
Table of Contents
12V200Ah Explosion-Proof Battery Containerized Energy Storage System
Technical Design Proposal
Proposal No.: LAIN-CN-BAT-20260802
Design Organization: Guangzhou Lain Intelligent System Development Co., Ltd.
Brand: KITOZER
Date: August 2026
—
Table of Contents
Chapter 1 Company Profile
1.1 Corporate Development History
1.2 Core Business and Product Portfolio
1.3 Brand, Qualifications and Honors
1.4 Core Competitive Advantages
1.5 Production and R&D Capabilities
Chapter 2 Project Overview
2.1 Project Background and Construction Significance
2.2 Project Construction Objectives
2.3 Applicable Project Scenarios
2.4 Basis for Proposal Preparation
2.5 Overall Project Scale and Core Specifications
Chapter 3 User Requirements Analysis
3.1 Energy Storage Capacity and Performance Requirements
3.2 Integration and Rapid Deployment Requirements
3.3 Safety, Explosion-Proof and Protection Rating Requirements
3.4 Monitoring and Intelligent O&M Requirements
3.5 Complex Environment Adaptability Requirements
3.6 Construction and Delivery Timeline Requirements
3.7 After-Sales Service and Technical Training Requirements
Chapter 4 Overall Design Description
4.1 Overall Design Principles
4.2 System Architecture Design
4.3 Container Internal Layout Design
4.4 Electrical System Overall Design
4.5 Explosion-Proof Safety System Design
4.6 Ventilation and Heat Dissipation System Design
4.7 Lightning Protection and Grounding System Design
4.8 Electromagnetic Compatibility Design
4.9 Ergonomics and O&M Convenience Design
Chapter 5 System Quotation and Configuration List
5.1 Battery Core Units
5.2 Battery Mounting Rack Units
5.3 DC Busbar Distribution Units
5.4 BMS Energy Storage Master Control Units
5.5 Electrical Connections and Wiring Accessories
5.6 Container Shell and Structural Units
5.7 Safety, Explosion-Proof and Fire Suppression Systems
5.8 Lighting and Emergency Systems
5.9 Grounding and Lightning Protection Units
5.10 Installation, Commissioning and Technical Services
Chapter 6 Detailed Technical Parameters of Each System Product
6.1 Valve-Regulated Sealed Lead-Acid Battery Technical Parameters
6.2 Battery-Specific Mounting Rack Technical Parameters
6.3 Battery Cluster DC Combiner Box Technical Parameters
6.4 BMS Integrated Energy Storage Master Control Cabinet Parameters
6.5 Energy Storage Container Cabinet Technical Parameters
6.6 Safety, Explosion-Proof and Fire Suppression System Equipment Parameters
6.7 Electrical Connection and Wiring Accessory Parameters
6.8 Lighting and Emergency System Equipment Parameters
Chapter 7 Core Advantages of the Proposal
7.1 Highly Integrated Turnkey Delivery Advantage
7.2 Multi-Layer Explosion-Proof Safety System Advantage
7.3 High-Precision Battery Management Advantage
7.4 All-Scenario Environmental Adaptability Advantage
7.5 Intelligent Unattended O&M Advantage
7.6 Modular Flexible Expansion Advantage
7.7 Full Lifecycle Cost Advantage
7.8 Customization Adaptability Advantage
Chapter 8 Technical Q&A
8.1 Battery System Technical Q&A
8.2 Container Shell Technical Q&A
8.3 Safety, Explosion-Proof and Fire Protection Q&A
8.4 BMS Monitoring System Technical Q&A
8.5 Installation and Construction Technical Q&A
8.6 O&M and Maintenance Technical Q&A
8.7 General Commercial Technical Q&A
Chapter 9 Construction Schedule Plan
9.1 Overall Project Timeline Planning
9.2 Detailed Construction Schedule Milestone Table
9.3 Key Milestone Descriptions
9.4 Schedule Assurance Measures
9.5 Delay Emergency Response Plan
Chapter 10 Construction Organization Plan
10.1 Construction Organization Structure and Responsibilities
10.2 Pre-Construction Preparation Work
10.3 Construction Process Flow for Major Sub-Projects
10.4 Construction Quality Control System
10.5 Construction Safety Management System
10.6 Civilized Construction and Environmental Protection Measures
10.7 Construction Acceptance Standards and Procedures
Chapter 11 After-Sales Service System
11.1 Warranty Service Commitment
11.2 Fault Response and Handling Mechanism
11.3 Regular Inspection and Maintenance Services
11.4 Spare Parts Supply Services
11.5 Post-Warranty Value-Added Services
11.6 Technical Support and Upgrade Services
Chapter 12 System Operation and O&M Training Plan
12.1 Training Objectives and Principles
12.2 Training Targets and Classification
12.3 Training Content System
12.4 Training Methods and Scheduling
12.5 Training Assessment and Certification
12.6 Training Material Delivery
Chapter 13 Typical Engineering Case Studies
13.1 Industrial Park Backup Power Energy Storage Container Project
