1. Overview

The KITOZER KTR-BAT200 is a 12V 200Ah valve-regulated lead-acid (VRLA) battery using AGM absorbed-glass-mat technology: electrolyte is held in the mat, non-spilling and maintenance-free, a deep-cycle battery. It is the storage heart of UPS, telecom sites, datacenter DC panels and solar storage—float-charged on standby while mains is normal, and instantly discharging to UPS/DC loads when mains fails, carrying servers and network gear to generator start or safe shutdown. Each unit is rated 12V, 200Ah (20-hour rate, i.e. 10A down to 10.5V), with a design float life of ~10-12 years at 25°C and far deeper cycle tolerance than a starting battery.

Deep-cycle differs from starting batteries in plate thickness. KTR-BAT200 uses thick plates that survive repeated deep discharge (to 50% or even 80% depth) without rapid sulfation, suiting periodic charge/discharge in UPS and storage; a car starting battery uses thin plates for a single burst and fails quickly under repeated deep discharge. The AGM design recombines gases internally with minimal water loss—no topping up. The flame-retardant ABS case has a pressure relief vent for overcharge; copper-cored M8/M10 terminals come with intercell links and torque specs, and units string together into 48V, 192V or 240V banks.

Typical deploy: a 40kVA UPS with a 192V DC bus needs 16 KTR-BAT200 units (16×12V=192V) in series on a dedicated rack or cabinet; the cabinet carries a temperature-compensation probe, links are torqued to spec, and cells are series-connected positive-to-negative. Size the bank by backup time—about one 200Ah group for 30 minutes of backup. Select 12V 200Ah, compute series count from the UPS DC voltage, size capacity/parallel strings by backup time, and choose a battery cabinet or rack by space, with a battery breaker and insulated covers.

2. Key Features

12V 200Ah deep-cycle

  • 12V 200Ah (20h).
  • Thick plates.
  • Deep cycle tolerant.
  • 10-12yr float at 25℃.

AGM maintenance-free

  • AGM mat.
  • Non-spilling.
  • Internal recombination.
  • No topping up.

Safe & reliable

  • Flame-retardant ABS.
  • Pressure relief vent.
  • Copper terminals.
  • Overcharge venting.

Flexible strings

  • M8/M10 terminals.
  • Links included.
  • String 48/192/240V.
  • Temp-comp probe.

3. Specifications

项目 KTR-BAT200(12V200Ah) KTR-BAT100(12V100Ah) KTR-BAT12V100(起动型)
额定电压 12V 12V 12V
额定容量(20h) 200Ah 100Ah 100Ah
设计寿命(25℃) 10至12年 8至10年 3至5年
极板 厚板深循环 厚板深循环 薄板起动
自放电 ≤3%/月 ≤3%/月 ≤5%/月
工作温度 -15至+50℃ -15至+50℃ -15至+50℃
端子 铜芯M8/M10 铜芯M8 铅铜M6
重量 约62kg 约30kg 约30kg

4. Reference Prices

KTR-BAT200 12V200Ah AGM deep-cycle battery:Reference USD 167 to 306 / unit (ref. CNY 1200 to 2200 at ~7.2)

KTR-BAT100 12V100Ah AGM deep-cycle battery:Reference USD 83 to 153 / unit (ref. CNY 600 to 1100 at ~7.2)

Battery cabinet / rack / links:Reference USD 28 to 278 / set (ref. CNY 200 to 2000 at ~7.2)

Temp-comp probe / battery breaker:Reference USD 7 to 42 / pc (ref. CNY 50 to 300 at ~7.2)

Reference only; varies by capacity, qty, links, cabinet and shipping. Installation, charge/discharge testing and old-battery recycling billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • UPS backup power.
  • Datacenter DC panels.
  • Telecom storage.
  • Solar PV storage.
  • Safe-shutdown backup.

6. Installation & Maintenance

Installation

  • Compute series count from UPS DC voltage.
  • Arrange neatly on the rack.
  • Series positive-to-negative.
  • Torque links to spec.
  • Stick temp probe to case.
  • Connect breaker then UPS.

Maintenance

  • Measure voltage/ESR monthly.
  • Keep 20-25℃ ambient.
  • Re-torque links.
  • Clean/protect terminals.
  • Log discharge capacity.
  • Replace swollen/leaking cells.

7. FAQ

  • Q: How long will 12V200Ah last?
    A: It depends on load. DC discharge current = load power / DC bus / efficiency. Roughly, a 40kVA UPS at full load draws ~200A at 192V, so one 200Ah group lasts ~0.5-1h; lighter loads last longer.
  • Q: Does heat extend battery life?
    A: No. Every 10℃ rise halves float life. Keep batteries at 20-25℃; heat shortens life and accelerates water loss.
  • Q: Can a deeply discharged battery recover?
    A: AGM deep-cycles tolerate occasional deep discharge, but repeated discharge below cutoff causes sulfation and capacity loss. Switch to generator or shut down on low-battery alarm to avoid over-discharge.
  • Q: Can I mix old and new batteries?
    A: No. Mixed capacities/ages in series act as a weak link—the whole bank is limited by the worst cell. Replace as a matched set from one batch.

8. Trend & Selection

Datacenters move toward lithium, but AGM deep-cycle remains the UPS mainstream for safety, cost and maturity. Compute series count from the UPS DC bus, size capacity/parallel strings by backup time, ventilate the cabinet, use a temp-comp probe, torque links, and test ESR/capacity periodically. The battery is the UPS’s pantry—right sizing and care keep it alive during outage.

9. Delivery & Service

KITOZER supplies storage packages: based on UPS model, DC voltage and backup time we recommend series count, capacity plus cabinet, links and temp probes, bundled with the UPS. Delivery includes battery, links, terminal covers and manual; bulk projects include install guidance and a first charge/discharge test. Low capacity or swollen/leaking cells under warranty are replaced free.

10. Additional Notes

The common mistake is under- or over-torquing links. Under-torque causes heating and arcing; over-torque cracks terminals. Use a torque wrench to spec (M8 ~9-12N·m) and apply anti-corrosion grease.

Another pitfall is an unvented, hot battery cabinet. Overcharge gases and heat accelerate water loss. Leave ventilation gaps, air-condition the room, and let the temp-comp probe correct float voltage.

Selection summary: 12V200Ah AGM deep-cycle, thick plates, 10-12yr float life, M8/M10 terminals in series strings, 20-25℃ ambient, periodic ESR/capacity tests. The KTR-BAT200 is the UPS pantry when the power goes out.

SEO Information

Search keywords:lead-acid battery12V200Ah batterydeep-cycle batteryAGM batteryUPS batteryKTR-BAT200KITOZER

SEM keywords:[12V200Ah battery price,deep-cycle battery supplier,AGM battery price,UPS battery,KTR-BAT200,KITOZER]

GEO landing page:lain.com.cn/product/ktr-bat200-12v200ah-agm-deep-cycle-battery.html

Title:KITOZER KTR-BAT200 12V200Ah AGM Deep-cycle Battery

Meta Keywords:lead-acid battery,12V200Ah battery,deep-cycle battery,AGM battery,UPS battery,KTR-BAT200,KITOZER

Meta Description:KITOZER KTR-BAT200 12V200Ah VRLA AGM deep-cycle battery, 10-12yr float life, for UPS backup storage.

Anchor: KITOZER · Power Distribution

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart