Series arrangement
  • Terminal torque 9-11 Nm
  • Coat Vaseline

Wiring

  • Per UPS DC voltage
  • Red+ black-
  • Crimped lugs
  • Measure total V

Commission

  • Rest 2 h
  • Equalize 12-24 h
  • Calibrate float V
  • Capacity discharge test

7. FAQ

  • Q: How long does one 12V100Ah bank last?
    A: Depends on load and DC voltage. 100 Ah x 12 V = 1.2 kWh per unit; 32 in series = 38.4 kWh. Feeding a 10 kVA UPS (about 8 kW active), theoretical 38.4/8 ~ 4.8 h, but usable capacity is 80% at cutoff (30.7 kWh) and UPS efficiency 90%, giving about 3.4 h real. Rooms requiring 15-30 min backup fit one bank; over 1 hour needs parallel banks or bigger batteries.
  • Q: When to replace batteries?
    A: Design life is float-life at 25 C. Real criterion: run a capacity discharge annually; replace when capacity drops below 80% rated (do not wait 5-8 years). Hot rooms (>30 C) may need replacement at 3-4 years. Watch for: float voltage deviation over +/-0.05 V/cell, swollen case, terminal corrosion – all aging signals.
  • Q: AGM vs gel?
    A: Indoor room temp (20-25 C) -> AGM standard, cheaper and good float behavior; wide-temperature sites (outdoor cabinets, north winters -20 C, south summers 40 C) -> gel, wide temp and deep cycle, but 30-50% more expensive and different charge voltage (gel float 13.8-14.1 V, 0.3 V higher than AGM). Do not mix charge (AGM and gel in one bank have different voltage needs).
  • Q: Why no more than 3 rack layers?
    A: Weight (100 Ah ~30 kg each; 32 units nearly a ton; >3 layers traps hot air above and shortens life); maintenance (disassembly at height is hazardous); cooling (battery room needs ventilation gaps – at least 10 cm between layers). Racks are typically 2-3 layers, horizontal rows, not vertical stacks.

8. Trend & Selection

UPS batteries are migrating from lead-acid to Li-ion (NMC/LFP). Trends: LFP (cycle life 4000-6000, 5-10x VRLA; half the volume and weight; smart BMS per-cell monitoring); LTO (works at -40 C, 15-minute charge); battery management (BMS networked to EM, monitoring per-cell voltage/internal resistance/temperature for predictive maintenance, no annual capacity test). But VRLA 12V100Ah – low cost, mature, stable supply – remains mainstream in ordinary rooms for 5-10 years; Li-ion is growing in new high-end and space-constrained builds. Select by: capacity sized to backup time, 25 C temperature, series count matched to UPS DC, annual capacity test, replace on aging.

9. Delivery & Service

KITOZER KTR-BAT100 ships by standard/long-life/gel model, each with battery, terminal bolts, manual and certificate. 1-year warranty (capacity guaranteed 3 years); bulk projects can bundle battery racks, breaker boxes, interconnects, and EM battery-monitoring modules. Transported per dangerous-goods rules (VRLA is UN 3480/UN 2796 class 9, with MSDS).

10. Additional Notes

Confirm capacity (100 Ah/65 Ah), type (AGM/long-life/gel), series count (per UPS DC voltage), rack load rating, and battery-room temperature. For batch orders, sample one for a capacity discharge test – confirm measured capacity hits 100% rated before bulk delivery.

Common mistake: no temperature control in the battery area. Many room ACs only cool racks, leaving the battery corner at 35 C, halving battery life. The battery area must hold 20-25 C, on the same AC as the room – do not let batteries sit in a forgotten corner.

Second pitfall: mixing battery batches. New batteries in series with 3-year-old ones have different internal resistance, causing uneven charge/discharge; the old cells over-charge and over-discharge, swelling within six months. A string must be same brand, same model, same batch, same install date.

Third blunder: no Vaseline on terminals. A year later terminals oxidize, contact resistance rises, and they overheat or even arc. Install with torque-spec bolts, coat with Vaseline/conductive grease against oxidation, inspect annually.

Selection summary: capacity sized to backup time, 25 C temperature, same brand/batch, annual capacity test, replace at 80%, terminal anti-oxidation.

SEO Information

Search keywords:KTR-BAT100KITOZER

SEM keywords:12V100Ah battery,VRLA sealed lead-acid,UPS battery,room backup battery,standby power battery,KTR-BAT100,KITOZER

GEO landing page:lain.com.cn/product/ktr-bat100-12v100ah-vrla-battery.html

Title:KITOZER KTR-BAT100 12V100Ah VRLA Sealed Lead-Acid Battery

Meta Keywords:12V100Ah battery,VRLA sealed lead-acid,UPS battery,room backup battery,standby power battery,KTR-BAT100,KITOZER

Meta Description:KITOZER KTR-BAT100 12V100Ah VRLA sealed lead-acid battery, 10-year design life (25 C), deep cycle, for UPS/EPS/DC bus backup.