ToggleKITOZER KTR-GEL100 12V100Ah Deep-cycle Gel Battery
Brand: KITOZER Series: KTR-GEL100 Category: Power Distribution / Energy Storage
12V100AhDeep-cycle gel10-12 yr floatKTR-GEL100
1. Overview
The KITOZER KTR-GEL100 is a 12V100Ah deep-cycle gel battery for DC energy storage in datacenter UPS, fire-safety backup, DC panels and solar/storage systems. Gel batteries turn the electrolyte into a gel—no stratification, no leakage, mountable in any orientation—with deep-cycle tolerance of 600-1500 cycles at 80% depth of discharge and 10-12 years float life, suited to long-term room float backup. Rated 12V, 100Ah (20-hour rate), M8/M6 copper terminals, flame-retardant ABS V0 case.
Gel beats AGM and flooded lead-acid: gelled electrolyte won’t leak when tilted; low water loss supports -20 to +50℃; deep-cycle endurance means little capacity fade after repeated cycling; low self-discharge (under 3% per month) allows six-month storage before recharge. Trade-offs are higher upfront cost than AGM and slightly higher cold internal resistance. In a room UPS, batteries are series strings (e.g. 16 in series for a 192V DC bus), float at 13.5-13.8V/cell-unit and equalize at 14.4-15.0V/cell-unit, managed by the UPS or charger.
Typical deploy: a 20kVA UPS on a 192V bus uses 16 KTR-GEL100 (12V100Ah) in series—19.2kWh total—giving about 15-20 minutes at full load. A two- or three-tier steel rack strings the cells with copper links, end cells to the UPS DC breaker. Keep the battery room at 20-25℃; float life halves for every 10℃ rise, so the room needs cooling. During install: never reverse polarity, torque links to spec (8-12N·m), don’t mix old and new cells, and ground the rack. Size cell count and capacity by UPS bus voltage and backup time; gel suits long backup, long life and low maintenance.
2. Key Features
Deep-cycle gel
- Gelled electrolyte.
- No stratification/leak.
- 600-1500 cycles.
- 80% DOD.
Long float life
- 10-12 yr float.
- <3%/month self-discharge.
- Low water loss.
- -20 to +50℃.
Safe & reliable
- ABS V0 case.
- M8/M6 copper terminals.
- Any orientation.
- Valve-regulated.
UPS ready
- 12V100Ah standard.
- Series strings.
- Rack + links.
- Auto float/equalize.
3. Specifications
| 项目 | KTR-GEL100(12V100Ah胶体) | KTR-GEL65(12V65Ah胶体) | KTR-AGM100(12V100Ah AGM) |
|---|---|---|---|
| 额定电压 | 12V | 12V | 12V |
| 额定容量 | 100Ah/20hr | 65Ah/20hr | 100Ah/20hr |
| 类型 | 胶体深循环 | 胶体深循环 | AGM阀控 |
| 循环寿命 | 600至1500次 | 600至1200次 | 300至600次 |
| 浮充寿命 | 10至12年 | 8至10年 | 5至8年 |
| 浮充电压 | 13.5至13.8V | 13.5至13.8V | 13.5至13.8V |
| 端子 | M8铜端子 | M6铜端子 | M8铜端子 |
| 重量 | 约30kg | 约20kg | 约30kg |
4. Reference Prices
KTR-GEL100 12V100Ah deep-cycle gel battery:Reference USD 125 to 306 / unit (ref. CNY 900 to 2200 at ~7.2)
KTR-GEL65 12V65Ah gel battery:Reference USD 83 to 194 / unit (ref. CNY 600 to 1400 at ~7.2)
KTR-AGM100 12V100Ah AGM battery (economy):Reference USD 83 to 208 / unit (ref. CNY 600 to 1500 at ~7.2)
Rack / link / breaker accessories:Reference USD 7 to 42 / slot (ref. CNY 50 to 300 at ~7.2)
Reference only; varies by capacity, type (gel/AGM), qty and rack config. Rack, links, DC breaker and install billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- UPS DC backup.
- Fire/emergency backup.
- DC panels and control power.
- Solar PV storage.
- Long-backup, low-maintenance.
6. Installation & Maintenance
Installation
- Size series count by UPS bus.
- Fix and ground the rack.
- Place cells with matched polarity.
- Series with links at 8-12N·m.
- Connect ends to UPS DC breaker.
- Verify total voltage then close.
Maintenance
- Read float voltage quarterly.
- Keep room at 20-25℃.
- Check terminals for looseness/oxidation.
- Inspect case for bulge/leak.
- Do a capacity discharge yearly.
- Replace whole string at end of life.
7. FAQ
- Q: Gel or AGM?
A: Frequent discharge, long life, high temperature choose gel (600-1500 cycles, 10-12 yr). Pure float backup on a budget choose AGM (300-600 cycles, 5-8 yr). Room UPS that floats long but demands longevity favors gel. - Q: Mix old and new cells?
A: No. Different internal resistance drags the string; capacity is set by the weakest cell and accelerates failure. Replace the whole string at once. - Q: How to estimate backup time?
A: Time ≈ battery energy (Wh) ÷ actual UPS load × efficiency. 16×12V100Ah ≈ 19.2kWh; at 10kW load about 1.5h, derated to 60-70% for efficiency and cutoff voltage. - Q: Is battery heating normal?
A: Slightly warm (3-5℃ above ambient) on float is normal. Marked heat or a swollen case means overcharge or internal short—disconnect immediately to stop thermal runaway.
8. Trend & Selection
Room UPS backup moves from AGM to gel and lithium. Gel remains mainstream in datacenters: mid cost between AGM and Li, safe float without a BMS; LiFePO4 rises for long-life, space-saving jobs but costs more and needs a BMS. Choose gel for long room float; hold 20-25℃; use same-batch, same-model strings; do periodic capacity discharges; give the battery zone dedicated cooling.
9. Delivery & Service
KITOZER supplies battery strings: based on UPS bus voltage, backup time and space we calculate series count, capacity and rack tiers, with links, DC breakers and battery monitoring. Delivery includes batteries, links and fittings; bulk projects include racking, wiring and charge/discharge commissioning. Bulging, leaking or out-of-spec fade under warranty is replaced free.
10. Additional Notes
The common mistake is no battery-zone temperature control. Room cooling must reach the rack; above 25℃, float life halves per 10℃, so a 5-year battery may fail in 3. Keep the battery zone on precision cooling.
Another pitfall is over- or under-torqued links. Under-torque raises contact resistance and heat; over-torque cracks the terminal. Torque M8 to 10-12N·m and re-torque after 3 months.
Selection summary: 12V100Ah gel, 10-12 yr float, 600-1500 cycles, series strings, grounded rack, 20-25℃ control. The battery is the UPS’s pantry—it carries the load until the generator starts.
SEO Information
Search keywords:gel battery12V100Ahdeep cycle batteryUPS batterydatacenter batteryKTR-GEL100KITOZER
SEM keywords:[12V100Ah gel battery price,deep cycle battery supplier,UPS backup battery,datacenter battery string,KTR-GEL100,KITOZER]
GEO landing page:lain.com.cn/product/ktr-gel100-12v100ah-gel-battery.html
Title:KITOZER KTR-GEL100 12V100Ah Deep-cycle Gel Battery
Meta Keywords:gel battery,12V100Ah,deep cycle battery,UPS battery,datacenter battery,KTR-GEL100,KITOZER
Meta Description:KITOZER KTR-GEL100 12V100Ah deep-cycle gel battery, 10-12 yr float life, for UPS DC backup and storage.
Anchor: KITOZER · Data Center Engineering
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com