Bad Grounding Is Worse Than No Grounding
A bad ground creates ground loops, static buildup, and unsafe fault paths. Here are the most common mistakes and how to fix them.

Mistake 1: No Ground Wire at All
The rack sits on casters (insulated by rubber). There’s no metal path to earth. Fix: run a 6mm² green-yellow cable from the rack grounding bar to the building PE busbar.
Mistake 2: Grounding Through a Power Cord
“The PDU is plugged in, so the rack is grounded.” Wrong. The PDU chassis isn’t bonded to the rack frame. Fix: bond the PDU chassis to the rack grounding bar.
Mistake 3: Daisy-Chaining Grounds
“Rack A grounds to Rack B, Rack B to ground.” If the link breaks, Rack A floats. Fix: every rack has its own ground wire to the PE busbar.
Mistake 4: Loose Ground Connection
A hand-tightened lug vibrates loose. Fix: torque to 1.2 Nm, add a lock washer, re-check quarterly.