13.2 Telecom Base Station Outdoor Energy Storage Container Project
13.3 Commercial Building Peak-Valley Arbitrage Energy Storage Container Project
13.4 Factory Microgrid Supporting Energy Storage Container Project
Chapter 14 SEO Optimization System and Keyword Layout
14.1 Core Keyword System
14.2 Page Optimization Tag Configuration
14.3 Internal Link Anchor Text Layout
14.4 Company Contact Information
Chapter 15 Website Backend Configuration Information
15.1 General Publishing Settings
15.2 Advanced Attribute Settings
15.3 Search Optimization Settings
15.4 Custom URL Options
—
Chapter 1: Company Profile
1.1 Corporate Development History
Guangzhou Lain Intelligent System Development Co., Ltd. was established in 2002, and is one of the early high-tech enterprises in China specializing in computer room engineering, intelligent enclosures, and environmental monitoring. In the early stages of development, the company focused on computer room renovation, power distribution, and monitoring system integration as its core business, providing traditional computer room construction services to government and enterprise clients in the Pearl River Delta region. As industry technology evolved and market demand upgraded, the company progressively expanded its business into integrated cabinets, micro-module cold aisle systems, shielded computer rooms, outdoor cabinets, containerized computer rooms, and other specialized segments, forming a full-industry-chain service capability spanning design, R&D, production, installation, and O&M.
Over more than two decades of deep industry involvement, the company has consistently adhered to the development philosophy of “Technology-Driven, Quality First”, continuously increasing R&D investment and launching new products and solutions that meet market demand. From traditional computer room engineering to modular data centers, from indoor cabinets to outdoor containerized integrated systems, the company’s product matrix has continued to expand, with service scenarios extending from government and enterprise computer rooms to industrial, telecommunications, energy, transportation, and other industries. To date, the company has completed over a thousand computer room and energy storage integration projects, accumulating rich project implementation experience and technical expertise.
1.2 Core Business and Product Portfolio
The company’s core business revolves around two major segments — “Computer Room Infrastructure + Intelligent Integrated Systems” — forming four major product portfolios:
Computer Room Engineering Systems: Covering IDC data center construction, shielded computer room engineering, computer room renovation, computer room power distribution and HVAC systems, and environment monitoring systems for computer rooms, providing integrated turnkey contracting services from solution design through construction delivery.
Intelligent Cabinet Systems: Including integrated data cabinets, micro-module cold aisle cabinets, intelligent shielded cabinets, outdoor weatherproof cabinets, console desks, and video walls, supporting customized dimensions, functions, and appearance on demand.
Containerized Integrated Systems: Including containerized data rooms, containerized energy storage systems, containerized equipment cabins, and explosion-proof containers, delivering factory-prefabricated solutions for rapid on-site deployment.
Environmental Monitoring and Control Systems: Covering temperature/humidity, water leakage, smoke, access control, video surveillance, power distribution, battery monitoring, and other environment monitoring products, as well as BMS battery management systems and energy storage control systems.
1.3 Brand, Qualifications and Honors
The company owns the proprietary brand KITOZER (开拓者), positioned in the mid-to-high-end computer room infrastructure and intelligent integrated equipment market. Backed by stable product quality and comprehensive service, the brand has earned a high degree of recognition and reputation within the industry.
In terms of qualifications and certifications, the company has passed:
- ISO9001 Quality Management System Certification
- ISO14001 Environmental Management System Certification
- OHSAS18001 Occupational Health and Safety Management System Certification
The company also holds multiple utility model patents, design patents, and software copyrights; has received High-Tech Enterprise certification; and products have passed CCC certification, explosion-proof certification, IP protection rating certification, and other authoritative testing.
