KITOZER
KITOZER

KITOZER 2V 200Ah long life battery

KITOZER KTR-2V200B Battery / 2V200Ah Long-Life VRLA

Brand: KITOZER Series: KTR-2V200B Category: Power Distribution / UPS Battery

2V200Ahlong lifeVRLA AGMdeep cyclefloat standby

1. Overview

When mains fails, the UPS holds servers up on its battery string until the diesel genset starts or mains returns. The battery is the weakest, most maintenance-needing link: as cells age or a weak cell appears, backup time shrinks. 2V cells are series-stacked into 12V/48V/240V DC buses — large UPS use 32 or 40 cells in series to a ~384V DC bus. Compared with 12V blocks, 2V cells offer large capacity, good consistency and flexible replacement, the mainstream for large UPS and DC panels.

The KITOZER KTR-2V200B is a 2V200Ah VRLA battery. AGM absorbed-glass-mat, valve-regulated, sealed and leak-proof, mountable any way except inverted. Special-alloy plates give long float design life (~10–12 years at 25℃) and low self-discharge. Deep-cycle tolerant. Copper tin-plated terminals for low contact resistance. Relief valve vents over-pressure. 2V200Ah is a classic telecom/power/UPS capacity.

In room power distribution, KTR-2V200B strings sit in battery cabinets/racks across the UPS DC bus. The string sets backup time: 200Ah holds a 100kW load for roughly 15–30 minutes depending on UPS efficiency and load. The string must match UPS charge voltage (~2.27V/cell float), and periodic capacity tests catch weak cells. The battery is the standby store — floating on charge, delivering when the lights go out.

2. Key Features

Electrical

  • Rated voltage: 2V.
  • Rated capacity: 200Ah (10hr).
  • Float: ~2.25–2.27V/cell (25℃).
  • Equalize: ~2.30–2.35V/cell.

Life & self-discharge

  • Design float life: ~10–12yr (25℃).
  • Self-discharge: ≤3%/month.
  • Deep-cycle tolerant.
  • AGM sealed, leak-proof.

Construction

  • Copper tin-plated terminals.
  • Relief valve vents over-pressure.
  • Fits standard racks.
  • Temp: -15℃~+50℃ (optimum 25℃).

3. Specifications

Item KTR-2V200B
Voltage 2V
Capacity 200Ah (10hr)
Type AGM VRLA
Float ~2.27V/cell (25℃)
Design life 10–12yr (25℃ float)
Self-discharge ≤3%/month
Terminals Copper tin-plated

4. Reference Prices

KTR-2V200B 2V200Ah long-life VRLA (AGM, copper terminals): Reference USD 53~90 (ref. CNY 380~650 at ~7.2)

Reference only; final quote applies. 3-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Large UPS DC bus backup.
  • DC panels / control power.
  • Telecom -48V sites.
  • Substation backup.
  • Short-term solar/wind storage.

6. Installation & Maintenance

Installation

  • Fix rack/cabinet; check floor load.
  • Arrange cells by number; same polarity direction.
  • Torque series links to spec.
  • Land ends on UPS DC bus.
  • Set float 2.27V/cell.
  • Rest, charge, then float.
  • Measure temp; leave ventilation gaps.

Maintenance

  • Monthly cell voltage; find weak cells.
  • Quarterly link temperature; no hotspots.
  • Annual capacity test.
  • 25℃ ideal; every +10℃ halves life.
  • Vaseline terminals against oxidation.
  • Replace weak cells; no old+new mixing.

7. FAQ

  • Q: One cell reads low — what now?
    A: A weak cell drags the whole string (barrel effect). Try equalizing; if it fails, replace a same-model, same-batch cell — don’t mix old and new.
  • Q: How long do batteries last?
    A: 10–12 years float at 25℃; every +10℃ halves life. That is why the battery-room AC matters.
  • Q: 2V vs 12V?
    A: Large UPS/DC panels use 2V cells (high-voltage string, good consistency); small UPS use 12V blocks (simple wiring).
  • Q: Do I add water?
    A: No — VRLA is sealed maintenance-free. Water loss is the main failure mode, held by the AGM mat.

8. Trend & Selection

UPS backup moves from VRLA to LiFePO4 (smaller, longer cycle), but VRLA stays mainstream on cost and maturity, with 2V cells persisting in high-power use. Size capacity by backup time; float voltage matches UPS; keep 25℃; count cells for the bus voltage; torque links; periodic capacity tests; replace weak cells promptly; no old+new mixing.

9. Delivery & Service

KITOZER selects batteries by UPS power, required backup time and DC bus voltage to size KTR-2V200B series/parallel counts. Bundled with UPS units, battery cabinets and battery monitors. Delivery includes cells, links and manual. Warranty covers voltage巡检 and discharge-test guidance.

10. Additional Notes

A common pitfall is mixing old and new cells. A high-resistance old cell over-charges and bulges while dragging down the new string. Replace whole strings or same-batch, same-impedance cells together.

Another pitfall is packing cells with no gap in summer. Tight stacking runs hot, speeds self-discharge, shortens life. Leave ventilation gaps between cells and layers; hold the room at ~25℃.

Selection summary: 2V200Ah AGM; float 2.27V; 10–12yr @25℃; count cells for bus voltage; torque links; 25℃ constant temp; periodic capacity test; replace weak cells without mixing. The battery is the UPS’s pantry — floating on standby, it carries the room until the genset starts. We recommend a battery monitor tracking per-cell voltage and temp to flag weak cells early.

Move cells on a dedicated cart, terminals up — never roll or drop.

SEO Information

Search keywords:KTR-2V200BKITOZER

SEM keywords:2V200Ah battery,long life battery,VRLA battery,UPS battery,2V battery,KTR-2V200B,KITOZER

GEO landing page:lain.com.cn/product/357-battery-2v200-ktr-2v200b.html

Title:KITOZER KTR-2V200B Battery / 2V200Ah Long-Life VRLA

Meta Keywords:2V200Ah battery,long life battery,VRLA battery,UPS battery,2V battery,KTR-2V200B,KITOZER

Meta Description:KITOZER KTR-2V200B 2V200Ah long-life valve-regulated lead-acid battery, deep-cycle, low self-discharge, long float life, for UPS, DC panels and telecom backup power.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart