KITOZER KTR-2V500B 2V500Ah Long-life VRLA Battery

Brand: KITOZER Series: KTR-2V500B Category: Power Distribution / Battery Backup

2V500AhVRLA sealed12-yr lifeKTR-2V500B

1. Overview

When a data center loses utility power, the UPS rides on the battery bank, holding up until the diesel generator starts (usually minutes to ten-plus minutes), or riding through short outages directly. The bank is a string of batteries in series (2V cells, 104 in series for 220 V; or 12 V batteries, 20 in series for 240 V). A 2V500Ah cell is a large-room size (telecom sites, data centers, 100+ cells in a string); small rooms use 12V100Ah. Batteries are consumables with a 10-12 year design life on float; in high ambient heat they fade in 5-8 years. Measure cell voltage and internal resistance regularly; replace weak cells.

KITOZER KTR-2V500B is a 2V500Ah valve-regulated lead-acid (VRLA) battery. It is a rectangular hard-plastic case (~240x120x320 mm, ~30 kg), with pasted positive plates, sponge-lead negative plates, and sulfuric acid electrolyte absorbed in AGM glass-mat separators (no spill, mountable in any orientation). The top has a one-way safety valve (vents at high internal pressure, otherwise sealed, no water topping, maintenance-free). Principle: charging gives positive PbO2 and negative sponge lead in sulfuric acid; discharging converts both plates to lead sulfate and dilutes the acid; charging restores. Key ratings: rated 2 V, 500 Ah (10-hour rate, i.e. 50 A for 10 h), 12-year design life (float at 25 C), operating -15 to +45 C, float voltage 2.25-2.27 V/cell (25 C), equalize 2.30-2.35 V/cell.

Selection: capacity (by backup time: load power / DC bus voltage = current; current x backup hours = needed Ah; 500Ah suits large rooms, small rooms use 100-200 Ah); cell count (UPS 220 V bus = 104 x 2V, 240 V = 120); life (12-year long-life costs more than 10-year but saves a replacement cycle); install (rack shelves or cabinet, series links between cells with correct torque); temperature (life halves for every 10 C rise – hold the room at 25 C); maintenance (measure internal resistance yearly, replace weak cells). Note: never short cells (insulate links); do not invert (AGM allows any orientation, but extreme tilt can leak); the initial charge must be full (factory state 50-80%).

2. Key Features

Electrical

  • 2V500Ah
  • 10h rate
  • 12-year life
  • AGM sealed

Build

  • Hard case
  • Safety valve
  • Pasted plates
  • Terminals

Use

  • Float 2.25V
  • Equalize 2.30V
  • 25 C ideal
  • Maintenance-free

3. Specifications

Item KTR-2V200B KTR-2V300B KTR-2V500B KTR-2V1000B
Rated V 2V 2V 2V 2V
Capacity 200Ah 300Ah 500Ah 1000Ah
Design life 10 yr 12 yr 12 yr 15 yr
Float V 2.25V 2.25V 2.25V 2.25V
Weight 13 kg 19 kg 30 kg 58 kg
Size (mm) 170x76x205 180x90x230 240x120x320 410x175x330

4. Reference Prices

KTR-2V200B 2V200Ah long-life: Reference USD 49-76 / pc (ref. CNY 350-550)

KTR-2V300B 2V300Ah long-life: Reference USD 76-111 / pc (ref. CNY 550-800)

KTR-2V500B 2V500Ah long-life: Reference USD 125-194 / pc (ref. CNY 900-1400)

KTR-2V1000B 2V1000Ah long-life: Reference USD 250-361 / pc (ref. CNY 1800-2600)

KTR-BAT-LINK inter-cell link + cover kit: Reference USD 4-8 / cell (ref. CNY 30-60)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • UPS DC battery bank
  • DC switchgear panel
  • Telecom backup
  • Emergency lighting
  • Solar storage