1.4 Core Competitive Advantages
1.4.1 Rapid Response and Delivery
As a manufacturer, the company owns an in-house sheet metal fabrication plant and integration assembly workshop, with core cabinets and structural components produced in-house, significantly shortening production lead times. Standard products can be stocked for rapid dispatch, while customized products can be quickly designed and prototyped to ensure project delivery timelines. Additionally, the company has a professional construction and technical service team capable of rapidly responding to on-site installation and commissioning needs nationwide and for overseas projects.
1.4.2 Strict Quality Control
The company has established a full-process quality control system. From raw material procurement, production and processing, finished product inspection, to on-site installation, every stage has clear quality standards and inspection procedures. Core components are sourced from reputable industry brands. Finished products undergo power-on testing, performance testing, protection testing, and multiple other inspection steps before leaving the factory. Third-party testing organizations conduct periodic sampling inspections to ensure stable and reliable product quality.
1.4.3 Custom Design Capability
The company has a professional structural design and electrical design team capable of providing one-on-one customized solution design based on customer usage scenarios, capacity requirements, installation environment, and functional requirements. From dimensional layout and electrical configuration to functional modules and appearance color schemes, all elements can be flexibly adjusted. Multiple design proposals are provided free of charge for customer selection, achieving a high degree of alignment with individual customer requirements.
1.4.4 Full-Cycle Premium After-Sales Service
The company provides a 7×24 hour technical service hotline, with professional customer service staff and technical engineers responding online to customer inquiries and fault reports. A dedicated personnel follow-up after-sales mechanism ensures service quality is tracked throughout the project delivery, warranty period, and post-warranty period. In addition to fault repair, the company provides regular inspections, maintenance guidance, system upgrades, technical training, and other value-added services to ensure long-term stable system operation.
1.5 Production and R&D Capabilities
The company’s production base is located in Panyu, Guangzhou, featuring standardized factory buildings and multiple sheet metal processing production lines, equipped with CNC punching machines, laser cutting machines, CNC bending machines, powder coating lines, and other advanced production equipment, with an annual production capacity of over a thousand cabinets and dozens of containerized integrated systems.
The R&D team consists of engineers from multiple disciplines including mechanical structure, electrical automation, and software development, dedicated to product structure optimization, performance enhancement, and intelligent function development, continuously driving product iteration and technological innovation.
The company has established a dedicated testing laboratory capable of performing protection rating tests, electrical performance tests, thermal cycle tests, vibration tests, and other inspections, ensuring factory-delivered products comply with design standards and industry specifications. Additionally, the company maintains technical cooperation with multiple universities and research institutes, continuously absorbing cutting-edge industry technology to maintain the technical advancement of its products and solutions.
—
Chapter 2: Project Overview
2.1 Project Background and Construction Significance
Against the backdrop of dual carbon goals and the construction of new power systems, energy storage technology — as the core technology for enhancing power system flexibility and ensuring power supply reliability — continues to expand its application scenarios. For industrial enterprises, telecommunication base stations, commercial buildings, and other end users, demands for backup power assurance, peak-valley electricity price arbitrage, and microgrid renewable energy integration are growing steadily.
Traditional battery room construction requires multi-disciplinary coordination including civil works, interior finishing, power distribution, and fire protection, resulting in long construction cycles, large floor area occupancy, poor relocation flexibility, and high construction costs with difficult protection in outdoor scenarios. Containerized energy storage systems integrate batteries, power distribution, monitoring, fire suppression, ventilation, and other subsystems within a standard container, with factory-prefabricated production. Field installation requires only simple wiring before the system can be put into operation — perfectly resolving the pain points of traditional construction models and becoming one of the mainstream forms of energy storage applications.
Meanwhile, lead-acid batteries release hydrogen gas during charge and discharge cycles, particularly under overcharge fault conditions. Hydrogen is a flammable and explosive gas; when it accumulates to the explosion limit in a confined space, it can easily trigger an explosion upon encountering electrical sparks or high temperatures. Therefore, explosion-proof safety design of energy storage containers is of critical importance. This project addresses the user’s capacity requirements and safety demands by developing a containerized battery energy storage system with a comprehensive explosion-proof safety system, balancing performance, safety, and convenience.
2.2 Project Construction Objectives
This project is designed around three core objectives: “Safe and Reliable, Intelligent and Efficient, Integrated and Convenient”.
