Grounding Bar Installation: Bond the Rack to Earth

Every Metal Rack Needs a Ground Connection

The rack frame must be bonded to the building’s protective earth (PE) ground. Without it, static electricity, fault current, and EMI have no safe path to earth. A grounding bar provides multiple bonding points inside the rack.

KITOZER wall mount server rack cabinet open door

Installation Steps

  1. Mount the grounding bar (tinned copper, 25x3mm) to the inside of the rack post.
  2. Connect the bar to the building PE busbar with 6mm² green-yellow cable.
  3. Bond the PDU chassis to the bar with a short wire.
  4. Bond the rack frame itself (if the post is painted, scrape a spot for contact).
  5. Connect shielded cable shields to the bar (if using shielded network cable).

Tools Needed

  • 6mm² green-yellow cable.
  • M6 ring terminals.
  • Crimp tool.
  • Screwdriver.
  • Multimeter (to verify continuity: bar to PE busbar should read near 0 ohms).