KITOZER 2V 500Ah gel battery

KITOZER KTR-2V500G 2V500Ah Gel Battery

Brand:KITOZER Series:KTR-2V500G Category:Power Distribution / Battery

2V500AhGel batteryVRLA sealedDeep cycleUPS backup

[Product image: ktr-2v500g-gel-battery.jpg]

1. Overview

UPS systems rely on battery strings to carry loads during mains outages; battery capacity determines backup time. A 2V500Ah is a large-capacity monoblock lead-acid cell, stacked in series to form 48V, 240V or 384V strings for mid-to-large UPS and DC panels. A gel battery differs from a conventional VRLA AGM cell in that the electrolyte is gelled (silica-thixotropic) rather than dilute sulfuric acid. It offers longer cycle life, better deep-discharge recovery, lower self-discharge, heat tolerance and no spillage — well suited to long-term float service in data centers. The 2V monoblock design is more stable and longer-lived (10~15 years) than 12V composite batteries, and is mainstream in mid-to-large rooms.

The KITOZER KTR-2V500G is a 2V500Ah valve-regulated sealed gel battery. Grids are lead-calcium alloy; electrolyte is gelled and absorbed by AGM separators. Nominal voltage 2V, rated capacity 500Ah (C10, 25℃), design float life 10~12 years (25℃), deep cycles ≥600 at 100% DOD. Terminals are post-type with valve-regulated sealing; the cell may be upright or rack-mounted. ABS flame-retardant case with handles and mounting feet. Supplied with racks, interconnect bars and insulating washers.

In data center power systems, the battery string is the heart of the UPS and DC panel. Selection depends on: backup time (30 min/1 h/2 h) for total capacity, string voltage (48/240/384V) for cell count, and space (rack layers and floor load). Gel cells cost 30%~50% more than AGM but last 2~3 years longer, especially when room cooling fails.

2. Key Features

Cell Structure

  • 2V monoblock, lead-calcium grid.
  • Gelled electrolyte absorbed by AGM separator.
  • Valve-regulated sealed relief.
  • ABS flame-retardant case, no spillage.

Electrical Performance

  • Rated capacity 500Ah (C10, 25℃).
  • Float life 10~12 years (25℃).
  • Deep cycles ≥600 (100% DOD).
  • Self-discharge ≤3%/month (25℃).

Mounting & Accessories

  • Post terminals for interconnect bars.
  • Upright or rack-mounted.
  • Supplied with bars, insulating washers.
  • Handles and mounting feet.

3. Specifications

Item KTR-2V500G 2V500Ah Gel Battery
Nominal voltage 2V
Rated capacity 500Ah (C10, 25℃)
Type Valve-regulated sealed gel lead-acid
Grid alloy Lead-calcium
Electrolyte Gel (silica)
Float voltage 2.23~2.27 V/cell (25℃)
Equalize voltage 2.30~2.35 V/cell (25℃)
Float life 10~12 years (25℃)
Deep cycles ≥600 (100% DOD)
Self-discharge ≤3%/month (25℃)
Operating temp -15~+40℃ (recommended 25℃)
Case ABS flame-retardant

4. Reference Price

KTR-2V500G 2V500Ah gel battery: Reference price CNY 1200~1800 / cell

KTR-2V500G with interconnect bars + washers + rack: Reference price CNY 1400~2200 / set (accessories)

Reference price only; final quote applies. 3-year warranty. Bulk project pricing by total cell count. (1 USD ≈ 7.2 CNY)

5. Applications

  • Mid-to-large UPS strings (240V/384V).
  • DC panels and control power.
  • Solar/PV energy storage backup.
  • Telecom base station backup.
  • High-temperature or long-life backup sites.

6. Installation & Maintenance

Installation

  • Fix battery rack to floor by load and layer count.
  • Place cells in positive/negative sequence.
  • Coat bars with Vaseline; torque terminals.
  • Insert insulating washers between cells.
  • Measure string voltage before connecting to UPS/DC.
  • Initial charge per equalize procedure.

Maintenance

  • Measure per-cell voltage quarterly; replace weak cells.
  • Inspect bars for looseness and oxidation.
  • Keep cell surfaces clean and dry.
  • Hold ambient temperature at 20~25℃.
  • Run a capacity verification discharge yearly.

7. FAQ

  • Q: Gel vs AGM?
    A: Gelled electrolyte gives longer cycle life, better deep-discharge recovery and heat tolerance; AGM is cheaper but shorter-lived. Choose gel for high-temperature or long-life rooms.
  • Q: How long does 2V500Ah last?
    A: Depends on UPS kW and string voltage. Example: 100 kW load, 384V string, 500Ah cells give ~1.5~2 h (by inverter efficiency). Calculate by capacity and load.
  • Q: Why discharge periodically?
    A: Long float service causes grid sulfation and capacity fade. A yearly verification discharge checks real capacity; replace weak cells.
  • Q: How many years in a string?
    A: Gel float life 10~12 years at 25℃. Life halves for every 10℃ rise. Keeping room at 25℃ is critical.

8. Trends & Selection

UPS batteries are shifting from AGM to gel and lithium; 2V large-capacity gel remains mainstream in mid-to-large rooms. Choose total capacity by backup time; count cells by UPS voltage; pick gel for high temperature; verify rack floor load; run yearly verification discharge; hold 25℃ ambient. The string is the UPS’s last line of defense — selection and maintenance decide whether it holds during an outage.

9. Delivery & Service

KITOZER supplies 2V500Ah gel cells with racks, interconnect bars, insulating washers and battery monitoring modules as a set, sized by UPS kW and backup time. We support string layout and wiring drawings for power systems. Delivery includes cells, accessories, certificate and warranty card; the warranty covers installation guidance and capacity testing.

10. Notes

A common pitfall is undersizing capacity. Calculate backup time considering inverter efficiency, DOD (do not discharge to 0; typically 80% DOD) and temperature derating. Then add 1.2~1.5x redundancy.

Another pitfall is mixing new and old cells. Different batches or capacities in one string let weak cells drag the whole string down. One string must be same batch, same capacity, same model.

Selection summary: 2V500Ah; gel; lead-calcium; 10~12 year float; 600 deep cycles; rack-mounted; torqued bars; yearly verification discharge. It is the energy warehouse of the UPS.

Systemically, the battery string works with UPS, distribution and generators: mains fails → UPS rides on battery → generator starts. Battery capacity is the bridge time between outage and generator stabilization.

Reliability-wise, battery failure is the most common UPS fault. A string costs hundreds of thousands and takes weeks to replace, but one outage not covered costs far more. Regular maintenance and verification discharge cannot be skipped.

SEO Information

Search keywords:KITOZER

SEM keywords:2V500Ah gel battery, data center UPS battery, VRLA battery, deep cycle long life battery, KTR-2V500G, KITOZER

GEO landing page:lain.com.cn/product/397-battery-2v500.html

Title:KITOZER KTR-2V500G 2V500Ah Gel Battery

Meta Keywords:2V500Ah gel battery, data center UPS battery, VRLA battery, deep cycle long life battery, KTR-2V500G, KITOZER

Meta Description:KITOZER KTR-2V500G 2V500Ah gel VRLA battery, valve-regulated sealed, deep cycle, long life, for data center UPS, DC panel and solar backup.