Safety Objectives: Establish a five-in-one safety and explosion-proof system of “gas monitoring – forced ventilation – explosion-proof electrical – pressure relief protection – gas fire suppression”, eliminating hydrogen explosion and fire risks, ensuring equipment and personnel safety, and complying with national explosion-proof and fire protection regulations.
Performance Objectives: Meet the user-defined energy storage capacity and power supply requirements, with stable battery discharge performance, minimal voltage deviation, and long cycle life; monitoring systems with high measurement accuracy and comprehensive protection functions to ensure safe battery operation and extend battery service life.
Schedule Objectives: Adopt a factory-prefabrication + rapid on-site deployment model, significantly shortening the project construction cycle. From order confirmation to delivery and commissioning, the timeline is controlled within a reasonable period, satisfying the user’s requirement for rapid deployment.
O&M Objectives: Achieve intelligent unattended operation, with both local and remote real-time system status monitoring, automatic fault alarming, and simple O&M procedures, reducing operational difficulty and cost.
2.3 Applicable Project Scenarios
The explosion-proof battery containerized energy storage system designed in this proposal is applicable to the following scenarios:
Industrial Enterprise Backup Power: Providing uninterrupted backup power for production lines, DCS control systems, emergency lighting, and other critical loads during grid power outages.
Telecom Base Stations and Edge Rooms: Power assurance for remote outdoor base stations and edge computing nodes, replacing traditional civil-constructed rooms with rapid deployment.
Commercial Building Peak-Valley Arbitrage: Utilizing peak-valley electricity price differentials, charging during off-peak hours and discharging during peak hours to reduce electricity costs.
Microgrids and Renewable Energy Integration: Coordinating with photovoltaic, wind power, and other renewable energy generation to smooth output fluctuations and enhance renewable energy consumption.
Remote Areas and Temporary Power Supply: Power assurance for mines, construction sites, field operations, and other areas without grid coverage, as well as emergency disaster relief temporary power.
Explosion-Hazardous Zones: Chemical, oil & gas, coal mining, and other areas containing flammable and explosive gases, serving as explosion-proof backup power sources.
2.4 Basis for Proposal Preparation
This proposal is strictly designed in accordance with current national standards, specifications, and industry technical requirements. The principal basis includes:
| Standard / Document | Description |
| — | — |
| GB 7251.1-2013 | Low-Voltage Switchgear and Controlgear Assemblies – Part 1: General Rules |
| GB 3836.1-2010 | Explosive Atmospheres – Part 1: Equipment – General Requirements |
| GB 3836.2-2010 | Explosive Atmospheres – Part 2: Equipment Protected by Flameproof Enclosures “d” |
| DL/T 5044-2014 | Technical Code for Design of DC Power Supply Systems in Electric Power Engineering |
| DL/T 637-2019 | Technical Conditions for Ordering Valve-Regulated Sealed Lead-Acid Batteries |
| GB 50016-2014 (2018 Edition) | Code for Fire Protection Design of Buildings |
| GB 50370-2005 | Code for Design of Gas Fire Extinguishing Systems |
| GB 50057-2010 | Code for Design of Lightning Protection of Buildings |
| GB/T 50065-2011 | Code for Design of AC Electrical Installations Earthing |
| NB/T 10394-2020 | Technical Specification for Containerized Energy Storage Systems |
| GB/T 36547-2018 | Technical Regulations for Energy Storage Systems Connected to Distribution Network |
| GB 50058-2014 | Code for Design of Electrical Installations in Explosive Atmospheres |
| GB/T 2423 Series | Environmental Testing for Electric and Electronic Products |
| — | User-provided capacity requirements, operating environment, and associated technical requirements |
2.5 Overall Project Scale and Core Specifications
The energy storage system in this project adopts valve-regulated sealed lead-acid (VRLA) batteries, configured as 2 independent battery clusters, each consisting of 32 × 12V 200Ah batteries in series, for a total of 64 batteries.
| Parameter | Specification |
| — | — |
| Single Cluster Nominal Voltage | 384V DC |
| System Rated Voltage | 384V DC |
| Single Cluster Rated Capacity | 200Ah (10-hour rate) |
| Total System Capacity | 200Ah |
| Total System Energy Storage | ≈153.6kWh |
| Integration Carrier | 1 × 20-foot standard explosion-proof energy storage container |
| Protection Rating | Container IP54; internal electrical equipment complies with explosion-proof class Ex de â…¡B T4 |
| Design Life | Container structure ≥20 years; battery float life ≥10 years |
| Operation Mode | Unattended, fully automatic operation, remote monitoring supported |
—
Chapter 3: User Requirements Analysis
3.1 Energy Storage Capacity and Performance Requirements
The user explicitly requires the configuration of 2 battery groups, each consisting of 32 × 12V 200Ah batteries, totaling 64 batteries, for DC backup power supply or supporting energy storage converter applications. The system must deliver stable charge/discharge performance with steady discharge voltage under rated loads, and capacity meeting design requirements. Battery consistency must be excellent with long cycle life, suitable for both long-term float standby and cyclic charge/discharge operation.
Additionally, the system must incorporate comprehensive electrical protection functions, including overcharge, over-discharge, overcurrent, short-circuit, and insulation fault protection, to prevent battery damage from abnormal operating conditions and ensure power supply continuity and equipment safety.
3.2 Integration and Rapid Deployment Requirements
The user requires the entire battery system to be housed within a container as a fully integrated solution. All equipment, cabling, and accessories must be installed and commissioned at the factory, then transported to the site as a complete unit. On-site work is limited to container positioning, external cable connections, grounding connections, and simple commissioning before the system is operational — significantly reducing on-site construction workload, shortening the construction period, and lowering on-site construction difficulty and management costs.
The container must adopt standard dimensions for ease of road transport and lifting, compatible with conventional container transport vehicles and lifting equipment, and adaptable to rapid deployment and relocation across different sites.
3.3 Safety, Explosion-Proof and Protection Rating Requirements
Given the hydrogen off-gassing risk of lead-acid batteries and the potential for outdoor or industrial deployment, the user has placed stringent requirements on safety protection:
Explosion-Proof Safety: A complete set of explosion-proof measures must be designed to address hydrogen explosion risks, including hydrogen concentration monitoring, forced ventilation, explosion-proof electrical equipment, and pressure relief devices, ensuring gas concentrations within the enclosure remain within safe limits and eliminating explosion hazards.
Fire Safety: An automatic fire suppression system must be configured with multiple activation modes — automatic, manual, and mechanical emergency — capable of rapidly extinguishing incipient fires and preventing fire escalation.
Outdoor Protection: The container must provide rainproof, dustproof, anti-corrosion, and wind-resistant outdoor protection, with a protection rating of no less than IP54, suitable for open-air installations without additional shelter construction.
Electrical Safety: Comprehensive grounding, insulation monitoring, and electric shock protection measures must be in place to ensure the safety of O&M personnel.
3.4 Monitoring and Intelligent O&M Requirements
The user requires intelligent battery management functionality, including real-time monitoring of:
- Individual battery cell voltages
- Total voltage of each battery cluster
- Charge/discharge current
- Battery temperature and other critical parameters
The system must feature fault diagnosis and alarm functions, issuing audible/visual alarms and remote notifications upon abnormal conditions. Battery balancing management is also required to improve battery group consistency and extend battery service life.
The system must support both local visual operation and remote monitoring. O&M personnel should be able to view operating data and operate equipment through the touchscreen on site, and also monitor multiple systems remotely through a backend platform, achieving unattended operation and reducing O&M labor investment.
3.5 Complex Environment Adaptability Requirements
The system must adapt to complex outdoor and industrial environments:
Temperature Adaptability: Normal operation within -20°C to +45°C ambient temperatures. In high temperatures, cooling is achieved through ventilation and heat dissipation; in low temperatures, battery performance meets basic usage requirements. For extreme low-temperature scenarios, heating devices can be optionally configured.
Corrosion Resistance: The container and external structural components must possess excellent corrosion resistance, adapting to corrosive environments such as industrial zones and coastal areas, remaining rust-free and corrosion-free over long-term use.
Altitude Adaptability: Adaptable to installation environments up to 4,000m altitude, with derating design available for high-altitude regions as required.
Seismic Resistance: The overall structure must be robust with securely fixed equipment, capable of withstanding Seismic Intensity VIII, with no equipment displacement, damage, or operational impairment after seismic events.
3.6 Construction and Delivery Requirements
The user requires complete delivery scope, including all hardware equipment, installation accessories, technical documentation, and operation manuals; on-site installation guidance or turnkey installation services; factory acceptance testing before delivery to ensure system functionality; and comprehensive commissioning and acceptance verification after on-site installation to ensure all specifications meet design requirements.
Delivered documentation must include complete technical documents such as system schematic diagrams, wiring diagrams, equipment manuals, test reports, and acceptance reports for subsequent O&M and management purposes.
3.7 After-Sales Service and Training Requirements
The user requires:
- Comprehensive after-sales service assurance with clearly defined warranty periods and timely fault response
- Regular inspection and maintenance services to ensure long-term stable system operation
- Operation and O&M training enabling user O&M personnel to independently perform routine operations, inspections, and common fault handling
- Post-warranty continued support including technical support, spare parts supply, and system upgrade services to ensure system availability throughout its full lifecycle
—
Chapter 4: Overall Design Description
4.1 Overall Design Principles
4.1.1 Safety First Principle
Safety is prioritized above all else, with a comprehensive safety protection system constructed across four dimensions: electrical safety, explosion-proof safety, fire safety, and structural safety. All designs strictly comply with relevant national safety regulations. Multiple protection layers are implemented at critical points to eliminate all types of safety hazards, ensuring equipment and personnel safety.
4.1.2 Reliability Priority Principle
Technically mature, stable, and reliable products and components are selected, with sufficient margin reserved for critical components. The system architecture adopts proven topologies to avoid reliability risks associated with excessive innovation. Connection and wiring designs are optimized to minimize fault points. Factory aging tests and functional tests ensure long-term stable operation, with system Mean Time Between Failures (MTBF) reaching advanced industry levels.
4.1.3 Advanced Technology and Practicality Integration Principle
On the basis of ensuring reliability, industry-leading battery management technology, intelligent monitoring technology, and explosion-proof technology are adopted to enhance system intelligence and O&M efficiency. Practicality is also emphasized, with functional designs aligned to actual user needs, avoiding redundant features that increase cost — achieving a balance of advanced technology and economic practicality.
4.1.4 Integration and Standardization Principle
A highly integrated design approach is adopted, consolidating all subsystems within a standard container for factory prefabrication and integrated delivery. Structural dimensions, electrical interfaces, and communication protocols all comply with industry standards, providing excellent compatibility and expandability for future capacity expansion and third-party system integration.
4.1.5 Easy O&M and Maintainability Principle
Layout design fully considers maintenance space, with equipment arranged for convenient operation and repair. Modular design enables independent replacement of individual components for easy maintenance. The monitoring system features a user-friendly interface, simple operation, and accurate fault localization, reducing the level of professional expertise required from O&M personnel.
4.2 System Architecture Design
This system adopts a layered architecture design, from bottom to top divided into Perception Layer, Control Layer, Execution Layer, and Interaction Layer, with clear division of responsibilities and coordinated operation.
4.2.1 Perception Layer
The Perception Layer serves as the system’s data acquisition source, comprising various sensors and acquisition units, including:
| Acquisition Unit | Function |
| — | — |
| Battery Voltage Acquisition Unit | Collects individual cell voltages and total battery cluster voltage |
| Current Acquisition Unit | Collects total charge/discharge current and branch currents |
| Temperature Acquisition Unit | Collects battery surface temperature and internal ambient temperature |
| Environmental Sensors | Hydrogen concentration detector, smoke detector, temperature/humidity sensor |
| Insulation Monitoring Unit | Monitors DC system insulation resistance to ground |
The Perception Layer transmits collected analog and digital signals to the Control Layer, providing data for system control and protection.
4.2.2 Control Layer
The Control Layer serves as the system’s brain, with the BMS Battery Management System Master Control Unit as its core, supplemented by auxiliary control units such as fire alarm controllers and ventilation controllers.
| Control Unit | Function |
| — | — |
| BMS Master Control Unit | Processes all battery data, executes protection logic, balancing control, alarm determination, data storage, and communication interaction |
| Fire Alarm Controller | Processes fire and gas detection signals, linking ventilation fans, fire suppression devices, and alarm outputs |
| Logic Interlock Unit | Implements interlocking control between subsystems (e.g., hydrogen exceedance interlocked with exhaust ventilation, fire interlocked with power disconnection) |
The Control Layer automatically issues control commands to the Execution Layer based on preset control logic and protection thresholds, ensuring safe and stable system operation.
