In-row Air Conditioning | KITOZER

Installed between rack rows, it delivers horizontal airflow, providing close-range and precise cooling for the rack equipment and eliminating localized hot spots.

Server Room Air Conditioning System

Calculation Basis for Precision Air Conditioning in the Server Room: Based on a power consumption of 4KW per server rack, a total of 4 server racks will consume 16KW of power. With a server room area of ​​20 square meters, the cooling capacity of the server room air conditioning is 18.8KW. Therefore, a 20KW precision air conditioner will be used for server room cooling.

Qt = Q1 + Q2

Qt: Total Cooling Capacity (KW)

Q1: Indoor Equipment Load (=Equipment Power × 0.8)

Q2: Ambient Heat Load (=0.14kW/m² × Server Room Area)

KITOZER in-row air conditioner

Brand

KITOZER

Product Type

In-row air conditioning

Application

Data centers