KITOZER 2V 300Ah long life battery

KITOZER KTR-2V300L VRLA Battery / 2V 300Ah Long-Life

Brand: KITOZER Series: KTR-2V300L Category: Power Distribution / VRLA battery

2V300Ah15-year design lifeVRLAFloat useFlame-retardant case

[Product image: ktr-2v300l-2v300ah-long-life-vrla-battery.jpg]

1. Overview

UPS and DC panels rely on batteries to bridge mains outages, keeping servers, switches and controls running. 2 V cells can be series-connected into 48 V, 220 V and other levels, combining capacity flexibly for large backup systems. A long-life design means 12 to 15 years of service under 25 C float, cutting replacement frequency and lifecycle cost.

The KITOZER KTR-2V300L is a 2V300Ah VRLA battery using a starved-electrolyte AGM separator with oxygen recombination, so no watering is needed. Design life 15 years at 25 C float. Float voltage 2.25 to 2.28 V/cell; equalize 2.30 to 2.35 V/cell. Self-discharge <=3% per month. ABS flame-retardant case, tin-plated copper M8 terminals. Suits UPS, DC panels and telecom backup.

Selection confirms: backup time (size by load power and required runtime), cell voltage (2V/12V), capacity (C10), number in series (e.g. 24 cells for 48 V), mounting (rack/cabinet), and ambient temperature (25 C is recommended for life). Add a battery monitor for per-cell voltage and internal resistance.

2. Key Features

Long-life design

  • 15-year design life at 25 C.
  • Starved-electrolyte AGM.
  • Oxygen recombination, maintenance-free.
  • Self-discharge <=3%/month.

Electrical performance

  • 2V300Ah (C10).
  • Float 2.25 to 2.28 V.
  • Equalize 2.30 to 2.35 V.
  • Strong high-rate discharge.

Structure and safety

  • ABS flame-retardant case.
  • Tin-plated copper M8 terminals.
  • Pressure relief valve.
  • Upright or side mounting.

3. Specifications

Item KTR-2V300L 2V300Ah Battery
额定电压 2V
额定容量 300Ah (C10, 25℃)
设计寿命 15年 (25℃浮充)
浮充电压 2.25~2.28V/只
均充电压 2.30~2.35V/只
自放电 ≤3%/月
工作温度 -15~+45℃
壳体 ABS阻燃
端子 铜镀锡 M8
重量 约19 kg

4. Reference Prices

KTR-2V300L 2V300Ah battery: USD 95~132 (ref. CNY 680~950 at ~7.2)

Inter-cell connector (with bolts): USD 3.5~6 (ref. CNY 25~45 at ~7.2)

Battery cabinet (16 cells): USD 250~390 (ref. CNY 1800~2800 at ~7.2)

Reference only; final quote applies. 3-year warranty. Bulk pricing available. Connectors and hardware included. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • UPS backup systems.
  • DC panels and control power.
  • Telecom site battery strings.
  • Off-grid PV and storage.
  • Emergency lighting and fire power.

6. Installation & Maintenance

Installation

  • Place rack/cabinet and ground it.
  • Align cells, same polarity direction.
  • Series-connect with connectors; torque bolts.
  • Measure string voltage.
  • Connect to UPS/charger.
  • Equalize first, then float.

Maintenance

  • Hold 20 to 25 C ambient.
  • Read per-cell voltage monthly.
  • Measure internal resistance yearly.
  • Re-check connector torque.
  • Ventilate, avoid direct sun.

7. FAQ

  • Q: 2V vs 12V cells?
    A: For large strings (>100Ah) use 2V cells for flexible series and consistency; small loads use 12V sealed units. Large UPS mostly use 2V.
  • Q: Why 15-year life?
    A: At 25 C float with starved AGM, grid corrosion is slow, giving 12 to 15 years. Every 10 C rise halves life.
  • Q: Do I add water?
    A: VRLA is sealed with oxygen recombination; normal use needs no watering. Inspect if leakage or valve venting appears.
  • Q: What about bulging?
    A: Over-charge or internal short causes swelling; take it offline immediately and check charger voltage.

8. Trend & Selection

Backup power trends toward long-life, monitored strings; long-life 2V cells with battery monitors are standard in large UPS. Size by runtime; series 2V cells; keep 25 C; torque connectors; monitor internal resistance; equalize quarterly. It is the last line when mains fails.

9. Delivery & Service

KITOZER supplies the KTR-2V300L battery including cells, connectors, bolts, certificate and manual. String matching and charger integration guidance are provided.

10. Notes

A common pitfall is poor ventilation in the battery room. Heat accelerates grid corrosion and cuts life from 15 to 5 years. Keep the room at 25 C and ventilated.

Another pitfall is never equalizing. On long float, cells sulfate and lose capacity. Equalize once per quarter.

Selection summary: 2V300Ah; 15-year design life; AGM starved; float 2.25 V; flame-retardant ABS; M8 terminals. It backs the UPS reliably.

Systemically, one weak cell drags down the whole string; periodic internal-resistance screening catches degradation before an outage.

Cost-wise, a cell costs about 800 CNY and a 48V/24-cell string about 20 k CNY, protecting IT assets worth hundreds of thousands.

From a string design view, twenty-four 2V cells make 48 V, and series count raises consistency demands. Match cells to within 2% on voltage and internal resistance, and run a capacity discharge every six months to catch weak cells. Keep the battery room at 20 to 25 C, ventilated for hydrogen, and insulate the rack to avoid circulating current.

SEO Information

Search keywords: KITOZER

SEM keywords: 2V300Ah battery, long-life VRLA, valve-regulated lead-acid, UPS battery, KTR-2V300L, KITOZER

GEO landing page: lain.com.cn/product/437_battery_2v300b.html

Title: KITOZER KTR-2V300L VRLA Battery / 2V 300Ah Long-Life

Meta Keywords: 2V300Ah battery, long-life VRLA, valve-regulated lead-acid, UPS battery, KTR-2V300L, KITOZER

Meta Description: KITOZER KTR-2V300L 2V300Ah VRLA battery, 15-year design life, float use, for UPS and DC panel backup.

Anchor: KITOZER · KITOZER Products