4.2.3 Execution Layer
The Execution Layer executes control commands from the Control Layer and performs specific actions, including:
| Execution Device | Function |
| — | — |
| DC Circuit Breakers, Contactors | Execute circuit make/break control |
| Explosion-Proof Axial Flow Fans | Execute ventilation, heat dissipation, and gas displacement actions |
| Heptafluoropropane Fire Suppression System | Execute fire suppression actions |
| Audible/Visual Alarm | Execute alarm notification actions |
| Emergency Power Disconnection Device | Executes total power cut-off in emergency situations |
4.2.4 Interaction Layer
The Interaction Layer provides the human-system interface, divided into local and remote interaction:
Local Interaction: Color touchscreen display on the master control cabinet, enabling real-time data viewing, parameter setting, equipment operation, and historical record queries.
Remote Interaction: Via Ethernet or 4G communication, connecting to the remote monitoring platform for centralized monitoring of multiple systems, remote O&M, and data analysis.
4.3 Container Internal Layout Design
This system utilizes a 20-foot standard container as the integration carrier. Internal layout design follows the principles of “sufficient safety clearances, smooth O&M pathways, rational ventilation airflow, and orderly standardized wiring.”
4.3.1 Overall Layout Plan
The container interior is divided along the length into two zones: the Battery Compartment Zone and the Power Distribution & Monitoring Zone.
Battery Compartment Zone: Located in the middle-to-rear section of the container, with 2 battery mounting racks arranged side by side. Each rack houses 32 batteries, corresponding to one battery cluster. An 800mm-wide O&M aisle is reserved between the two racks for battery inspection, maintenance, and replacement operations. A 200mm clearance is maintained between battery racks and side walls for cable routing and air circulation.
Power Distribution & Monitoring Zone: Located at the front end near the container door, housing 1 × BMS integrated energy storage master control cabinet, along with fire control units, terminal blocks, and auxiliary equipment. A 1,000mm operating space is reserved between the master control cabinet and battery racks for convenient cabinet door access, touchscreen operation, and equipment servicing.
4.3.2 Auxiliary Facility Layout
| Facility | Location / Arrangement |
| — | — |
| Air Intake Louvers | Lower section of the container door end |
| Exhaust Louvers & Explosion-Proof Axial Fans | Upper section of the opposite end wall |
| Hydrogen Detectors, Temperature/Humidity Sensors | Top sides of the battery compartment (hydrogen, being lighter than air, accumulates at ceiling level — top mounting provides more sensitive detection) |
| Smoke Detectors | Evenly distributed across the compartment ceiling, covering all areas for rapid fire detection |
| Heptafluoropropane Fire Suppression Cabinet | Adjacent to the master control cabinet; nozzles arranged at the compartment ceiling with evenly distributed piping for rapid agent dispersion throughout the protected space |
| Explosion-Proof LED Ceiling Lamps | Directly above the central aisle for adequate maintenance lighting |
| Emergency Power Disconnection Button | On the exterior side wall of the container — one-press total DC power cut-off without opening the door in emergencies |
| Grounding Terminal Bars | On both interior side walls; all equipment metal enclosures, racks, and container body are reliably connected to the grounding system |
4.3.3 Layout Safety Compliance
- All live parts are provided with insulation protection and safety signage, with sufficient safety clearances maintained between exposed live parts and personnel-accessible areas.
- Distances between equipment, and between equipment and walls, comply with electrical safety and fire protection regulations, with sufficient heat dissipation space and evacuation routes reserved.
- Doors open fully outward with unobstructed pathways, ensuring rapid personnel evacuation in emergencies.
- All equipment is firmly secured with anti-tipping and anti-displacement measures, suitable for transportation and vibration scenarios.
4.4 Electrical System Overall Design
4.4.1 Main Circuit Topology Design
The system adopts two independently designed battery clusters, each with 32 × 12V batteries in series, forming a 384V battery cluster. Each battery cluster corresponds to one DC combiner box, equipped with DC circuit breakers, fuses, and anti-reverse diodes inside, achieving independent make/break, overcurrent protection, and reverse-connection protection for each cluster.
The outputs of the two battery clusters are combined within the master control cabinet, then output through the main DC circuit breaker to the external load or energy storage converter. The main circuit is equipped with current sensors, voltage sensors, and insulation monitoring devices to monitor system operating status in real time.