6. Deployment & Installation

Install

  • Rack shelf
  • Series links
  • Torque fix
  • Insulating cover

Wiring

  • Correct +/-
  • Thick cable
  • Contact resist.
  • String voltage

Maintain

  • Equal float V
  • Annual ESR
  • Replace weak
  • 25 C room

7. FAQ

  • Q: How many cells in a 2V500Ah string?
    A: By the UPS DC bus voltage. Common: small UPS (<10kVA) uses 240V (20 x 12V, or 120 x 2V); medium/large (20-200 kVA) uses 220V (104 x 2V) or 380V (180 x 2V). One 2V500Ah cell, 104 in series = 208V500Ah. Follow the UPS manual – do not decide yourself. Capacity: load kW x backup hours / DC voltage = current; divide by discharge factor to get Ah.
  • Q: How long do batteries last?
    A: Design life 12 years on float at 25 C. In reality: life halves for every 10 C rise (corrosion accelerates). A 25 C battery room gives 8-10 years. Without AC (35 C in summer), capacity fades to 80% in 5-6 years. Deep discharge (running to cutoff) sulfates plates and slashes life. UPS batteries are shallow-cycled on float (only discharge during outages), so they last long. Run an annual capacity test; below 80%, plan replacement.
  • Q: How to find a bad cell?
    A: Measure internal resistance (a battery ESR meter, one per cell). Cells in a string should match (within 20%); one with suddenly doubled ESR is the weak cell – replace it. Also check float voltage: a weak cell reads low (cannot accept charge), healthy cells are even. A capacity discharge test shows which cell sags fastest. An online BMS measures each cell’s voltage and ESR and alarms remotely.
  • Q: Can I mix new and old batteries?
    A: No. Old cells have higher ESR; in series discharge they take a larger share of voltage and over-destruct, while new cells stay under-charged. Either replace the whole string, or swap only the clearly weak cells with same-model, same-batch cells of near-identical ESR. Mixing kills the whole string early. After 8-10 years, replace the whole string (costly but safe); at 2-3 years with a single bad cell, swap one same-batch cell.

8. Trend & Selection

Battery technology is moving to long life and smart monitoring. Trends: gel batteries (gelled electrolyte, no spill, heat-tolerant, deep-cycle friendly, longer than AGM); LiFePO4 lithium (small, light, high cycle count, displacing lead-acid in UPS but pricier); BMS (per-cell voltage/temp monitoring, remote balancing, auto alarms); modular UPS (battery integrated, plug-and-play); storage fusion (banks also do peak shaving). Traditional 2V500Ah VRLA remains mainstream for UPS backup (low cost, mature). Select by: capacity for backup time, cell count for UPS DC bus, 25 C room, annual ESR test, whole-string replacement.

9. Delivery & Service

KITOZER KTR-2V500B ships per cell on a wooden pallet with foam, including battery, inter-cell links, insulating covers, manual, certificate and factory test report (capacity, ESR). 1-year warranty; bulk projects can bundle battery racks, BMS units, battery breakers and discharge testers.

10. Additional Notes

Calculate capacity for backup time, confirm cell count for the UPS DC bus, and confirm battery-room ventilation and temperature control.

Common mistake: no AC in the battery room. At 35 C in summer, life drops from 10 years to 5. The battery room needs dedicated AC or shares the room’s temperature zone.

Second pitfall: links not torqued. Loose links raise contact resistance; under high discharge they heat, spark and burn terminals. Torque per factory spec (usually 10-15 N·m) and coat with petroleum jelly against oxidation.

Third blunder: swapping one cell without matching ESR. A new cell’s ESR differs from the old string and becomes the weak point. Match batch and ESR when swapping.

Selection summary: capacity for backup time, count by DC bus, 25 C control, annual ESR test, whole-string replacement.

SEO Information

Search keywords:KTR-2V500BKITOZER

SEM keywords:2V500Ah battery,VRLA battery,long-life battery,UPS backup battery,KTR-2V500B,KITOZER,power distribution

GEO landing page:lain.com.cn/product/ktr-2v500b-valve-regulated-lead-acid-battery.html

Title:KITOZER KTR-2V500B 2V500Ah Long-life VRLA Battery

Meta Keywords:2V500Ah battery,VRLA battery,long-life battery,UPS backup battery,KTR-2V500B,KITOZER,power distribution

Meta Description:KITOZER KTR-2V500B 2V500Ah VRLA battery, 12-year design life, float charge, for UPS and DC panel backup.

Anchor: KITOZER by Guangzhou Laian · KITOZER products