Every Metal Rack Needs a Ground Connection
The rack frame must be bonded to the building’s protective earth (PE) ground. Without it, static electricity, fault current, and EMI have no safe path to earth. A grounding bar provides multiple bonding points inside the rack.

Installation Steps
- Mount the grounding bar (tinned copper, 25x3mm) to the inside of the rack post.
- Connect the bar to the building PE busbar with 6mm² green-yellow cable.
- Bond the PDU chassis to the bar with a short wire.
- Bond the rack frame itself (if the post is painted, scrape a spot for contact).
- Connect shielded cable shields to the bar (if using shielded network cable).
Tools Needed
- 6mm² green-yellow cable.
- M6 ring terminals.
- Crimp tool.
- Screwdriver.
- Multimeter (to verify continuity: bar to PE busbar should read near 0 ohms).