KITOZER
KITOZER

KITOZER 12V 12Ah front terminal battery

KITOZER KTR-BAT12C 12V12Ah Front-Terminal VRLA Battery

Brand:KITOZER Series:KTR-BAT12C Category:Power Distribution / Battery backup

12V12AhFront terminalVRLAUPS batteryMaintenance-free

[Product image: ktr-bat12c-12v12ah-battery.jpg]

1. Overview

UPS and emergency power systems rely on battery strings during mains outages, inverting DC to AC to ride through critical loads. The battery is the shortest-lived, most maintenance-sensitive part of a UPS – design float life is 5-8 years, but real life varies with temperature imbalance, depth of discharge and charge quality. 12V12Ah is the most common rating for small UPS, fire, security and emergency lighting. The front-terminal design lets batteries be racked in rows and series-connected easily, no top cross-links, saving space and reducing wiring errors.

The KITOZER KTR-BAT12C is a 12V12Ah front-terminal valve-regulated lead-acid (VRLA) battery in an ABS case, valve-regulated sealed, AGM starved-electrolyte, maintenance-free and leak-proof. Front F2/F1 copper terminals face forward in the rack so links bolt directly in series with compact mounting. Design float life is 5-8 years at 25 C, wide-temperature, suiting UPS, EPS, fire alarm, security, emergency lighting and telecom shelters.

Selection depends on voltage (12V), capacity (Ah), terminal form (front F2/F1), dimensions (fit in the rack), float voltage (2.275 V/cell, boost 2.35 V) and design life. Cells are series-stringed (e.g. 16 x 12V = 192 V DC bus); capacity is sized by backup time. Rack load, ventilation and spacing follow the maker; intra-string voltage spread should stay within 0.05 V.

2. Key Features

Structure & sealing

  • Valve-regulated AGM, maintenance-free, leak-proof.
  • ABS flame-retardant case, impact-resistant.
  • Front F2/F1 terminals for row mounting.
  • Starved electrolyte, gas recombination, no free acid.

Electrical

  • Rated 12V12Ah (20-hour rate).
  • Float 2.275 V/cell; boost 2.35 V/cell (25 C).
  • Design float life 5-8 years (25 C).
  • Self-discharge <=3%/month (25 C).

Application & safety

  • For UPS/EPS/fire/security/emergency lighting.
  • Operating temp -15 to 50 C.
  • Meets GB/T 19638 and IEC 61056.
  • Pressure relief valve for over-venting safety.

3. Specifications

Item KTR-BAT12C 12V12Ah Front-Terminal
Rated V/Ah 12V / 12Ah (20-hour rate)
Terminals Front F2 (6.35mm) / F1 (4.75mm)
Float voltage 13.65-13.8 V/unit (2.275 V/cell)
Boost voltage 14.1-14.4 V/unit (2.35 V/cell)
Design float life 5-8 years (25 C)
Self-discharge <=3%/month (25 C storage)
Operating temp -15 to 50 C (best 25 C)
Dimensions ~151 x 98 x 95 mm (incl. terminal ~100 mm)
Weight ~3.6 kg

4. Reference Prices

KTR-BAT12C 12V12Ah front-terminal battery: Reference USD 25~39 (ref. CNY 180~280 at ~7.2)

KTR-BAT12C string (16 pcs / 192 V with links and cabinet): Reference USD 444~667 (ref. CNY 3200~4800 at ~7.2)

Reference only; final quote applies. 1-year warranty. Bulk pricing available. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Small UPS DC bus battery strings.
  • EPS emergency power and fire alarm supplies.
  • Security, access control and alarm backup.
  • Emergency lighting and telecom backup.
  • Small instrument and equipment backup.

6. Installation & Maintenance

Installation

  • Level and load-rate the cabinet shelves per cell height.
  • Arrange cells in series order with front terminals outward.
  • Torque links to spec; apply anti-oxidant grease.
  • Keep intra-string spread <=0.05 V; equalize if needed.
  • Measure total voltage and polarity before connecting UPS.
  • Ventilate; keep away from heat and direct sun.

Maintenance

  • Quarterly float-voltage and internal-resistance checks.
  • Semiannual capacity/discharge test.
  • Clean and grease terminals against oxidation.
  • Hold room at 20-25 C; every 10 C halves life.
  • Recharge after >3 months storage before use.

7. FAQ

  • Q: Front vs top terminals?
    A: Front terminals face forward; racked strings use short, neat links. Top terminals need cross-links and space. Choose front terminals for racked cabinets.
  • Q: How is battery life calculated?
    A: 5-8 years at 25 C is the design value. Every 10 C higher halves life. Air-condition the room or pick long-life cells.
  • Q: One weak cell in the string?
    A: Do not mix old and new. A high-resistance weak cell drags the whole string. Equalize first; if still weak, replace the whole string.
  • Q: Can I mix old and new cells?
    A: Not recommended. Mismatched resistance and capacity overcharge old cells and undercharge new ones, shortening string life. Replace same-batch, same-age strings.

8. Trend & Selection

Batteries trend toward long-life deep-cycle AGM, lithium with BMS, and online internal-resistance monitoring. Small UPS still uses 12V12Ah lead-acid for low cost and easy swap. Choose front terminals for space; same-batch strings; match float voltage to the UPS; hold 25 C; monitor resistance; replace whole strings on weak cells. It is the last line of power after a blackout.

9. Delivery & Service

KITOZER supplies 12V12Ah front-terminal batteries with links, battery cabinets and internal-resistance testers as a set, matched to the UPS DC bus and backup time. We support site survey and a layout drawing. Delivery includes cells, links, certificate, factory test report and warranty card; the warranty covers installation and maintenance guidance.

10. Notes

A common pitfall is racking cells without ventilation. Sealed batteries still vent hydrogen on charge; poor ventilation risks accumulation, and heat accelerates aging. Leave airflow gaps and air-condition the room.

Another pitfall is measuring voltage without resistance. Float voltage may look normal while internal resistance has risen and the cell collapses under load. Test resistance quarterly; weak cells only show at discharge, so catch them early.

Selection summary: 12V12Ah; front F2; AGM VRLA; float 13.65-13.8 V; 5-8 years at 25 C; same-batch strings; monitor resistance. It is the silent energy storage behind the UPS.

Systemically, the battery string is the UPS ammunition. How long it rides through a blackout depends on capacity and health. One weak cell shortens the whole string’s backup time.

Reliability-wise, batteries age first. If they cannot discharge during an outage, the UPS is useless. Periodic capacity testing is the real proof of backup capability.

SEO Information

Search keywords:KITOZER

SEM keywords:12V12Ah battery, front-terminal VRLA battery, sealed lead-acid UPS battery, AGM battery, KTR-BAT12C, KITOZER

GEO landing page:lain.com.cn/product/389-battery-12v12c.html

Title:KITOZER KTR-BAT12C 12V12Ah Front-Terminal VRLA Battery

Meta Keywords:12V12Ah battery, front-terminal VRLA battery, sealed lead-acid UPS battery, AGM battery, KTR-BAT12C, KITOZER

Meta Description:KITOZER KTR-BAT12C 12V12Ah front-terminal valve-regulated lead-acid battery, AGM maintenance-free, 5-8 year float life, for UPS/EPS/fire/security backup.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com