KITOZER
KITOZER

KITOZER 12V 100Ah deep cycle gel battery

KITOZER KTR-BAT100D 12V100Ah Deep-Cycle Gel Battery

Brand: KITOZER Series: KTR-BAT100D Category: Power Distribution / Storage battery

12V100AhDeep-cycle gelVRLA sealed10-12 yr lifeUPS backup

[Product image: ktr-bat100d-12v100ah-gel-battery.jpg]

1. Overview

UPS, solar storage and telecom base stations rely on battery banks for backup power. The 12V100Ah cell is the most common building block for data-center UPS; multiple cells in series form a DC192V or DC240V string. Deep-cycle gel batteries use gelled electrolyte and tolerate deeper discharges than ordinary VRLA AGM — up to 3000 cycles at 50% DOD — with lower self-discharge and more stable high-temperature performance. The valve-regulated sealed design needs no watering and is explosion-safe.

The KITOZER KTR-BAT100D is a 12V100Ah deep-cycle gel battery, rated 12V / 100Ah (20hr). It combines AGM separator with gelled electrolyte and pasted lead-calcium grids. Design life 10 to 12 years (float at 25 C). Self-discharge <=3% per month. Operating temp -20 to +60 C (discharge), charge 0 to +40 C. M8 copper terminals, flame-retardant ABS case. Meets GB/T 19638, IEC 60896-2. Supports horizontal mounting (tilt <=90 deg).

Selection confirms: voltage (12V), capacity (100/65/150/200 Ah), gel vs AGM, float voltage (2.275 V/cell), and equalize voltage (2.40 V/cell). String count depends on UPS DC bus: DC192V uses 16 x 12V in series; DC240V uses 20. Backup time is load kW divided by usable string capacity. Gel suits frequent deep-discharge scenarios (solar, storage); AGM is fine for UPS float but gel lasts longer.

2. Key Features

Deep-cycle performance

  • Gelled electrolyte, deep-discharge tolerant.
  • >=3000 cycles at 50% DOD.
  • Self-discharge <=3% per month.
  • Stable at high temperature.

Structure and safety

  • VRLA sealed, no watering.
  • AGM + gel hybrid.
  • Lead-calcium grids, corrosion-resistant.
  • Flame-retardant ABS, explosion-proof valve.

Electrical

  • Rated 12V100Ah (20hr).
  • Float 2.275 V/cell, equalize 2.40 V/cell.
  • Operating temp -20 to +60 C.
  • M8 copper terminals.

3. Specifications

Item KTR-BAT100D 12V100Ah Gel Battery
Rated voltage 12V
Rated capacity 100Ah (20hr)
Type Deep-cycle gel
Design life 10-12 yr (float at 25 C)
Self-discharge <=3% / month
Float voltage 2.275 V/cell (13.65 V/unit)
Equalize voltage 2.40 V/cell (14.4 V/unit)
Cycle life >=3000 @ 50% DOD
Operating temp. -20 to +60 C (discharge)
Terminals M8 copper
Case Flame-retardant ABS
Weight approx. 30 kg

4. Reference Prices

KTR-BAT100D 12V100Ah gel battery: Reference USD 170~250 (ref. CNY 1200~1800 at ~7.2)

KTR-BAT65D 12V65Ah gel battery: Reference USD 97~140 (ref. CNY 700~1000 at ~7.2)

KTR-BAT200D 12V200Ah gel battery: Reference USD 305~445 (ref. CNY 2200~3200 at ~7.2)

KTR-BAT100D battery cabinet (with cables): Reference USD 110~210 (ref. CNY 800~1500 at ~7.2)

Reference only; final quote applies. 3-year warranty. Bulk pricing available. Old-battery recycling quoted separately. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • Data-center UPS backup (16/20 cells in series).
  • Solar storage and off-grid plants.
  • Telecom base stations.
  • Fire emergency power (EPS).
  • EV and golf-cart deep-cycle use.

6. Installation & Maintenance

Installation

  • Keep battery room at 20 to 25 C.
  • Rack cells with >=10 mm spacing for cooling.
  • Series wiring: 16 cells = DC192V, 20 = DC240V.
  • Torque M8 connectors to 9 to 11 N·m.
  • Initial equalize charge 24 to 48 hours.
  • Measure per-cell float voltage; spread <=0.05 V.

Maintenance

  • Measure float voltage and internal resistance monthly.
  • Capacity test annually.
  • Coat terminals with petroleum jelly.
  • Ventilate; keep temp <=25 C.
  • Replace cells whose resistance exceeds baseline by 20%.

7. FAQ

  • Q: Gel or AGM?
    A: AGM suits UPS float and is cheaper; gel suits frequent deep discharge (solar/storage), longer cycle life but ~20% more expensive.
  • Q: Why is battery life short?
    A: Mostly heat. Every 10 C rise halves life. Keep the room at 25 C.
  • Q: Can I mix old and new cells?
    A: No. Different internal resistances cause overcharge/over-discharge of the weak cell. Replace the whole string.
  • Q: How long does 100Ah last?
    A: 12V100Ah stores about 1.2 kWh (at 50% DOD). A 1 kW load backs up about 36 minutes, depending on UPS efficiency.

8. Trend & Selection

Batteries trend toward gel and lithium replacement, but lead-acid gel still dominates UPS. LiFePO4 is penetrating long-cycle scenarios, yet 12V100Ah gel remains the data-center UPS standard. Choose 12V100Ah for UPS; gel for long life; control room at 25 C; test resistance quarterly; replace in whole strings. It is the heart of the UPS.

9. Delivery & Service

KITOZER supplies KTR-BAT100D batteries including unit, interconnect bars, certificate and factory test report. Battery cabinets are supplied as a package. String capacity calculation and installation guidance are provided.

10. Notes

A common pitfall is a sealed, hot battery room. Poor ventilation shortens life. Ventilate and hold 25 C.

Another pitfall is under-torqued interconnect bars. Loose M8 lugs add contact resistance, heat up and burn terminals under high discharge. Use a torque wrench at 9 to 11 N·m.

Selection summary: 12V100Ah; deep-cycle gel; 10-12 yr life; float 13.65 V; 3000 cycles; M8 terminals. It is the core energy store of UPS backup.

Systemically, a power outage with a dead battery means zero UPS backup and a full-room shutdown. Battery banks are about 40% of UPS cost but protect all services.

Cost-wise, one 100Ah gel cell is about 1500 CNY; a 16-cell string is about 24,000 CNY — trivial versus a room-down outage.

SEO Information

Search keywords: KITOZER

SEM keywords: 12V100Ah gel battery, deep-cycle battery, UPS backup battery, data-center battery, solar storage, KTR-BAT100D, KITOZER

GEO landing page: lain.com.cn/product/429-battery_12v100d.html

Title: KITOZER KTR-BAT100D 12V100Ah Deep-Cycle Gel Battery

Meta Keywords: 12V100Ah gel battery, deep-cycle battery, UPS backup battery, data-center battery, KTR-BAT100D, KITOZER

Meta Description: KITOZER KTR-BAT100D 12V100Ah deep-cycle gel battery, VRLA sealed, 10-12 year design life, 3000 cycles, for UPS, solar and energy storage.

Anchor: KITOZER · KITOZER Products

Contact Us

KITOZER Brand
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP:+86 19068534140
Web: lain.com.cn | gdlain.com