ToggleKITOZER KTR-2V500G Battery / 2V 500Ah Gel Battery
Brand: KITOZER Series: KTR-2V500G Category: Power Distribution / Battery bank
2V 500AhGel electrolyte15-year design lifeDeep cycleVRLA sealed
1. Overview
UPS and DC bus systems rely on battery banks for backup during mains failure. Batteries are the last line of defense; their capacity and lifetime directly determine how long a data center survives an outage. 2 V cells are the mainstream for medium-to-large UPS and telecom power because they offer low voltage, high capacity and flexible series/parallel strings. Gel batteries, with gelled electrolyte, are leak-proof, low self-discharge and deep-cycle friendly, and are widely used in long-backup rooms.
The KITOZER KTR-2V500G is a 2 V 500 Ah VRLA gel battery. Positive plates are pasted, negative grids are lead-calcium alloy, and electrolyte is silica gel. Internal pressure is regulated by a valve-controlled safety vent. Float design life is 15 years at 25 C; deep-cycle count is >=1200 at 50% DOD; self-discharge <=3% per month. Cell size is about 240x170x230 mm and weight about 31 kg. Cells can be series-connected into 48 V or 220 V banks for UPS, DC panels and solar storage.
Selection confirms: cell voltage (2 V), capacity (500 Ah), backup time (minutes/hours), string redundancy (N+1), rack/cabinet size, and ambient temperature (ideal 20-25 C). For example, a 100 kVA UPS with 30-minute backup needs about 40 series-connected 2 V 500 Ah cells to form a 480 V bank. Install in a dedicated battery room or cabinet, well ventilated, away from direct sun; perform a capacity discharge test annually.
2. Key Features
Gel electrolyte
- Silica gel, leak-proof.
- Self-discharge <=3%/month.
- >=1200 cycles at 50% DOD.
- VRLA starved-electrolyte, mountable any way.
Long-life design
- Lead-calcium grids, corrosion-resistant.
- 15-year float life at 25 C.
- Valve-regulated vent.
- High vent pressure, explosion-safe.
Structure
- Flame-retardant ABS case.
- Copper terminals.
- Size ~240x170x230 mm.
- Stackable on racks.
3. Specifications
| Item | Specification |
|---|---|
| Nominal voltage | 2 V |
| Rated capacity (C10) | 500 Ah |
| Float design life | 15 years at 25 C |
| Deep cycles | >=1200 at 50% DOD |
| Self-discharge | <=3% / month |
| Equalize voltage | 2.30 to 2.35 V/cell |
| Float voltage | 2.25 to 2.27 V/cell |
| Operating temp | -15 to 50 C (best 20-25 C) |
| Dimensions | ~240x170x230 mm |
| Weight | ~31 kg |
4. Reference Prices
KTR-2V500G 2V500Ah gel battery (each): USD 125~180 (ref. CNY 900~1300 at ~7.2)
Inter-cell connector (spare): USD 4~8 (ref. CNY 30~60 at ~7.2)
Battery cabinet (with terminals): USD 210~485 (ref. CNY 1500~3500 at ~7.2)
Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Medium/large UPS backup.
- Telecom -48 V DC panels.
- Data center VRLA banks.
- Off-grid solar and storage.
- Emergency lighting and fire power.
6. Installation & Maintenance
Installation
- Keep battery room at 20-25 C.
- Level and ground the rack.
- Arrange cells by number with correct polarity.
- Tighten connectors diagonally to torque.
- Connect the main +/- to the UPS last.
- Equalize charge for 24-48 h after install.
Maintenance
- Measure cell voltage monthly.
- Capacity discharge test annually.
- Apply petroleum jelly on terminals yearly.
- Life halves for every 10 C rise.
- Dispose of dead batteries as hazardous waste.
7. FAQ
- Q: Gel vs AGM?
A: Gel has gelled electrolyte, better deep-cycle and lower self-discharge, slightly higher cost. AGM absorbs electrolyte in glass mat, better high-current discharge. Long backup favors gel; short high-current favors AGM. - Q: Why series of 40+ cells?
A: UPS DC bus is 384 V or 480 V; with 2 V cells, you need many in series. 480 V needs about 240 cells. - Q: How long do they last?
A: 15-year float design at 25 C; real rooms at 30+ C see 8-12 years; rely on capacity tests. - Q: Do new batteries need initial charge?
A: Yes. Ships charged, but loses ~5% in transit; equalize 24-48 h before service.
8. Trend & Selection
Data center batteries are moving toward longer life, smart monitoring and lithium, but gel VRLA will remain mainstream for 5+ years thanks to maturity, low cost and recycling. Size capacity by load x time; keep under 25 C; add string redundancy; test annually.
9. Delivery & Service
KITOZER ships the KTR-2V500G charged, with test report, certificate and manual; bulk orders include racks and connectors.
10. Notes
A common mistake is a hot battery room. Life halves every 10 C, so air-conditioning or placing batteries near cold aisles matters.
Another pitfall is under-torqued connectors. Loose links overheat during high-current discharge and can melt; torque diagonally.
Selection summary: 2V500Ah; gel; 15-year float; 1200 deep cycles; 3%/month self-discharge. It is the core storage of UPS backup.
Systemically, one weak cell drags down the whole string; monthly cell-voltageInspection is essential.
Cost-wise, a 480 V bank costs about 100k CNY; a failure can drop the whole room, so selection and maintenance cannot be skimped.
From a battery-management standpoint, add a BMS cell-monitoring module to track per-cell voltage and temperature in real time, alerting on weak cells before they drag down the string. The BMS connects to the DCIM over RS485.