KITOZER
KITOZER

KITOZER Outdoor UPS Cabinet 10 kVA 2 Hour Backup

The KITOZER 10 kVA outdoor UPS cabinet delivers wall-to-wall conditioned power in a single weatherproof enclosure for remote infrastructure that lacks a dedicated equipment room. Combining online double-conversion UPS power electronics, a sealed battery bay, and a thermally controlled cabinet, it protects telecom, traffic, surveillance, and instrumentation loads against grid outages, sags, surges, and wide voltage fluctuations. The cabinet is engineered for unattended outdoor service with remote monitoring and automatic battery management. Compared with renting a small shed and installing an indoor UPS, the KITOZER cabinet removes climate control risk and arrives pre-commissioned, cutting site launch time by more than half.

Product Overview

The cabinet is built around a 10 kVA double-conversion UPS module mounted in the upper equipment bay, with a lower battery bay supporting VRLA or lithium iron phosphate strings. A fire-rated steel partition separates power electronics from batteries, and the battery bay includes thermal runaway ventilation ducted to the exterior. The front service door and rear cable entry door are independently locked, and the plinth base provides cable routing and forklift access. The unit arrives factory-tested, charged to storage state, and ready for site connection. A touchscreen HMI on the front door displays load, battery state, and alarms, and an optional 4G modem transmits all events to a central NOC.

Technical Specifications

Ingress protection IP55. Enclosure material 1.5mm galvanized steel with outdoor polyester powder coat, optional 304 or 316 stainless. UPS rating 10 kVA / 9 kW online double conversion, single phase or three phase versions, input 120 to 275 VAC, output 220 VAC plus or minus 1 percent, efficiency up to 94 percent, power factor 0.9 output. Battery bay supports up to 32 x 12V 100Ah VRLA or equivalent 48V lithium pack, providing 2 hour backup at full load. Thermal: 1000W outdoor air conditioner with redundant fan, 150W PTC heater, condensate evaporator tray. Monitoring: LCD HMI, SNMP, Modbus TCP, dry contacts, optional 4G. Dimensions 800mm W by 800mm D by 1800mm H. Operating range minus 30 degrees Celsius to plus 55 degrees Celsius. KITOZER 3 year UPS warranty, 5 year enclosure warranty.

Applications

The cabinet supports 5G small cell power, intelligent traffic intersection controllers, railway level crossing signals, outdoor edge computing PoE nodes, water pipeline remote pump controls, solar farm SCADA power, broadcasting remote transceivers, and coastal microwave sites. It also serves disaster recovery mobile command power, outdoor broadcast equipment, and temporary event infrastructure where a UPS room is not available. Operators commonly install one cabinet per remote site, linking multiple sites into a centralized monitoring dashboard for fleet management.

Advantages and Features

Integrated UPS and shelter eliminate on-site integration risk. Air-conditioned battery bay extends battery life by holding 20 to 25 degrees Celsius year round. The online double-conversion topology cleans up poor grid quality common at remote sites. Wide input window reduces battery cycling and extends service intervals. Remote SNMP and 4G monitoring allow energy managers to track runtime, battery health, and cabinet temperature from a central NOC. The modular UPS design supports hot-swappable power modules for future expansion. The cabinet also supports generator compatibility with programmable transfer logic, preventing nuisance battery discharge during generator start-up.

Installation and Maintenance Recommendations

Install on a level concrete plinth with 100mm freeboard above flood level. Connect neutral and earth separately and verify earth resistance below 5 ohms. Commission input breaker, then UPS, then output loads. During the first month, record battery float voltage and internal resistance weekly, then monthly thereafter. Test battery runtime annually under 50 percent load. Clean air conditioner condenser and filter every six months, inspect door gaskets annually, and replace batteries at end of design life or earlier if capacity drops below 80 percent. Keep condensate drain clear and verify heater function before cold seasons. Retain a spare AC fan and UPS module locally for fast repair.

Customization and Quality

KITOZER offers lithium upgrade, longer runtime, parallel redundant UPS, 4G remote, and 316L stainless options. Every cabinet passes a factory load bank test, battery charge cycle, and thermal soak before shipment. Units ship with wiring diagrams, commissioning manual, and test certificate. Project customers receive dedicated power study support including load schedule and runtime calculation.

Working Principle and Design Detail

The cabinet operates as a sealed thermal and electrical island: incoming AC power passes through the input breaker and surge arrester before reaching the internal distribution bus, while the climate controller continuously compares internal air temperature against the setpoint and switches fans or compressor on demand. The door gasket is compressed by multi-point latches to maintain the rated ingress protection across the full door perimeter, and all cable entries use rated glands so that no unsealed opening remains. Internal cable managers route power, signal, and fiber cables on separate paths to prevent electromagnetic interference and simplify tracing during maintenance. The grounding busbar bonds the cabinet frame, internal equipment chassis, and external surge protection to a single equipotential network, reducing touch voltage risk during fault conditions. This structured design ensures that every field-installed connection remains serviceable for the full service life of the enclosure.

Quality and Certification

Every enclosure is manufactured under a documented quality system that includes incoming material inspection, in-process welding and coating checks, and a final factory acceptance test before shipment. Test records cover insulation resistance, continuity, ingress protection verification, and thermal function. Standard certifications include CE marking where applicable, and the enclosure is constructed from materials that comply with RoHS directives. The cabinet is packaged in foam-lined seaworthy crates suitable for long-haul ocean freight, with desiccant bags to prevent transit condensation. KITOZER supports long-term spare parts availability and offers extended warranty options for mission-critical deployments.

Price

From $4,800 per unit excluding batteries. Contact KITOZER for lithium upgrade, runtime configuration, and project lead time.

Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com

Scroll to Top