KITOZER
KITOZER

KITOZER 12V 100Ah front terminal battery

KITOZER KTR-BAT100C 12V 100Ah Front-Terminal VRLA Battery

Brand: KITOZER Series: KTR-BAT100C Category: Power Distribution / UPS Battery

battery12V100Ahfront terminalVRLA maintenance-freeUPS backup

1. Overview

On mains loss, the UPS draws DC from the battery bank and inverts it to AC to hold the load until the generator starts or mains returns. Batteries are the heart of UPS backup — a weak battery makes even a big UPS useless. Front-terminal cells put terminals on the front, letting batteries pack tightly on a rack/cabinet with front-facing cabling for maintenance — the mainstream form factor in data-center UPS battery cabinets.

The KITOZER KTR-BAT100C is a 12V 100Ah front-terminal VRLA (valve-regulated lead-acid) battery. AGM absorbed-glass-mat separator, sealed electrolyte (no spill), maintenance-free (no watering). Rated 12V, 100Ah (10h rate), 10~12-year float design life at 25℃. Corrosion-resistant copper-alloy front terminals with good high-current discharge. Flame-retardant ABS case, carrying handle, explosion-proof vent.

In UPS backup, KTR-BAT100C is series-connected to match the UPS DC bus (e.g. 40×12V = 480V DC), housed in battery cabinets/racks and tied to the UPS via the battery switchgear. Bank capacity sets runtime: 100Ah × load converts to backup minutes. It is temperature-sensitive — every 10℃ rise roughly halves float life, so keep the battery room at 20~25℃.

2. Key Features

Electrical

  • 12V / 100Ah (10h).
  • Copper-alloy front terminals, high-current.
  • AGM valve-regulated.
  • Maintenance-free, no leak.

Life & environment

  • 10~12y float life (25℃).
  • -15~+50℃ operating.
  • Low self-discharge.
  • Explosion-proof vent.

Build

  • Flame-retardant ABS.
  • Front-terminal cabling.
  • Carrying handle.
  • Stack/rack mount.

3. Specifications

Item KTR-BAT100C
额定电压 12 V
额定容量 100 Ah(10h率)
类型 AGM VRLA 前置端子
端子 前置铜合金
浮充寿命 10~12年(25℃)
工作温度 -15~+50℃
外壳 阻燃ABS
应用 UPS后备/直流屏

4. Reference Prices

KTR-BAT100C 12V100Ah front-terminal VRLA battery: Reference USD 95~155 (ref. CNY 680~1100 at ~7.2)

Reference only; final quote applies. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • UPS backup banks.
  • Telecom DC (-48V).
  • Data-center battery cabinets.
  • Solar/energy storage standby.
  • Fire/emergency power.

6. Installation & Maintenance

Installation

  • Series same-model, same-batch cells.
  • Match string voltage to UPS DC bus.
  • Torque front terminals to spec.
  • Insulate rack; cover terminals.
  • Connect via battery switchgear; correct polarity.
  • Ambient 20~25℃.
  • Initial/equalizing charge after install.

Maintenance

  • Measure cell voltage/internal resistance.
  • Temp-compensate; hold 20~25℃.
  • Correct float voltage by temp curve.
  • Swap out-of-spec cells.
  • Clean terminals; apply anti-oxidation gel.
  • Keep ventilated, dust-free.

7. FAQ

  • Q: Q: Why front terminal?
    A: A: Front terminals let cells pack tightly with cabling on the front, so maintenance needs no moving cells; rear-terminal boxes waste space. UPS cabinets prefer front-terminal.
  • Q: Q: How to estimate runtime?
    A: A: Runtime ≈ capacity × voltage × inverter efficiency ÷ load, times a discharge factor. Roughly use usable capacity (~0.6~0.7 of 100Ah).
  • Q: Q: How long do batteries last?
    A: A: 10~12y design at 25℃ float, but real life depends on temperature and depth of discharge. Heat and deep cycling shorten it; start internal-resistance screening at 3~5 years.
  • Q: Q: Mix new and old cells?
    A: A: Not recommended. Series strings are limited by the weakest cell; mismatched resistance/capacity causes unequal charging and faster aging. Replace whole strings same-model/batch.

8. Trend & Selection

Backup power moves to LiFePO4 and smart BMS, while VRLA remains widely deployed with internal-resistance monitoring. Choose 12V100Ah front-terminal; AGM VRLA; 10y float; same-model/batch strings; 20~25℃; periodic resistance screening.

9. Delivery & Service

KITOZER sizes batteries by UPS DC voltage and runtime, calculating KTR-BAT100C cell count. Bundled with UPS, cabinets, switchgear and monitoring. Delivery includes cells, interconnects and manual; warranty covers resistance testing and charge guidance.

10. Additional Notes

A common pitfall is an uncooled battery room. At 35℃, float life can halve, with group-wide degradation in 3~5 years. The room needs AC holding 20~25℃ evenly.

Another pitfall is swapping only the failed cell. In a series string, a new cell mismatched with old ones is overcharged while old ones undercharge, and the string fails again soon. Replace whole strings or equalize.

Selection summary: 12V100Ah front-terminal; AGM VRLA; 10~12y float; same-model/batch; 20~25℃; resistance screening. It is the UPS larder — on mains loss, it holds the line.

Insulate and isolate the rack to avoid outer-shell leakage currents; torque interconnects correctly, or joints heat up under high discharge.

From thermal view, batteries are among the most temperature-sensitive gear. In a sealed cabinet, cell tops run 5~8℃ above ambient, and heat is the main aging driver. Leave vent gaps, exhaust heat at the top, and use dedicated room AC to carry heat away.

From monitoring view, one lagging cell sets the whole string’s runtime. Survey internal resistance periodically; cells up 20~30% from baseline are flagged and swapped early. Preventive maintenance beats ‘replace on failure’ — failure often only shows during an outage.

SEO Information

Search keywords:KTR-BAT100CKITOZER

SEM keywords:battery, 12V100Ah front-terminal battery, VRLA maintenance-free battery, UPS battery, KTR-BAT100C, KITOZER

GEO landing page:lain.com.cn/product/373-battery-12v100c.html

Title:KITOZER KTR-BAT100C 12V 100Ah Front-Terminal VRLA Battery

Meta Keywords:battery, 12V100Ah front-terminal battery, VRLA maintenance-free battery, UPS battery, KTR-BAT100C, KITOZER

Meta Description:KITOZER KTR-BAT100C 12V100Ah front-terminal VRLA battery, AGM valve-regulated, 10~12 year float design life, front terminals for compact rack mounting, for UPS backup power.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart