Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 31

Warning: Undefined variable $taxonomy in /www/wwwroot/gdlain.com/public_html/wp-content/mu-plugins/gdlain-breadcrumb-jsonld.php on line 32
KITOZER
KITOZER

Base Station Lithium Iron Phosphate Battery Installation, Wiring and Commissioning Manual

Table of Contents

Preface

With the comprehensive deployment of 5G communication networks and the continuous advancement of the new infrastructure strategy, communication base stations serve as the core infrastructure bearing network traffic. The reliability, safety, and economy of their power supply systems directly determine the operational quality and service continuity of communication networks. Traditional valve-regulated sealed lead-acid batteries, plagued by short cycle life, low specific energy, poor environmental adaptability, and heavy metal pollution, can no longer meet the power supply demands of the new generation of high-density, high-power-consumption, wide-coverage base stations.

Lithium iron phosphate batteries, leveraging their technical advantages of high energy density, long cycle life, wide temperature range operation, high safety performance, and environmental friendliness, have become the mainstream upgrade solution for base station backup power systems. This manual addresses the dedicated lithium iron phosphate battery system for base station power distribution scenarios, comprehensively covering the full lifecycle technical requirements including product principles, installation and wiring, commissioning and operation, maintenance, fault diagnosis, and acceptance specifications. It strictly complies with industry standards including *YD/T 2344.1-2023 Communication Lithium Iron Phosphate Battery Packs — Part 1: Integrated Battery Packs*, *DL/T 5892-2024 Electrical Installation Engineering — Battery Construction and Acceptance Specifications*, and other industry standards, providing standardized, actionable technical guidance for telecom operators, tower companies, engineering contractors, and O&M teams.

This manual was compiled by the Technical R&D Center of Guangzhou Lain Intelligent System Development Co., Ltd. All technical parameters, operational procedures, and safety specifications have been extensively validated through engineering practice and laboratory testing to ensure safe and stable product operation in various base station scenarios. All relevant personnel must read this manual carefully before installation, commissioning, and operation, and strictly follow the specifications. Non-compliant operation may result in equipment damage, personal injury, or power supply accidents.

Table of Contents

Product Introduction

Product Composition

Product List

Product Working Principles

Product Technical Parameters

Product Functions and Features

Product Application Scenarios

Product Installation

Product Wiring

Product Commissioning

Product Precautions

Product Maintenance and Service

Product Common Problems and Solutions

Product Q&A

Product Acceptance

SEO Optimization System and Keyword Layout

Contact Information and Copyright Notice

Chapter 1 Product Introduction

1.1 Industry Background

The backup power system of communication base stations is the last line of defense ensuring uninterrupted operation of communication networks. When utility power is normal, the battery bank is in float charge standby state; when utility power is interrupted or the switching power supply fails, the battery bank instantaneously switches to discharge state, providing continuous power support to core loads including base station main equipment, transmission equipment, and monitoring systems, preventing base station outage, service interruption, and user complaints caused by power failure.

Traditional base stations commonly use valve-regulated sealed lead-acid batteries (VRLA) as backup power, but they have numerous inherent defects: First, short cycle life — under standard conditions the cycle life is only 500–800 cycles, and in remote areas with frequent power outages, the actual service life is only 2–3 years. Second, low specific energy — at the same capacity, the volume and weight are approximately 2–3 times that of lithium iron phosphate batteries, significantly increasing the load-bearing pressure and floor space requirements of base station equipment rooms. Third, poor temperature adaptability — the optimal operating temperature is only 20–25°C; life decays rapidly in high-temperature environments and capacity drops sharply in low-temperature environments, failing to meet the requirements of complex environments such as outdoor base stations and high-altitude base stations. Fourth, high maintenance costs — periodic equalization charging, internal resistance testing, and capacity verification are required, and there are safety hazards such as acid leakage and gas evolution. Fifth, poor environmental performance — containing heavy metals such as lead, disposal of waste batteries is difficult, not conforming to green and low-carbon development requirements.

With the large-scale construction of 5G base stations, per-station power consumption has increased 2–3 times compared to 4G, imposing higher requirements on backup power capacity, discharge rate, response speed, and intelligence level. Meanwhile, under the dual-carbon goals, the communication industry’s demand for energy conservation, consumption reduction, and green O&M is increasingly urgent. Lithium iron phosphate batteries, leveraging their comprehensive performance advantages, have become the preferred technological route for base station backup power, with rapidly increasing market penetration.

1.2 Product Definition

The base station-specific lithium iron phosphate battery is an integrated energy storage power product specifically designed for communication base station DC power supply systems. It uses lithium iron phosphate (LiFePO₄) cathode material lithium-ion cells as the core energy storage unit, equipped with an intelligent Battery Management System (BMS), power distribution unit, heat dissipation structure, and protective enclosure to realize energy storage, conversion, and intelligent management. The standard output voltage is adapted to the communication industry’s universal -48V DC power supply system and can directly replace traditional lead-acid batteries for connection into existing base station switching power supply systems.

Compared with general-purpose energy storage lithium batteries, base station-specific lithium iron phosphate batteries have been deeply customized and optimized for communication scenarios: First, they strictly comply with communication industry standards, with electrical interfaces, communication protocols, and installation dimensions fully compatible with existing base station power systems, enabling seamless replacement. Second, float charge and shallow charge/shallow discharge operating modes are optimized to suit the usage characteristics of base station backup power with long-term float charging standby and occasional discharge. Third, wide temperature range design and protection ratings are enhanced to adapt to harsh environments including outdoor cabinets, underground equipment rooms, and high-altitude locations. Fourth, comprehensive alarm and communication functions are integrated, allowing connection to the base station environment monitoring system (FSU) for remote status monitoring and centralized management.

1.3 Design Philosophy

This product adheres to the core design philosophy of “safe and reliable, intelligent and efficient, environmentally adaptable, and easy to maintain,” comprehensively meeting the power supply requirements of base station scenarios:

Safety-First Design: A four-level safety protection system is established from cell selection, structural design, BMS protection, to system integration, eliminating thermal runaway risks through multiple protection mechanisms including overcharge, over-discharge, overcurrent, short circuit, over-temperature, and low-temperature protection, satisfying communication equipment room safety specifications.

Long-Life Design: High-cycle-life lithium iron phosphate cells are adopted, with optimized charge/discharge control strategies and balance management algorithms. Under standard conditions, the cycle life is ≥6000 cycles, with a design float charge service life of ≥10 years, significantly reducing total lifecycle cost.

Intelligent Design: A high-precision BMS management system is equipped, achieving real-time monitoring of individual cell voltage, current, and temperature with accurate SOC/SOH estimation, supporting remote parameter configuration, fault alarms, and upgrade maintenance to improve O&M efficiency.

High Adaptability Design: Wide operating temperature range design supports continuous operation from -10°C to 55°C, with special custom versions covering extreme environments from -40°C to 65°C, adapting to environmental conditions of base stations in different regions and types.

Modular Design: Standardized module structure is adopted, supporting parallel expansion for capacity increase. Installation and replacement are convenient, with flexible configuration according to base station capacity requirements, reducing initial investment and expansion costs.

Green and Environmentally Friendly Design: Free of heavy metals such as lead and cadmium, no corrosive electrolyte, minimal pollution during production and use, and waste cells are recyclable, conforming to green communication development requirements.

1.4 Executive Standards

This product strictly complies with the following national and industry standards in design, production, inspection, and installation:

  • YD/T 2344.1-2023 *Communication Lithium Iron Phosphate Battery Packs — Part 1: Integrated Battery Packs*
  • YD/T 2344.2-2015 *Communication Lithium Iron Phosphate Battery Packs — Part 2: Discrete Battery Packs*
  • YD/T 3568.1-2019 *Technical Requirements for Echelon-Used Lithium-Ion Batteries for Communication — Part 1: Lithium Iron Phosphate*
  • DL/T 5892-2024 *Electrical Installation Engineering — Battery Construction and Acceptance Specifications*
  • GB/T 36276-2018 *Lithium-Ion Batteries for Electrical Energy Storage*
  • GB 40165-2021 *Safety Technical Specification for Lithium-Ion Batteries and Battery Packs for Stationary Electronic Equipment*
  • GB/T 19520.16-2015 *Mechanical Structures for Electronic Equipment — Dimensions of Mechanical Structures of the 482.6 mm (19 in) Series — Part 3-10: Subracks and Associated Plug-in Units*
  • YD/T 1970-2009 *Maintenance Technical Requirements for Power System of Telecommunications Stations — Valve-Regulated Sealed Lead-Acid Batteries*
  • GB 50689-2011 *Code for Engineering Design of Lightning Protection and Grounding for Telecommunication Stations*
  • YD/T 2165-2010 *Modular Uninterruptible Power Supply for Telecommunications*

Chapter 2 Product Composition

The base station-specific lithium iron phosphate battery system features an integrated design, primarily consisting of seven core units: cell module unit, Battery Management System (BMS), power distribution and protection unit, cabinet structure unit, thermal management unit, communication interface unit, and grounding system. All units work in coordination to achieve the complete functions of energy storage, management, protection, and communication.

2.1 Cell Module Unit

The cell module is the core energy storage unit of the battery system, serving as the carrier for electrical energy storage and release, directly determining the capacity, voltage, and core performance of the battery system.

2.1.1 Lithium Iron Phosphate Cells

This product utilizes prismatic aluminum-shell lithium iron phosphate cells, with lithium iron phosphate as the cathode material, graphite as the anode material, lithium-ion organic electrolyte, and ceramic-coated polypropylene separator.

Cathode Material: Nano-scale lithium iron phosphate material with doping modification to enhance electrical conductivity, featuring a stable olivine crystal structure. During charge/discharge cycles, lattice deformation is minimal, providing excellent cycling stability. It contains no precious metals such as cobalt, offering low material cost and high safety.

Anode Material: Artificial graphite material with high specific capacity, good rate performance, and cycling stability. The SEI film forms uniformly, effectively inhibiting lithium dendrite growth.

Separator: 16μm thick ceramic-coated separator with good dimensional stability at high temperatures and high shutdown temperature, effectively preventing internal short circuits and enhancing cell safety.

Electrolyte: High flash point flame-retardant electrolyte with film-forming additives and overcharge protection additives, enhancing cell high-temperature stability and safety.

Enclosure: 0.8mm thick aluminum alloy shell, lightweight with good heat dissipation and high deformation resistance. The top integrates an explosion-proof valve that automatically opens to relieve pressure when internal cell pressure exceeds the threshold, preventing cell explosion.

2.1.2 Module Structure

The cell module is assembled from multiple individual cells in series/parallel configuration. The standard module adopts a 16-series structure with a nominal voltage of 51.2V, adapted to the communication -48V DC system. The module primarily consists of cells, busbars, insulation brackets, sampling harnesses, module housing, and connection terminals.

Series/Parallel Structure: Standard 1P16S configuration (1 parallel, 16 series). Individual cell nominal capacities are 50Ah/100Ah/150Ah/200Ah, corresponding to module capacities of 50Ah–200Ah, with system capacity expansion achievable through parallel connection of multiple modules.

Busbars: T2 copper tin-plated busbars with excellent electrical conductivity, low contact resistance, and low temperature rise under high current. Connection methods include laser welding or bolted fastening to ensure connection reliability.

Insulation Brackets: Flame-retardant ABS+PC engineering plastic injection molded, offering high insulation strength, high-temperature resistance, and anti-aging properties. Each cell is individually fixed and isolated to prevent cell displacement and short circuits, while reserving heat dissipation channels.

Sampling Harnesses: High-temperature-resistant, low-smoke, halogen-free wiring. Each cell is equipped with an independent voltage sampling wire and temperature sampling wire, connected to the BMS via connectors to ensure sampling accuracy and reliability.

Module Terminals: Copper nickel-plated high-current terminals supporting high-current charge/discharge, with convenient wiring, low contact resistance, and temperature rise conforming to standard requirements.

2.2 Battery Management System (BMS)

The Battery Management System (BMS) is the “brain” of the battery system, responsible for battery state monitoring, safety protection, balance management, state-of-charge estimation, and communication interaction. It is the core component ensuring safe, reliable, and long-life operation of the battery system. The base station-specific BMS adopts a modular design, divided into three parts: master control unit, acquisition unit, and execution unit.

2.2.1 Master Control Unit

The master control unit is the core control module of the BMS, employing a 32-bit industrial-grade microcontroller (MCU) running a real-time operating system, with powerful data processing capability and high reliability. Its main functions include:

  • Receiving individual cell voltage, temperature, total voltage, and current data uploaded by acquisition units for analysis, processing, and logical determination;
  • Achieving accurate estimation of State of Charge (SOC), State of Health (SOH), and State of Function (SOF);
  • Executing control logic for charge/discharge protection, temperature protection, and fault alarms, driving execution unit actions;
  • Running balance control algorithms and issuing equalization control commands;
  • Providing external communication interfaces for data exchange with switching power supplies and environment monitoring systems;
  • Storing operational data and fault records, supporting historical data query and export.

2.2.2 Acquisition Unit

The acquisition unit is responsible for collecting and preprocessing battery state signals, serving as the “sensory organs” through which the BMS perceives battery status. The main parameters collected include:

Individual Cell Voltage Acquisition: Each cell is equipped with an independent voltage acquisition channel using a high-precision differential sampling circuit, with sampling accuracy of ±5mV and sampling period of ≤100ms, enabling real-time monitoring of each cell’s voltage status.

Total Voltage Acquisition: Monitors the total positive and total negative voltage of the battery pack with sampling accuracy of ±0.5%, used for system-level voltage monitoring and protection.

Current Acquisition: Uses a high-precision Hall effect current sensor or shunt, supporting bidirectional current acquisition with sampling accuracy of ±1%, covering the full charge/discharge current range, used for ampere-hour integration SOC estimation and overcurrent protection.

Temperature Acquisition: Multiple NTC thermistors are distributed within the module to collect temperatures at cell surfaces, busbars, and BMS main board locations, with sampling accuracy of ±1°C, used for temperature protection and thermal management control.

2.2.3 Execution Unit

The execution unit is responsible for executing BMS control commands, achieving circuit make/break and protection. It mainly includes:

Charge/Discharge MOSFETs: Low internal resistance, high-power MOSFETs forming the main charge/discharge loop switches, responding to BMS commands to control the make/break of charge and discharge circuits, with response time ≤10ms.

Balancing Circuit: Passive balancing scheme is adopted, with each series cell configured with an independent balancing resistor and switch transistor. The balancing current is 0.5A–2A. When the voltage difference between individual cells exceeds the threshold, balancing is automatically activated to improve battery pack consistency.

Alarm Relay: Provides dry contact alarm outputs including total fault alarm, charge/discharge alarm, and over-temperature alarm, connectable to base station monitoring systems.

Pre-charge Circuit: Configured with pre-charge resistor and pre-charge relay. On power-up, the back-end capacitors are pre-charged first to prevent inrush current from damaging equipment.

2.2.4 BMS Core Protection Functions

The BMS has a comprehensive multi-level protection mechanism to ensure safe operation of the battery system under various operating conditions. Protection parameters can be flexibly configured according to requirements:

Overcharge Protection: When individual cell voltage exceeds the overcharge protection threshold, the charging circuit is immediately disconnected; when the voltage recovers to below the recovery threshold, charging is automatically restored.

Over-discharge Protection: When individual cell voltage falls below the over-discharge protection threshold, the discharging circuit is immediately disconnected; when the voltage recovers to above the recovery threshold, discharging is automatically restored.

Charge Overcurrent Protection: When charge current exceeds the protection threshold, the charging circuit is disconnected; after fault clearance, automatic or manual restoration.

Discharge Overcurrent Protection: When discharge current exceeds the protection threshold, the discharging circuit is disconnected; after fault clearance, automatic or manual restoration.

Short Circuit Protection: When a short circuit occurs at the output, the discharge circuit is rapidly disconnected within microseconds, preventing large currents from damaging cells and equipment.

Over-temperature Protection: When temperature exceeds the high-temperature protection threshold, charge/discharge is prohibited; when temperature drops below the recovery value, operation automatically resumes.

Low-temperature Protection: When temperature is below the low-temperature charge threshold, charging is prohibited; when below the low-temperature discharge threshold, discharging is prohibited, preventing low-temperature lithium plating from damaging cells.

Cell Voltage Difference Protection: When the voltage difference between individual cells exceeds the threshold, an alarm is triggered and balancing is initiated; in severe cases, high-current charge/discharge is prohibited.

2.3 Power Distribution and Protection Unit

The power distribution and protection unit is the connection hub between the battery system and the external power supply system and load system, achieving electrical energy distribution, isolation, and protection. It mainly consists of the following components:

DC Circuit Breaker: The main battery output circuit is configured with a DC-specific molded case circuit breaker with overload and short circuit protection functions, serving as the system master switch for power isolation during maintenance and fault protection.

Fuses: Key circuits are equipped with fast-acting fuses as secondary short circuit protection, rapidly clearing faults to isolate fault circuits and protect cells and load equipment.

Surge Protection Device (SPD): The DC side is configured with a DC surge protection module with a nominal discharge current of 20kA and maximum discharge current of 40kA, suppressing lightning surges and switching overvoltages to protect the battery system and downstream equipment.

Shunt/Hall Sensor: Used for total current sampling, providing current signals to the BMS.

Terminal Blocks: Configured with power terminals and signal terminals for convenient wiring with clear identification, facilitating on-site wiring and maintenance.

Status Indicator Lights: Configured with power indicator, operation indicator, and alarm indicator lights, visually displaying the battery system operating status.

2.4 Cabinet Structure Unit

The cabinet is the load-bearing and protective structure of the battery system, providing mounting support and environmental protection for internal components. Base station-specific battery cabinets are classified into indoor and outdoor types.

2.4.1 Indoor Cabinet

The indoor cabinet is adapted for standard 19-inch rack mounting, fabricated from 1.5mm thick high-quality cold-rolled steel plate with electrostatic powder coating for corrosion and rust resistance.

Installation Dimensions: Standard 19-inch rack width, with height divided into 3U, 4U, 5U, 6U specifications depending on capacity. It can be directly installed in standard base station equipment racks, or configured with a separate floor-standing cabinet.

Structural Design: Front-to-back ventilation structure with ventilation openings on front and rear doors, forming natural heat dissipation air ducts. Modular installation design with modules adopting drawer-type or fixed-type mounting for convenient maintenance and replacement.

Protection Rating: IP20, preventing finger contact with internal live components and entry of solid foreign objects larger than 12mm diameter.

Grounding Design: The cabinet is equipped with a dedicated grounding copper busbar and grounding terminal to ensure reliable grounding.

2.4.2 Outdoor Cabinet

The outdoor cabinet is specifically designed for outdoor base stations, roadside cabinets, and other outdoor scenarios, featuring high-strength protection and environmental adaptability.

Cabinet Material: 1.5–2mm thick galvanized steel plate or stainless steel plate with multi-layer anti-corrosion surface treatment, UV-resistant and corrosion-resistant, adapting to outdoor sun and rain exposure.

Protection Rating: IP55, dust-proof and water-jet-proof, adaptable to outdoor rain, snow, and sand environments.

Sealing Design: Cabinet doors use EPDM rubber sealing strips for waterproofing and dust prevention; cable entry/exit points are equipped with cable glands to ensure sealing at cable entries.

Thermal Insulation Design: The cabinet interlayer is filled with thermal insulation material to reduce the impact of external temperature changes on internal batteries, mitigating the effects of high-temperature solar exposure and low-temperature freezing on battery performance.

Anti-theft Design: Equipped with anti-theft door locks and anti-pry structure to prevent theft of outdoor equipment.

2.5 Thermal Management Unit

Temperature is a key factor affecting lithium battery performance and lifespan. The thermal management unit functions to maintain the battery operating within the appropriate temperature range, ensuring performance and safety.

2.5.1 Natural Heat Dissipation System

Standard indoor scenarios adopt a natural heat dissipation solution, utilizing cabinet ventilation openings and internal heat dissipation air ducts to remove heat generated during battery operation through natural air convection.

  • Heat dissipation gaps are reserved between modules, forming vertical heat dissipation air ducts;
  • Ventilation openings are provided at the top and bottom of the cabinet, creating a chimney effect to improve heat dissipation efficiency;
  • Heat sink fins are attached to key heat-generating components to enhance localized heat dissipation.

2.5.2 Forced Air Cooling System

High-rate, large-capacity, or high-temperature environment scenarios adopt a forced air cooling solution with intelligent temperature-controlled fans.

  • Low-noise DC fans are used, automatically started/stopped and speed-controlled by the BMS based on temperature;
  • Forced air ducts with front-inlet/rear-outlet or bottom-inlet/top-outlet design ensure uniform airflow across each cell;
  • Dust filters are installed at air inlets to prevent dust from entering the interior, with periodic cleaning and replacement capability.

2.5.3 Heating System

Low-temperature environment scenarios are equipped with a heating system to ensure the battery can be normally charged and discharged at low temperatures.

  • PTC positive temperature coefficient heating pads are used, installed at the bottom or sides of modules, providing uniform heating with safety and reliability;
  • The BMS automatically controls heating start/stop based on temperature. When temperature falls below the set threshold, heating is activated; when the appropriate temperature is reached, heating stops;
  • The heating system has over-temperature protection and dual temperature control to prevent overheating risks.

2.6 Communication Interface Unit

The communication interface unit enables data exchange between the battery system and external devices, supporting connection to base station environment monitoring systems for remote management.

RS485 Communication Interface: Standard configuration includes 2 RS485 interfaces supporting the Modbus-RTU communication protocol, connectable to switching power supplies and environment monitoring FSU, with transmission distance up to 1200m.

Dry Contact Alarm Interface: Provides multiple dry contact outputs including total fault, charge/discharge abnormality, over-temperature, and low-voltage alarm signals. Passive contacts, supporting connection to legacy monitoring systems.

CAN Communication Interface: Optional CAN bus interface supporting parallel communication between multiple modules for coordinated multi-module management.

Bluetooth/WiFi Interface: Optional Bluetooth or WiFi module supporting on-site wireless connection via mobile phone APP or computer for parameter reading, configuration, and commissioning.

Ethernet Interface: High-end models are configured with an Ethernet interface supporting TCP/IP protocol, enabling direct network connection for remote cloud platform monitoring.

2.7 Grounding System

A complete grounding system is key to ensuring equipment safety, lightning protection, and electromagnetic compatibility performance. Battery system grounding includes working grounding, protective grounding, and lightning protection grounding.

Protective Grounding: The cabinet metal shell, metal brackets, and other components are reliably connected to the equipment room grounding grid via grounding copper busbars, preventing electric shock from energized enclosures.

Working Grounding: The DC negative pole of the battery system is connected to the working ground busbar in accordance with communication system specifications, ensuring stable potential of the -48V system.

Lightning Protection Grounding: The dedicated grounding terminal of the surge protection device is connected to the lightning protection ground busbar at the nearest point for lightning current discharge.

Chapter 3 Product List

3.1 Main Product List

Taking the standard 48V100Ah integrated base station lithium iron phosphate battery system as an example, the main product list is as follows:

No. Component Name Specification/Model Qty Unit Remarks
1 Lithium iron phosphate battery module 48V100Ah, 16-series prismatic cells 1 Set Includes cells, busbars, insulation brackets, sampling harnesses
2 Battery Management System (BMS) Base station-specific 16-series BMS master control board 1 Unit Includes acquisition unit, execution unit, protection circuits
3 Power distribution unit Includes DC circuit breaker, fuses, surge protector, terminal blocks 1 Set DC side distribution protection
4 Equipment cabinet 19-inch standard 5U chassis / outdoor cabinet 1 Unit Indoor/outdoor optional
5 Thermal management components Cooling fan / heating pad (configured as required) 1 Set Customized for high/low temperature scenarios
6 Communication components RS485 communication module, dry contact alarm module 1 Set Standard configuration
7 Grounding copper busbar 30×3mm tin-plated copper 1 Piece Cabinet internal grounding

3.2 Random Accessory List

The product is shipped with the following random accessories for on-site installation and basic commissioning:

No. Accessory Name Specification Qty Unit Remarks
1 DC power cable 16mm² low-smoke halogen-free flame-retardant cable 2 m Positive and negative each 1 pc, length customizable
2 Communication cable RVSP 2×1.0mm² shielded twisted pair 3 m RS485 communication line
3 Ground wire BVR 16mm² yellow-green dual-color wire 2 m Protective grounding wire
4 Copper cable lug OT-16 copper tin-plated lug 8 pcs For power cable crimping
5 Mounting bolts M6 hex socket bolts + flat washers + spring washers 20 sets Cabinet mounting and fixing
6 Fuses 5A glass fuse 5 pcs Control circuit spare
7 Dust filter Adapted to cabinet ventilation openings 2 pcs Spare replacement
8 Product certificate of conformity / 1 pc Factory inspection conformity certificate
9 Product user manual / 1 copy Paper version
10 Factory inspection report / 1 copy Factory test data

3.3 Special Tool List

The following special tools are required for installation and commissioning. Some may be provided by the contractor, and some may be applied for from the manufacturer:

No. Tool Name Specification Purpose
1 Digital multimeter 4½-digit precision, DC voltage/current/resistance ranges Voltage measurement, continuity testing, wiring verification
2 Torque wrench 5–50 N·m Bolt tightening, torque control
3 Hydraulic crimping tool 10–120 mm² Cable lug crimping
4 Insulated screwdriver set Flat/Phillips, insulated handle Screw fastening during live operation
5 Wire stripper 0.5–16 mm² Cable stripping
6 Infrared thermometer -20°C to 200°C Temperature detection, temperature rise testing
7 Ground resistance tester 0–100 Ω Ground resistance testing
8 Insulation resistance tester 500V/1000V Insulation performance testing
9 Portable battery tester Supports voltage, internal resistance, capacity testing Battery performance testing
10 Personal protective equipment Insulated gloves, safety goggles, safety helmet Construction safety protection

3.4 Optional Accessory List

The following expansion accessories may be optionally configured according to on-site requirements:

No. Accessory Name Functional Description Applicable Scenario
1 Parallel communication module Supports parallel expansion of multiple battery banks, up to 8 banks Large-capacity base station expansion
2 Bluetooth commissioning module Mobile phone APP wireless connection for commissioning, no need to open cover for wiring On-site O&M commissioning
3 Temperature heating kit Low-temperature environment heating, cold start at -40°C Base stations in cold northern regions
4 Forced air cooling kit Enhanced heat dissipation for high-temperature environments, continuous operation above 55°C High-temperature southern regions, outdoor base stations
5 Smoke sensor Smoke detection inside cabinet, linked alarm and power-off Indoor equipment room safety enhancement
6 Water immersion sensor Water immersion detection at cabinet bottom, alarm notification Underground equipment rooms, low-lying base stations
7 Door sensor Cabinet door open/close detection, unauthorized opening alarm Outdoor cabinet anti-theft monitoring
8 Wall-mounting bracket Supports wall-mounted installation, saving floor space Small base stations, indoor distribution rooms

Chapter 4 Product Working Principles

4.1 Electrochemical Working Principles of Lithium Iron Phosphate Cells

The charge/discharge process of lithium iron phosphate batteries is achieved through the intercalation and deintercalation of lithium ions between the positive and negative electrodes, accompanied by mutual conversion between electrical and chemical energy. The entire process is a reversible electrochemical reaction.

4.1.1 Charging Process

When an external power source charges the battery, lithium ions in the positive electrode lithium iron phosphate detach from the positive electrode crystal lattice under the electric field, pass through the electrolyte and separator, and intercalate into the layered structure of the negative electrode graphite. Simultaneously, electrons flow through the external circuit from the positive electrode to the negative electrode, achieving charge balance, and electrical energy is converted into chemical energy stored in the battery.

Positive electrode reaction: LiFePO₄ → Li₁₋ₓFePO₄ + xLi⁺ + xe⁻

Negative electrode reaction: C + xLi⁺ + xe⁻ → LiₓC

Overall reaction: LiFePO₄ + C → Li₁₋ₓFePO₄ + LiₓC

The charging process is divided into three stages:

Constant Current Charging Stage: Charging at a constant current, with cell voltage gradually rising. This stage offers fast charging speed, with the charged capacity accounting for approximately 80%–90% of the total capacity.

Constant Voltage Charging Stage: When cell voltage rises to the charge cutoff voltage (3.65V), the charger switches to constant voltage charging, and the charging current gradually decreases until the current drops to the set cutoff current, at which point charging ends. This stage supplements the remaining capacity to ensure the battery is fully charged.

Float Charge Standby Stage: After charging is completed, the battery transitions to float charge state, with a very small float current compensating for battery self-discharge losses to maintain the battery in a fully charged state, adapting to the long-term standby working mode of base station backup power.

4.1.2 Discharging Process

When an external load is connected, lithium ions in the negative electrode graphite deintercalate, pass through the electrolyte, and return to the positive electrode lithium iron phosphate crystal lattice. Simultaneously, electrons flow through the external circuit from the negative electrode to the positive electrode, generating discharge current, and chemical energy is converted into electrical energy supplied to the load.

Positive electrode reaction: Li₁₋ₓFePO₄ + xLi⁺ + xe⁻ → LiFePO₄

Negative electrode reaction: LiₓC → C + xLi⁺ + xe⁻

Overall reaction: Li₁₋ₓFePO₄ + LiₓC → LiFePO₄ + C

During discharge, the battery voltage gradually decreases as capacity is released. When the individual cell voltage drops to the discharge cutoff voltage (typically 2.5V–2.8V), discharge should be stopped to prevent over-discharge damage to the cells. Lithium iron phosphate batteries have a stable discharge plateau, with a nominal voltage of 3.2V and discharge plateau of approximately 3.0–3.2V. Most capacity is released within the plateau range, providing good power supply stability.

4.1.3 Self-Discharge Principle

Lithium batteries undergo slow self-discharge during static storage, causing gradual capacity decline. Lithium iron phosphate batteries have a low self-discharge rate, with a monthly self-discharge rate of ≤3% at normal temperature, far lower than lead-acid batteries. Self-discharge primarily originates from two sources:

Physical Self-Discharge: Slow electrochemical reactions caused by internal micro-short circuits and electrolyte impurities within the cell, which are intrinsic characteristics that cannot be completely eliminated.

Chemical Self-Discharge: Side reactions between electrode materials and electrolyte, slow decomposition of the SEI film, etc., closely related to temperature — the higher the temperature, the faster the self-discharge rate.

4.2 BMS Working Principles

4.2.1 State Monitoring Principles

The BMS collects various operating parameters of the battery pack in real-time through high-precision sampling circuits, serving as the basis for control and protection.

Voltage Acquisition: Voltage divider sampling and differential amplifier circuits convert individual cell voltage signals into digital signals recognizable by the MCU, achieving millivolt-level measurement precision through high-precision ADC conversion. Each series cell has an independent sampling channel to avoid crosstalk.

Current Acquisition: The mainstream approach uses Hall effect current sensors, achieving non-contact measurement of AC/DC current based on the Hall effect, with electrical isolation between input and output for high safety. Small-capacity systems may also use shunt sampling, where current is calculated by measuring the voltage across the shunt resistor.

Temperature Acquisition: NTC negative temperature coefficient thermistors are used, whose resistance value decreases as temperature rises. The BMS calculates the resistance value by measuring the divided voltage, then converts it to the corresponding temperature value through the thermistor’s R-T curve.

4.2.2 SOC Estimation Principles

State of Charge (SOC) refers to the percentage of remaining battery capacity relative to rated capacity, and is one of the most critical parameters in battery management. The base station-specific BMS employs a composite algorithm combining ampere-hour integration + open-circuit voltage correction + temperature compensation to improve SOC estimation accuracy.

Ampere-Hour Integration Method: Real-time charge/discharge current is collected and integrated over time. Charged capacity is accumulated and discharged capacity is subtracted, yielding remaining capacity. The formula is:

SOC = SOC₀ + (∫I_charge dt − ∫I_discharge dt) / Cₙ

Where SOC₀ is the initial SOC, I is the current, and Cₙ is the rated capacity.

This method is simple in principle with good real-time performance, but accumulated errors will gradually increase over long-term operation.

Open-Circuit Voltage Correction: Lithium iron phosphate batteries have a corresponding relationship between open-circuit voltage and SOC. When the battery has been at rest for a sufficient period to reach electrochemical equilibrium, the measured open-circuit voltage can be looked up to obtain an accurate SOC value, used to correct the accumulated error of ampere-hour integration. Due to the flat voltage plateau of lithium iron phosphate, voltage changes are only significant in the SOC<20% and SOC>90% ranges, so correction is mainly performed at the fully charged and fully discharged ends.

Temperature and Aging Compensation: Battery available capacity varies at different temperatures, and actual capacity also decays at different aging levels. Temperature coefficients and SOH health state coefficients are introduced into the algorithm to dynamically correct capacity, improving estimation accuracy.

4.2.3 Balance Management Principles

Due to factors such as manufacturing process variations and differences in usage environments, individual cells within a battery pack will exhibit differences in capacity, voltage, and internal resistance. Over long-term use, these differences gradually widen, causing the pack capacity to be limited by the “short-board effect” of the weakest cell, resulting in overall capacity reduction. The purpose of balance management is to reduce differences between individual cells, improve battery pack consistency, and extend service life.

This product adopts a passive balancing scheme. The principle is that when a particular series cell’s voltage is detected to be higher than other cells, the excess energy is dissipated as heat through the balancing resistor corresponding to that series, reducing the charge of the high-voltage cell, ultimately achieving voltage consistency across all cells.

Balancing Trigger Condition: Balancing is initiated when the maximum voltage difference between cells is ≥50mV;

Balancing Current: Standard configuration 1A, optional 2A high-current balancing;

Balancing Timing: Balancing is performed during the end of charging and in resting state; balancing is generally not performed during discharge;

Balancing Control: The BMS monitors individual cell voltages in real-time and dynamically controls the balancing switches of each series to achieve intelligent balancing.

4.2.4 Protection Control Principles

BMS protection functions employ a “two-level protection” architecture: the first level is software protection, and the second level is hardware protection, ensuring reliable protection.

Software Protection: The MCU monitors various parameters in real-time. When parameters exceed protection thresholds, protection logic is executed and control signals are issued to turn off MOSFETs or relays. Software protection can set delay times to prevent false triggering, and protection thresholds can be adjusted through software.

Hardware Protection: An independent hardware protection chip is configured to directly acquire voltage and current signals. When severe overcurrent, short circuit, or other extreme faults occur, the hardware protection circuit directly and rapidly shuts down, with response time far faster than software protection, serving as the last line of defense.

Protection actions are divided into three levels:

Alarm Level: Parameters approach thresholds, triggering audible/visual alarms and remote alarms without restricting charge/discharge, reminding O&M personnel to pay attention.

Restriction Level: Parameters exceed pre-alarm thresholds, restricting charge/discharge current and reducing power operation to prevent fault escalation.

Protection Level: Parameters exceed protection thresholds, completely cutting off charge/discharge circuits, isolating faults, and ensuring safety.

4.3 Charge/Discharge System Working Principles

The base station lithium iron phosphate battery system, together with the switching power supply and base station loads, forms the DC power supply system. Operating modes are divided into two conditions: normal utility power and utility power interruption.

4.3.1 Normal Utility Power Condition

When utility power is normal, the base station switching power supply converts AC power to -48V DC power, supplying power to base station loads on one hand and float charging the battery bank on the other.

  • The BMS detects battery voltage and SOC. When SOC is below the float charge start threshold, the switching power supply supplements the battery at the set float charge voltage;
  • When the battery is fully charged, the switching power supply maintains the float voltage, and the battery only absorbs a very small float current to compensate for self-discharge, remaining in standby state;
  • The BMS continuously monitors battery status and periodically performs balance management to maintain battery consistency;
  • During normal system operation, the battery bank operates in parallel with the switching power supply, jointly providing regulated voltage support to loads and smoothing load fluctuations.

4.3.2 Utility Power Interruption Condition

When utility power is interrupted or the AC side of the switching power supply fails, the switching power supply output voltage drops, and the battery bank instantaneously and automatically switches to discharge state, providing uninterrupted power to loads with zero switching time, ensuring no power interruption to loads.

  • During discharge, the BMS monitors individual cell voltage, total voltage, discharge current, and temperature in real-time, calculating remaining SOC and discharge duration;
  • When discharged to the low-voltage alarm threshold, a low-voltage alarm is issued, alerting O&M personnel that utility power should be restored as soon as possible;
  • If utility power interruption persists and the battery discharges to the cutoff voltage, the BMS disconnects the discharge circuit to prevent over-discharge damage to the battery, at which point the base station load is de-energized;
  • After utility power restoration, the switching power supply automatically restarts, first charging the battery at constant current, then transitioning back to float state after full charge, and the system returns to normal standby.

4.4 Thermal Management System Working Principles

The thermal management system consists of temperature sensors, a controller, and cooling fans/heating pads, operating on closed-loop control principles to maintain battery temperature within the appropriate range.

High-Temperature Cooling Control: When battery temperature is detected to be higher than the cooling start threshold (e.g., 35°C), the cooling fan is activated to force air convection to remove heat; when temperature drops to the cooling stop threshold (e.g., 30°C), the fan stops. Multiple speed levels are supported; the higher the temperature, the higher the fan speed.

Low-Temperature Heating Control: When battery temperature is detected to be lower than the heating start threshold (e.g., 0°C), the PTC heating pads are activated to heat the battery modules; when temperature rises to the heating stop threshold (e.g., 5°C), heating stops.

Extreme Temperature Protection: When temperature exceeds the high-temperature protection threshold (e.g., 55°C) or falls below the low-temperature protection threshold (e.g., -10°C), the BMS prohibits charge/discharge to protect cell safety.

Chapter 5 Product Technical Parameters

This chapter details the technical parameters of the base station-specific lithium iron phosphate battery system, based on mainstream models. Products with different capacities and configurations can be customized according to customer requirements.

5.1 Electrical Performance Parameters

Parameter Category Parameter Item 48V50Ah Model 48V100Ah Model 48V200Ah Model Remarks
Basic Parameters Nominal voltage 51.2V 51.2V 51.2V 16-series lithium iron phosphate
Rated capacity 50Ah 100Ah 200Ah 10-hour rate, 25°C
Rated energy 2.56kWh 5.12kWh 10.24kWh Nominal voltage × rated capacity
Number of cells 16 16 16 1P16S configuration
Cell nominal voltage 3.2V 3.2V 3.2V Lithium iron phosphate cell
Charging Parameters Charge cutoff voltage 57.6V 57.6V 57.6V 3.6V per cell
Recommended charge current 25A 50A 100A 0.5C charging
Maximum charge current 50A 100A 200A 1C charging, 25°C
Float voltage 53.6V~54.4V 53.6V~54.4V 53.6V~54.4V Recommended 54.0V
Float current ≤0.5A ≤1A ≤2A Steady-state value after full charge
Discharge Parameters Discharge cutoff voltage 40.0V 40.0V 40.0V 2.5V per cell
Continuous discharge current 50A 100A 200A 1C continuous discharge
Peak discharge current 100A/30s 200A/30s 400A/30s Short-term peak discharge
Discharge efficiency ≥95% ≥95% ≥95% 1C discharge, 25°C
System Parameters System efficiency ≥94% ≥94% ≥94% Including BMS losses
Standby power consumption ≤1W ≤1.5W ≤2W Static standby loss
Insulation resistance ≥10MΩ ≥10MΩ ≥10MΩ 500V megger
Parallel capability Max. 8 banks Max. 8 banks Max. 8 banks Parallel connection of same model

5.2 Environmental Performance Parameters

Parameter Item Technical Specification Remarks
Operating temperature range -10°C ~ +55°C Discharge: -10°C~55°C; Charge: 0°C~55°C
Storage temperature range -40°C ~ +70°C Long-term storage recommended at 0°C~35°C, SOC 50%
Operating relative humidity 5% ~ 95% Non-condensing
Operating atmospheric pressure 70kPa ~ 106kPa Altitude ≤3000m; derating required above 3000m
Cooling method Natural cooling / forced air cooling Standard type: natural cooling; high-temperature type: forced air cooling
Protection rating IP20 (indoor) / IP55 (outdoor) Compliant with GB 4208
Vibration resistance Compliant with GB/T 2423.10, 10–55Hz, 0.15mm amplitude Transportation and operation vibration requirements
Shock resistance Compliant with GB/T 2423.5, 15g, 11ms Transportation shock requirements
Salt spray protection Neutral salt spray 48h without obvious corrosion Outdoor type enhanced anti-corrosion
UV protection 1000h UV irradiation without aging or cracking Outdoor type enclosure

5.3 Safety Performance Parameters

Test Item Technical Requirement Applicable Standard
Overcharge Protection Charging at 1.5x rated charge voltage; no fire, no explosion YD/T 2344.1-2023
Overdischarge Protection Discharge to 0V; no fire, no explosion; function recoverable YD/T 2344.1-2023
Short Circuit Protection Direct short circuit of positive and negative terminals; no fire, no explosion; recoverable after protection YD/T 2344.1-2023
Overcurrent Protection Discharge at 3x rated current; reliable protection; no fire, no explosion YD/T 2344.1-2023
High-Temperature Storage Storage at 85°C for 16h; no fire, no explosion, no leakage GB/T 36276-2018
Low-Temperature Storage Storage at -40°C for 16h; no fire, no explosion, no leakage GB/T 36276-2018
Nail Penetration Test Steel nail penetration of cell; no fire, no explosion GB 38031-2020
Crush Test 13kN crush force; no fire, no explosion GB 38031-2020
Drop Test Free drop from 1m height; no fire, no explosion GB/T 2423.8
Flame Retardance Enclosure material UL94 V-0 rating UL 94
Insulation Withstand Voltage AC 1500V/1min; no breakdown, no flashover GB 7251.1

5.4 Mechanical Structure Parameters

Parameter Item 48V50Ah (3U) 48V100Ah (5U) 48V200Ah (8U) Remarks
Width 482.6mm 482.6mm 482.6mm 19-inch standard width
Height 133.4mm (3U) 222.3mm (5U) 355.6mm (8U) Including mounting ears
Depth 380mm 400mm 450mm Custom depth available
Weight ≤35kg ≤65kg ≤120kg Reference value
Mounting Method Rack mount / Wall mount / Floor mount Rack mount / Floor mount Rack mount / Floor mount Standard rack mounting ears included
Cable Entry/Exit Front exit / Bottom exit Front exit / Bottom exit Front exit / Bottom exit Optional
Terminal Specification M6 copper terminal M8 copper terminal M10 copper terminal Power wiring terminals

5.5 Communication and Monitoring Parameters

Parameter Item Technical Specification Remarks
Communication Interfaces 2x RS485, 1x CAN, 4x dry contacts Standard configuration
Optional Interfaces Ethernet, Bluetooth, WiFi, 4G Optional per requirements
Communication Protocols Modbus-RTU, CAN2.0 Custom private protocols available
Monitoring Parameters Total voltage, total current, cell voltage, temperature, SOC, SOH, alarm status Full parameter monitoring
Cell Voltage Sampling Accuracy ±5mV At 25°C ambient
Current Sampling Accuracy ±1% FS Full scale
Temperature Sampling Accuracy ±1°C -10°C ~ 60°C
SOC Estimation Accuracy ±5% Under stable conditions
Alarm Output Passive dry contacts, rating DC30V/5A Total fault, undervoltage, overtemperature, charge/discharge abnormality
Data Storage ≥30 days of operating data, ≥100 fault records Circular overwrite

5.6 Lifecycle and Reliability Parameters

Parameter Item Technical Specification Test Conditions
Cycle Life ≥6000 cycles 25°C, 1C charge/discharge, 80% DOD, capacity retention ≥80%
Float Charge Life ≥10 years 25°C ambient, float charge voltage 54.0V
Calendar Life ≥12 years 25°C, storage at 50% SOC
Self-Discharge Rate ≤3%/month 25°C, stored at full charge
Capacity Recovery Rate ≥95% Capacity recovery after 3 months of storage
MTBF ≥100,000 h System level
BMS Service Life ≥8 years Electronic component lifespan
Warranty Period 3-year full machine warranty Standard warranty, extendable

6.1 Core Electrical Performance Advantages

6.1.1 High Energy Density, Saving Installation Space

Using high specific energy lithium iron phosphate cells, the system energy density can reach over 120Wh/kg. Under the same capacity, the volume is only 1/2 that of lead-acid batteries, and the weight is only 1/3, significantly reducing the floor loading pressure of equipment rooms and saving cabinet installation space. It is particularly suitable for base station equipment rooms with tight space and limited load-bearing capacity. The 19-inch standard rack mount design allows direct replacement of existing lead-acid battery cabinets without modifying the equipment room structure.

6.1.2 Long Cycle Life, Reducing Total Lifecycle Cost

Under standard conditions, the cycle life is ≥6000 cycles, which is 8~10 times that of lead-acid batteries; the float charge service life can reach over 10 years, 2~3 times that of lead-acid batteries. Although the initial investment is slightly higher than lead-acid batteries, there is no need for frequent replacement over the entire lifecycle. The comprehensive operation, maintenance, and replacement costs are significantly reduced. Over a 10-year period, the Total Cost of Ownership (TCO) is over 30% lower than lead-acid batteries, delivering significant economic benefits.

6.1.3 Excellent Rate Discharge Performance

Supports 1C continuous discharge and 2C peak discharge. Under high-current discharge, voltage drop is minimal with excellent power characteristics, meeting the peak power consumption requirements of 5G base stations. Low-temperature discharge performance is also superior to lead-acid batteries; at -10°C, the 1C discharge capacity retention rate is ≥75%, ensuring reliable winter power supply for base stations in cold regions.

6.1.4 High Charging Efficiency, Energy Saving and Consumption Reduction

The charging conversion efficiency of lithium iron phosphate batteries is ≥95%, far higher than the 80%~85% of lead-acid batteries. The electrical energy loss during charging is minimal, effectively reducing base station power consumption and meeting the energy-saving and consumption-reduction requirements of the communications industry. It also supports high-current fast charging, reaching 90% capacity in 3 hours. When utility power is restored after an outage, the battery can quickly replenish its charge, effectively handling frequent outage scenarios.

6.1.5 Stable Discharge Platform, High Power Supply Quality

The voltage remains stable during discharge, with over 90% of capacity released within the 3.0~3.2V plateau range. The supply voltage is stable, ensuring stable operating voltage for base station equipment and reducing equipment failures caused by voltage fluctuations. There is no memory effect, allowing charge/discharge at any time without requiring full discharge before recharging (unlike nickel-cadmium batteries), providing convenient usage.

6.2 Multi-Level Safety Protection Features

6.2.1 Cell-Level Safety Design

  • Lithium iron phosphate material itself has excellent thermal stability, with a decomposition temperature above 500°C. It will not undergo violent decomposition releasing oxygen at high temperatures like ternary lithium, fundamentally reducing the risk of thermal runaway at the material source.
  • The cells use ceramic-coated separators, which maintain dimensional stability at high temperatures with a high shutdown temperature, effectively preventing internal short circuits.
  • Cells are equipped with explosion-proof valves that automatically relieve pressure when internal pressure becomes excessive, avoiding the risk of explosion.
  • Cell casings use high-strength aluminum shells with strong resistance to crushing and puncture.

6.2.2 System-Level Multiple Protection

The BMS provides six levels of electrical protection: overcharge, overdischarge, overcurrent, short circuit, overtemperature, and low temperature. Combined with hardware secondary protection, it ensures reliable battery protection under any abnormal condition. The power distribution unit is configured with three levels of electrical protection: circuit breakers, fuses, and surge protectors, achieving full-link safety protection from cell to system.

6.2.3 Structural Safety Design

  • The cabinet uses a metal enclosure with high flame retardance rating. The internal cells and circuits are enclosed within the metal housing, effectively containing flame spread even if a cell becomes abnormal.
  • Modules use fully isolated insulating bracket design, eliminating the risk of short circuits between cells.
  • All conductive components are insulated and protected; exposed live parts have protective covers to prevent accidental contact.
  • A complete grounding system ensures personnel and equipment safety.

6.2.4 Thermal Safety Management

The intelligent thermal management system monitors temperature in real time, automatically dissipates heat at high temperatures, and automatically heats at low temperatures, maintaining battery operation within a safe temperature range. Overtemperature protection is provided — when temperature rises abnormally, charging/discharging is immediately halted to prevent thermal runaway. Multi-point temperature monitoring at critical locations enables precise temperature distribution awareness and early detection of abnormal temperature rise.

6.3 Intelligent Management Functions

6.3.1 Precise Status Monitoring

The BMS monitors the voltage and temperature of every individual cell in real time, along with full-dimension parameters including system total voltage, total current, SOC, and SOH. With high monitoring accuracy and fast data refresh, it provides precise awareness of battery health status. Compared with traditional lead-acid batteries which can only monitor total voltage, lithium batteries enable cell-level refined management, identifying weak cells early and avoiding failure of the entire battery string.

6.3.2 Intelligent Balancing Management

The active balancing management system automatically corrects cell voltage differences, maintaining battery pack consistency and extending the overall pack service life. The balancing process is fully automatic with no manual intervention required, effectively mitigating the “short board effect” and increasing the pack’s usable capacity. Compared with lead-acid batteries which can only achieve rough balancing through equalization charging, lithium battery cell-level balancing provides significantly improved results.

6.3.3 Intelligent Charge/Discharge Management

The BMS dynamically adjusts charge/discharge strategies based on battery status and ambient temperature — automatically limiting charge current at low temperatures and reducing power at high temperatures to protect the battery while maximizing performance output. It supports multiple charging modes including float charge, equalization charge, and top-up charge, adapted to the characteristics of base station switch-mode power supply systems. Pre-charge functionality provides smooth voltage ramping at power-up, avoiding inrush currents.

6.3.4 Comprehensive Alarms and Communication

Supports a multi-level alarm mechanism including pre-alarm, general alarm, and critical alarm, reported through multiple channels: local indicator lights, dry contacts, and communication interfaces. Standard RS485 interface enables seamless integration with base station environment monitoring systems, providing remote status viewing, parameter configuration, and fault alarms. Maintenance personnel can monitor battery operating status without visiting the site, significantly improving maintenance efficiency and reducing maintenance costs.

6.3.5 Fault Diagnosis and Recording

The BMS features intelligent fault diagnosis capability that precisely identifies fault type and fault location — such as overvoltage on a specific cell series or excessive temperature at a specific point — facilitating rapid troubleshooting and repair. Fault information and operating data are automatically recorded, with historical data query and export support for fault tracing and analysis.

6.4 Wide Environmental Adaptability

6.4.1 Wide Temperature Range Operation

Compared with lead-acid batteries which have an optimal operating temperature of only 20~25°C, lithium iron phosphate batteries have a much wider operating temperature range — normal operation from -10°C to 55°C, with custom versions covering extreme environments from -40°C to 65°C. High-temperature degradation is minimal, with capacity retention ≥95% at 55°C; low-temperature discharge capability is strong, still delivering over 75% capacity at -10°C. Suitable for a full range of base station environments from cold northern regions to hot southern regions, and from plains to high altitudes.

6.4.2 Strong Environmental Protection

Outdoor models feature IP55 protection rating, dustproof and waterproof, allowing direct installation on outdoor poles and roadside cabinets without additional equipment room construction. The enclosure is corrosion-resistant, rust-proof, and UV-resistant, adapted to harsh outdoor conditions including sun, rain, and salt spray corrosion. Anti-theft and tamper-resistant designs enhance outdoor equipment security.

6.4.3 High-Altitude Adaptability

Supports normal operation at altitudes up to 3000m. The high-altitude version, through derating design and enhanced insulation, can adapt to altitudes up to 5000m, meeting the base station construction needs of western plateau regions.

6.5 Convenient Maintenance and Installation Features

6.5.1 Modular Design, Easy Installation

Uses standardized modules and rack-mount structure. The installation method is compatible with traditional lead-acid batteries — direct replacement of existing lead-acid batteries is possible without modifying the existing power system. Modules are lightweight, allowing single-person handling and installation, with low construction difficulty. Standardized interfaces simplify wiring and shorten construction time.

6.5.2 Maintenance-Free Design, Low Maintenance Cost

The battery features a fully sealed structure — no water refilling, no acid testing, no periodic equalization charging required, achieving true maintenance-free operation. Routine maintenance only requires periodic visual inspection and data retrieval, with no complex maintenance procedures. Compared with lead-acid batteries requiring periodic water refilling, equalization charging, and capacity testing, maintenance workload is reduced by over 80%.

6.5.3 Flexible Expansion, Configuration on Demand

Supports parallel expansion of multiple battery groups, with a maximum of 8 groups in parallel operation. Capacity can be expanded progressively based on base station load growth, avoiding one-time investment waste. The parallel system automatically achieves current sharing without additional current-sharing devices, making expansion simple and convenient.

6.6 Green and Environmentally Friendly Features

  • Free of heavy metals such as lead, cadmium, and mercury; no corrosive electrolyte; no toxic or hazardous substance emissions during production and use; no soil or water source contamination.
  • No outgassing and no acid mist during charging; no ventilation or exhaust required; no impact on equipment room environment or maintenance personnel health.
  • End-of-life cells are recyclable and reusable; cathode materials can be extracted and repaired, consistent with the circular economy and green, low-carbon development philosophy, supporting the communications industry’s dual-carbon goals.

Base station-specific lithium iron phosphate batteries are widely used in various communications base station and equipment room scenarios, adapting to different environments, capacities, and power supply modes. Typical application scenarios include:

7.1 Macro Base Stations

Macro base stations are the core coverage nodes of mobile communication networks, typically configured with high-capacity base station equipment. They have high power consumption and stringent requirements for backup power capacity and reliability.

Scenario Characteristics: Relatively ample equipment room space, mostly indoor equipment rooms or outdoor integrated cabinets; relatively stable utility power; backup time requirements of 2~4 hours, with some remote areas requiring 8 hours or more.

Product Adaptation: Recommend 48V100Ah~200Ah high-capacity models with multiple parallel groups for extended backup time. Use standard rack-mount products for indoor equipment rooms and IP55 outdoor cabinet products for outdoor sites.

Application Value: Long-life design reduces replacement frequency; large capacity meets long-duration backup requirements; intelligent monitoring enables remote management, reducing macro station maintenance workload; high/low temperature adaptability ensures stable operation across different climate regions.

7.2 Micro/Small Base Stations

Micro base stations, pico base stations, and femto base stations are used for hotspot coverage gap-filling and capacity enhancement. They are numerous, widely distributed, and installed in diverse environments.

Scenario Characteristics: Limited installation space, mostly deployed on utility poles, walls, and building weak-current shafts; variable utility power conditions; inconvenient maintenance access.

Product Adaptation: Recommend 48V50Ah compact models with wall-mount or pole-mount installation; small size and light weight adapt to confined installation spaces.

Application Value: Compact size enables flexible deployment; maintenance-free design reduces maintenance pressure for massive micro station deployments; wide voltage input adapts to unstable utility environments; remote monitoring enables batch centralized management.

7.3 Indoor Distribution Systems

Indoor distribution systems provide signal coverage in shopping malls, office buildings, subways, tunnels, and other indoor scenarios. Equipment room space is limited but the environment is relatively stable.

Scenario Characteristics: Equipment rooms are mostly weak-current shafts or underground rooms with confined space; some underground rooms have humidity and water ingress risks.

Product Adaptation: Recommend compact rack-mount products installable in standard 19-inch power cabinets; underground equipment rooms can be optionally equipped with water immersion sensors and moisture-proof design.

Application Value: Small size saves weak-current shaft space; no acid mist and no pollution make it suitable for indoor environments; low self-discharge suits low-power, long-backup indoor distribution scenarios.

7.4 Edge Computing Rooms / 5G MEC Rooms

5G edge computing rooms are deployed at the network edge, housing MEC servers and transmission equipment. They have high power consumption and high requirements for power supply reliability and intelligence.

Scenario Characteristics: High equipment density and power consumption; high requirements for intelligent and manageable power systems; needs to interface with edge network management systems.

Product Adaptation: Recommend high-capacity, high-rate models supporting high-current discharge; configure Ethernet communication interface for integration with edge management platforms; optional integrated lithium battery + UPS solution.

Application Value: High-rate discharge meets server peak power requirements; intelligent BMS provides refined energy management; protocol customization supports deep integration with edge systems.

7.5 Transmission Node Rooms / Optical Distribution Frames

Transmission node rooms and optical cable distribution frames are key nodes of the transmission network. They are widely distributed and numerous, requiring uninterrupted transmission link operation.

Scenario Characteristics: Dispersed sites, mostly unattended; varying utility reliability; long maintenance inspection cycles.

Product Adaptation: Recommend small-to-medium capacity integrated products with outdoor protection rating, supporting remote monitoring and alarm reporting.

Application Value: Long cycle life adapts to frequent outage scenarios; maintenance-free design reduces inspection workload; remote alarms enable timely fault detection, ensuring stable transmission link operation.

7.6 Remote / Rural Base Stations

Base stations in remote mountainous areas and rural regions typically have poor utility power conditions with frequent and prolonged outages. Some areas have no utility access and require photovoltaic power supply.

Scenario Characteristics: Unstable utility power with frequent and prolonged outages; some are off-grid PV-powered; harsh environments; inconvenient maintenance.

Product Adaptation: Recommend high-capacity, long-cycle-life models with PV charging compatibility; wide temperature range design adapts to field environments.

Application Value: 6000-cycle life adapts to frequent charge/discharge scenarios; high charging efficiency matches PV power supply; wide temperature design adapts to large temperature variations in the field, significantly reducing the cost of frequent battery replacement.

7.7 High-Altitude Base Stations

Western plateau regions have high altitude, low temperatures, and thin air, requiring high environmental adaptability from batteries.

Scenario Characteristics: Altitudes above 3000m; winter temperatures can reach below -30°C; reduced insulation strength in thin air; intense UV radiation.

Product Adaptation: Custom high-altitude, low-temperature models with enhanced insulation design, low-temperature heating system, and UV-resistant enclosure.

Application Value: Low-temperature heating ensures normal charging in winter; high-altitude insulation design prevents breakdown; UV-resistant enclosure extends outdoor service life; solves the pain points of short battery life and winter failure at plateau base stations.

7.8 Emergency Communications Support Scenarios

Emergency communication vehicles, temporary base stations, and disaster relief communication points require rapidly deployable, portable backup power.

Scenario Characteristics: Temporary deployment with frequent transport; requires fast installation and wiring; high reliability and strong environmental adaptability.

Product Adaptation: Recommend portable integrated battery packs with wheels and handles for easy transport, quick-connect interfaces for plug-and-play operation.

Application Value: Light weight facilitates transport; quick wiring enables rapid deployment; high reliability ensures uninterrupted emergency communications; no leakage risk makes it suitable for vehicle transport.

7.9 Base Station Peak Shaving / Peak-Valley Arbitrage Scenarios

In regions with significant peak-valley electricity price differentials, base station lithium batteries can charge during off-peak hours and discharge during peak hours, reducing base station electricity costs.

Scenario Characteristics: Normal utility power; economic benefits achieved through peak-valley price differentials; battery undergoes one charge/discharge cycle per day.

Product Adaptation: Recommend long-cycle-life models; BMS supports scheduled charge/discharge strategies; can interface with smart grid dispatch systems.

Application Value: 6000-cycle life meets daily cycling requirements; intelligent management system supports time-of-use pricing strategies; achieves cost reduction and efficiency improvement while maintaining backup power functionality.

8.1 Pre-Installation Preparation

8.1.1 Personnel Preparation

  • Installation personnel must be professionally trained and familiar with lithium iron phosphate battery performance, structure, and safety regulations, understanding the installation procedures and requirements in this manual.
  • At least 2 construction personnel must be on site, with 1 designated as site supervisor responsible for construction organization, safety management, and quality control.
  • Construction personnel must wear approved personal protective equipment including insulating gloves, safety helmets, safety goggles, and insulating work shoes. Wearing synthetic fiber clothing and metal jewelry is strictly prohibited.
  • For work at height, certified climbing personnel must be engaged, holding valid work-at-height certifications, wearing safety harnesses, and complying with work-at-height safety regulations.

8.1.2 Tools and Instruments Preparation

Prepare tools according to the dedicated tool list in Section 3.3 of this manual; check tool integrity and accuracy before installation:

  • Electrician tools: Insulated screwdrivers, wire strippers, crimping pliers, torque wrenches, etc. Ensure insulation integrity and correct specifications.
  • Measuring instruments: Digital multimeter, ground resistance tester, insulation resistance tester, infrared thermometer — calibrated and within validity period.
  • Auxiliary tools: Flashlight, marking pens, cable ties, cleaning agents, anhydrous alcohol, lint-free cloths, etc.
  • Hoisting and transport tools: High-capacity battery packs require manual hydraulic pallet trucks and lifting slings. Using steel wire ropes to directly bundle batteries is strictly prohibited.

8.1.3 Technical Documentation Preparation

  • Product manual, factory inspection report, product certificate, and other documentation supplied with the equipment.
  • Engineering design drawings, system wiring diagrams, and equipment room floor plans.
  • Installation construction plan and safety technical disclosure documents.
  • Installation quality record forms, commissioning record forms, and other acceptance documents.

8.1.4 On-Site Environment Inspection

Before installation, conduct a comprehensive inspection of the installation site to confirm compliance with installation conditions:

  • Equipment room environment check: Room renovation completed; floor level and clean; no dust, standing water, or corrosive gases; doors and windows intact with weather protection; fire protection equipment complete and functional.
  • Load-bearing check: Floor or cabinet load-bearing capacity at installation location meets battery weight requirements. For rack mounting, confirm cabinet load capacity; for floor mounting, confirm floor load capacity; reinforce if necessary.
  • Space check: Sufficient operating space reserved at installation location — front operating distance ≥600mm, side maintenance distance ≥400mm, top clearance ≥300mm for heat dissipation.
  • Temperature and humidity check: Site ambient temperature between 0°C~40°C, relative humidity ≤85%, no condensation. If outside this range, corrective measures must be taken before installation.
  • Grounding system check: Equipment room grounding system completed; ground resistance ≤10Ω; grounding busbar installed with reserved grounding terminals.
  • Power supply check: Base station switch-mode power supply installed and commissioned; output voltage normal; battery access breaker and terminals reserved.
  • Safety check: No flammable or explosive materials on site; keep away from heat sources and open flames; equip with CO2 or dry powder fire extinguishers. Using water-based fire extinguishers is strictly prohibited.

8.2 Unpacking and Inspection

After equipment arrival and before installation, unpacking inspection must be performed to confirm equipment integrity and completeness of accessories. The inspection process requires the presence of both supplier and buyer personnel.

Packaging check: Verify the outer packaging is intact with no damage, water immersion, or impact marks; confirm the model and quantity on package labels match the order. If packaging is visibly damaged, photograph the damage and contact the manufacturer.

Visual inspection: Remove the equipment main unit and check the cabinet surface for deformation, paint peeling, or rust; verify cabinet door open/close smoothness and lock functionality; check interface terminals for deformation or corrosion and seal gaskets for detachment.

Internal inspection: Open the cabinet door and check internal modules, BMS, and distribution components for looseness, detachment, or damage; check wiring harnesses for detachment and screws for looseness; inspect for foreign objects, water stains, or mold.

Initial electrical check: Use a multimeter to measure the battery total output voltage. The voltage should be between 51V~54V (approximately 53.6V at full charge), polarity correct, no short circuit. Measure individual cell voltages — should be between 3.2V~3.4V with a maximum differential ≤50mV.

Accessory verification: Check all accessories and documentation against the packing list, confirming completeness and integrity.

Inspection records: Complete the unpacking inspection record form, documenting results, with signatures from both parties. If deficiencies or quality issues are found, contact the manufacturer promptly for resolution.

Precautions: Protect the equipment during unpacking to avoid hard impacts; strictly prohibit violent dismantling of packaging; handle the equipment gently when removing; never lift or pull on terminals, wiring harnesses, or other vulnerable components.

8.3 Indoor Rack-Mount Installation

Indoor base station equipment rooms typically use 19-inch standard cabinets for installation. The procedure is as follows:

Position marking: Determine the battery installation position in the cabinet according to design drawings and mark mounting holes. Typically installed in the middle-to-lower section of the cabinet to lower the center of gravity and improve stability.

Install mounting rails: Install the matching rails onto the cabinet mounting posts using cabinet-specific screws. Ensure rails are level, front-to-back aligned, and the distance between left and right rails is correct.

Insert equipment: With two people cooperating, smoothly lift the battery equipment onto the rails and slowly push into the cabinet. Avoid scraping the cabinet and equipment front panel; prevent impact to terminals and internal components.

Secure equipment: Once pushed into position, secure the front panel mounting ears to the cabinet posts using the provided screws. Tighten diagonally and evenly to ensure the equipment is firmly secured without wobbling.

Level check: Use a spirit level to verify installation levelness; level deviation ≤1mm/m. Correct by adjusting screws or shims if not level.

Grounding connection: Use dedicated grounding wire to connect the equipment grounding terminal to the cabinet grounding busbar. Connection must be secure with good contact.

8.4 Floor-Mount Installation

High-capacity battery packs or standalone battery cabinets use floor-mount installation:

Base positioning: Determine the installation position according to design drawings. The floor must be level and solid. If the floor is uneven, lay steel plates or insulating pads to level.

Cabinet positioning: Use a hydraulic pallet truck or manual handling to move the cabinet to the designated position. Ensure correct orientation with the front facing the operating aisle.

Cabinet securing: For applications requiring seismic resistance, secure the cabinet base to the floor using expansion bolts at no fewer than 4 fixing points. Ensure the cabinet is stable and seismic resistance rating meets local requirements.

Level and plumb check: Use a spirit level and plumb line to check cabinet levelness and verticality. Level deviation ≤2mm/m; verticality deviation ≤1.5mm/m. Adjust using base shims.

Grounding connection: Connect the cabinet protective grounding terminal to the equipment room grounding grid, and the working grounding terminal to the DC working ground busbar. Ground wire cross-section must meet design requirements with secure and reliable connections.

8.5 Outdoor Cabinet Installation

Installation of outdoor battery cabinets for outdoor base stations and pole-mounted sites:

Foundation construction: Pour concrete foundation or install steel structural supports per design requirements. Foundation levelness and load capacity must meet requirements; reserve fixing bolt holes and cable penetration holes.

Cabinet hoisting and positioning: Use crane lifting or manual handling to place the cabinet on the foundation; adjust position and levelness.

Cabinet securing: Secure the cabinet base to the foundation using bolts; apply anti-corrosion treatment. For pole mounting, use dedicated mounting clamps with dual-clamp fixation to ensure secure fastening and wind resistance meeting requirements.

Sealing treatment: After routing cables through cable entry holes, seal with waterproof cable glands. Ensure cabinet sealing gaskets fit tightly to prevent rain and dust ingress.

Grounding connection: Connect the cabinet grounding terminal to the nearest grounding grid. Ground resistance ≤10Ω. Outdoor sites require proper lightning protection grounding.

8.6 Multi-Group Parallel Installation

When single-group battery capacity is insufficient and multiple groups need to be connected in parallel for expansion, the following requirements must be observed:

Consistency requirements: Parallel battery groups must be from the same manufacturer, same model, and same production batch, with identical capacity, voltage, and software versions. Mixing batteries of different brands, capacities, ages, or states of health in parallel is strictly prohibited.

Installation layout: Multiple battery groups should be installed as close together as possible to minimize parallel cable length. Ensure cable length and conductor cross-section of each branch circuit are identical to ensure current sharing.

Busbar connection: Configure a dedicated DC busbar. Connect the positive and negative terminals of each battery group to the busbar, then connect uniformly to the switch-mode power supply.

Parallel communication: Connect the CAN or RS485 parallel interface of each battery group in series using communication cables to achieve coordinated management of the parallel system, ensuring synchronized current sharing and protection.

Switch configuration: Configure an independent circuit breaker in the positive circuit of each battery group to allow individual group maintenance without affecting other groups.

8.7 Installation Quality Inspection Standards

After installation, perform installation quality self-inspection according to the following standards:

Inspection Item Standard
Installation security: Equipment firmly fixed; no looseness or wobble; all screws fully tightened; none missing
Levelness/Verticality: Cabinet level deviation ≤2mm/m; verticality deviation ≤1.5mm/m
Visual integrity: No damage, paint peeling, or deformation on equipment surfaces; surfaces clean; no construction debris
Labeling completeness: Equipment nameplate, warning labels, and terminal markings clear and complete; cable labels complete and accurate
Grounding reliability: Grounding connections secure; ground resistance meets requirements; grounding continuity good
Space compliance: Operating space and heat dissipation clearance meet requirements; no obstruction of ventilation openings
Electrical safety: Output terminals free of short circuits; positive/negative polarity correct; insulation resistance meets requirements

9.1 Wiring Preparation

9.1.1 Safety Confirmation

  • Confirm before wiring that the battery pack main switch is in the open (OFF) position and the battery breaker on the switch-mode power supply side is also open, ensuring de-energized wiring operations.
  • Re-measure the battery output terminal voltage with a multimeter to confirm normal voltage and no short circuit; confirm no short circuit fault on the load side.
  • Set up warning signs at the work site; unauthorized personnel are prohibited from entering. Live-work is strictly prohibited; shorting positive and negative terminals is strictly prohibited.
  • Construction personnel must wear insulated protective equipment and use insulated tools. Metal parts of tools should be wrapped with insulating material.

9.1.2 Cable Selection

Select power cable with appropriate conductor cross-section based on battery capacity and maximum discharge current, ensuring cable current-carrying capacity meets requirements with acceptable temperature rise during long-term operation. Recommended cable selection is as follows:

Battery Capacity Continuous Discharge Current Recommended Power Cable Recommended Terminal
50Ah 50A 10mm² flame-retardant stranded copper cable OT-10
100Ah 100A 16mm² flame-retardant stranded copper cable OT-16
200Ah 200A 35mm² flame-retardant stranded copper cable OT-35
300Ah 300A 50mm² flame-retardant stranded copper cable OT-50
  • Cable type: Prefer low-smoke, halogen-free flame-retardant power cable (WDZ-YJV), meeting equipment room fire protection requirements.
  • Cable length: Minimize cable length to reduce voltage drop and losses; leave appropriate excess at both ends.
  • Communication cable: Use shielded twisted pair (RVSP 2*1.0mm²) for RS485 communication; shield layer grounded at one end only.

9.1.3 Cable Pre-Processing

  • Cut cables to actual wiring length with tolerance within ±5%; parallel group cable lengths must be identical.
  • Strip insulation from both cable ends; strip length must match terminal specifications to avoid excessive or insufficient exposed copper; do not damage copper strands during stripping.
  • Crimp wiring terminals using an appropriately sized hydraulic crimping tool. Crimps must be secure with clear crimp indentations and pass pull-test without detachment. After crimping, insulate terminals or apply heat-shrink tubing.
  • Apply identification labels at both cable ends indicating circuit name, polarity, and destination. Labels must be clear, secure, and resistant to falling off.

9.2 DC Power Wiring

DC power wiring connects the battery system to the switch-mode power supply and loads. It is the most critical wiring and must strictly follow specification.

9.2.1 Wiring Sequence

Strictly follow the wiring sequence: “connect load side first, then battery side; connect negative first, then positive.” Reverse the sequence for disconnection.

1. First connect the cable’s other end to the switch-mode power supply battery terminals or DC distribution busbar. Verify correct polarity — negative to -48V, positive to 0V (working ground).

2. After completing switch-mode power supply side wiring, proceed to battery side wiring — connect the negative cable first, then the positive cable.

3. One person works while another supervises. Hands and tools must not simultaneously contact both positive and negative terminals to prevent short circuits.

9.2.2 Wiring Process Requirements

Polarity verification: Repeatedly verify positive/negative polarity before connection. Battery positive connects to system positive (0V); battery negative connects to system negative (-48V). Reverse connection is strictly prohibited — it can cause BMS damage, battery short circuit, and even fire. Must be double-checked by two persons.

Terminal tightening: Use a torque wrench to tighten bolts to specified torque. Copper terminals and connection posts must fit tightly with good contact. Recommended tightening torques:

Bolt Size Recommended Torque
M6 5~6 N·m
M8 10~12 N·m
M10 18~22 N·m
M12 30~35 N·m

Contact requirements: Contact surfaces must be flat and clean — free of oxidation layers, oil, and contaminants. Conductive grease may be applied to busbar-terminal contact surfaces to reduce contact resistance and prevent oxidation.

Insulation protection: After wiring, cover exposed live parts with insulation sleeves or wrap with insulating tape to prevent accidental contact and short circuits. Maintain sufficient safe distance between positive and negative terminals to prevent foreign object bridging.

Cable securing: Route cables neatly and secure with cable ties. Cabling should be horizontal and vertical in alignment, avoiding stress on terminals. Leave slack at bends; avoid excessively small bend radii.

Parallel group wiring: For multiple parallel groups, cable length and conductor cross-section from each battery group to the busbar must be identical to ensure balanced discharge current among groups. Busbar current-carrying capacity must meet total current requirements.

9.2.3 Post-Wiring Inspection

Continuity and polarity check: Use multimeter continuity mode to verify no short circuit between positive and negative; use voltage mode to verify correct polarity and no reverse connection.

Voltage measurement: Measure battery side voltage and switch-mode power supply side voltage; the difference between them should be ≤0.5V to avoid excessive inrush current at closing.

Contact resistance check: For high-current systems, measure voltage drop across wiring terminals to calculate contact resistance, ensuring good contact and no loose connections.

Insulation check: Measure insulation resistance between live parts and cabinet; ≥10MΩ is acceptable.

Workmanship check: Verify wiring neatness, label clarity, and insulation protection completeness per workmanship standards.

9.3 Communication Wiring

Communication wiring enables data exchange between the battery system and environment monitoring/switch-mode power supply systems.

9.3.1 RS485 Communication Wiring

  • Use RVSP 2*1.0mm² shielded twisted pair. Connect A wire to A terminal and B wire to B terminal, correspondingly connecting to the monitoring equipment RS485 interface.
  • The shield layer is grounded at one end only (monitoring side); the battery side is left floating to avoid shield circulating currents caused by ground potential differences between locations.
  • For communication distances exceeding 1000m, install termination resistors at both ends of the bus, typically 120Ω.
  • When multiple devices are daisy-chained on the same 485 bus, use series daisy-chain topology; star connections are strictly prohibited. Bus length ≤1200m; node count ≤32.
  • Keep communication cables away from power cables; do not route in the same conduit as high-voltage cables to prevent electromagnetic interference.

9.3.2 Dry Contact Alarm Wiring

  • Dry contacts are passive (voltage-free) contacts connected to the alarm collection circuit of the monitoring system. Connect normally-open or normally-closed contacts according to monitoring system requirements.
  • Use RVV 2*0.75mm² cable for alarm wiring. Each alarm circuit can be separately wired or share a common terminal.
  • Before wiring, confirm alarm contact rating matches monitoring circuit voltage and current to avoid overload burning out contacts.
  • Test alarm function after wiring — simulate a fault and verify the alarm signal is correctly transmitted.

9.3.3 Parallel Communication Wiring

  • For multiple battery groups in parallel, use dedicated communication cables to connect the parallel interface of each group in series, forming a daisy-chain topology.
  • The first and last battery groups should have termination resistors enabled per requirements; intermediate groups should have termination disabled.
  • After wiring, verify communication status to confirm all groups communicate normally with synchronized and consistent data.

9.4 Grounding Wiring

Proper grounding is essential for safe equipment operation. The grounding system includes protective grounding, working grounding, and lightning protection grounding.

Protective grounding: Use yellow-green dual-color grounding wire to connect the cabinet grounding terminal to the equipment room protective grounding busbar. Ground wire cross-section ≥16mm², connections secure, contact resistance low. This prevents the equipment enclosure from becoming live and ensures personnel safety.

Working grounding: The positive terminal of the communications -48V system is typically used as working ground, connected to the DC working ground busbar and reliably connected to the equipment room grounding grid, ensuring stable system potential.

Lightning protection grounding: The battery system’s DC surge protective device (SPD) grounding terminal must be connected to the nearest lightning protection grounding busbar. Grounding wire should be as short and straight as possible to reduce lead inductance and enhance surge protection effectiveness.

Grounding requirements:

Requirement Specification
Anti-corrosion treatment at grounding connection points Ensure long-term reliable contact
Ground resistance value ≤10Ω; may be relaxed to ≤30Ω in mountainous areas and high soil resistivity regions
Circuit breakers or fuses in grounding circuit Strictly prohibited
Grounding to water pipes, heating pipes, or other utility structures Strictly prohibited

9.5 Wiring Safety Precautions

  • Live wiring is strictly prohibited. Before wiring, confirm all relevant power switches are in the open position and post warning signs.
  • Strictly prohibit placing metal tools, screws, washers, or other metal objects on top of the battery or near terminals to prevent dropped-object short circuits.
  • During wiring, hands and tools may contact only one terminal at a time; simultaneous contact with both positive and negative terminals is strictly prohibited.
  • Temporarily exposed cable ends must be wrapped with insulating tape to prevent accidental contact short circuits.
  • All wiring must be secure and reliable. Loose connections can cause heating under high current and potentially cause fire.
  • After wiring completion, clean the work area and account for all tools and parts to prevent leaving items inside the equipment that could create hazards.

10.1 Pre-Commissioning Preparation

10.1.1 Condition Confirmation

  • Installation and wiring fully completed; installation quality and wiring workmanship self-inspection passed; records complete.
  • Site environment meets operating requirements — temperature, humidity, ventilation, and fire protection conditions acceptable; no safety hazards.
  • Utility power supply normal; switch-mode power supply operating normally with stable output voltage.
  • Commissioning tools and instruments ready — multimeter, thermometer, laptop (with commissioning software), communication cables, all in good condition.
  • Commissioning personnel familiar with product principles and commissioning procedures, holding appropriate qualifications, with clear division of duties and safety responsibilities.
  • Emergency response plan for commissioning established, with clear abnormal condition handling procedures and responsible persons.

10.1.2 Comprehensive Pre-Energization Inspection

Before energization, a comprehensive inspection must be performed to confirm no safety hazards. Inspection items include:

Visual and structural check: Cabinet door closed and intact; no tools or debris left inside; modules securely installed without looseness; wiring harnesses neat without pinching or damage.

Wiring check: All power cables, communication cables, and grounding wires correctly and securely connected; polarity correct; labels clear; exposed live parts properly insulated.

Switch status check: Battery internal circuit breaker and output switch in open position; switch-mode power supply side battery breaker in open position.

Insulation resistance test: Use a 500V megger to measure insulation resistance between positive/negative terminals and ground. ≥10MΩ is acceptable. Disconnect the BMS and surge protector before measurement to avoid damaging electronic components.

Voltage check: Measure battery open-circuit total voltage and individual cell voltages; record values; confirm voltages within normal range and cell voltage differential meets requirements.

Grounding check: Verify grounding connections are secure; measure ground resistance to confirm compliance.

10.2 No-Load Energization Commissioning

10.2.1 Power-On Procedure

1. Close the battery pack internal main circuit breaker. The BMS powers up and panel indicator lights illuminate in sequence.

2. Observe the BMS startup process — power indicator solid on, operation indicator flashing, alarm indicator briefly illuminating then going out, indicating normal system startup.

3. Wait for system initialization to complete. The system enters normal operating state after approximately 30 seconds.

4. If the alarm indicator remains solid or flashing during startup, a fault exists. Immediately disconnect power and troubleshoot the cause.

10.2.2 No-Load Parameter Verification

Status indicator check: Observe panel indicator status — power indicator on indicates normal supply; operation indicator flashing indicates normal operation; alarm indicator off indicates no faults.

Voltage parameter reading: Read system total voltage and individual cell voltages via the BMS display panel or commissioning software; record data. Cell voltages should be between 3.2~3.4V with maximum differential ≤50mV.

Temperature parameter reading: Read each temperature measurement point. Values should be close to ambient temperature with differential ≤3°C and no abnormal high-temperature points.

Current check: In no-load state, current should be 0 or near 0. Significant current indicates leakage or internal fault requiring investigation.

SOC and SOH reading: Read SOC value — should correspond to battery open-circuit voltage. New battery SOH should read 100%.

Firmware version check: Verify BMS firmware version matches factory version and meets site requirements.

10.2.3 Alarm Function Test

Fault simulation test: Use commissioning software to simulate overvoltage, undervoltage, overtemperature, and other faults. Verify the alarm indicator illuminates, alarm dry contacts activate, and alarm information is displayed correctly.

Alarm recovery test: Clear the simulated fault and verify the alarm automatically clears and the system returns to normal operation.

Alarm record check: Review BMS fault records to confirm alarm events were correctly logged with accurate time and type.

10.3 Float Charge Commissioning

After no-load commissioning passes, perform float charge commissioning to verify battery and switch-mode power supply compatibility.

Switch-mode power supply parameter setting: Set the switch-mode power supply battery float charge voltage to 54.0V (fine adjustment per manufacturer recommendations). Set charge current limit to 0.5C (e.g., 50A for a 100Ah battery).

Closing operation: Confirm battery voltage and switch-mode power supply output voltage difference ≤0.5V. Slowly close the battery output switch, observing for inrush current and sparking. Closing should be smooth with no abnormality.

Charge state observation:

  • If battery SOC is low, the switch-mode power supply enters constant-current charging mode — charge current reaches the current limit and battery voltage gradually rises.
  • When battery voltage rises to the float charge voltage, transition to constant-voltage float charging occurs — charge current gradually decreases.
  • During charging, the BMS operates normally without alarms; cell voltages rise synchronously with differential maintained within a reasonable range.

Parameter monitoring:

Parameter Monitoring Requirement
Monitoring frequency Record total voltage, charge current, highest/lowest cell voltage, maximum temperature every 10 minutes
Maximum cell voltage during charging ≤3.65V
Maximum temperature during charging ≤45°C
Float current at steady state ≤0.01C, compliant with YD/T standard requirements

Balancing function verification: At the end of charging, observe whether the BMS balancing function activates and whether cell voltage differential gradually decreases, verifying normal balancing operation.

Full charge determination: The battery is considered fully charged when the charge current continuously decreases to the cut-off current (typically 0.02C) and is maintained for over 2 hours, cell voltages stabilize at 3.35~3.4V, and SOC displays 100%.

10.4 Discharge Function Commissioning

After charging is complete, perform a discharge test to verify battery discharge performance and protection functions. The discharge test can be conducted using actual base station load discharge or external dummy load discharge.

10.4.1 Load Discharge Commissioning Steps

1. Confirm the battery is fully charged, float charge current is stable, and record initial voltage, SOC, and individual cell voltages.

2. Disconnect the AC input of the switching power supply to simulate a mains power outage; the battery automatically switches to discharge state, and the base station load is powered by the battery.

3. Observe the switching process — the load equipment should not lose power or restart, the switchover should be smooth, indicating normal battery discharge response.

4. Discharge process monitoring:

  • Monitor discharge current, total voltage, cell voltages, and temperature changes; record every 15 minutes;
  • The discharge plateau should be stable, voltage drop rate normal, cells drop synchronously, and cell voltage differential should not increase significantly;
  • Discharge current should match load power with no overcurrent;
  • Battery temperature rises slowly, maximum temperature not exceeding 50°C, with normal temperature rise.

5. Low voltage alarm verification: Continue discharging to the low voltage alarm threshold (typically 2.8V per cell, 44.8V total), check whether the low voltage alarm triggers normally and whether the alarm signal is uploaded to the monitoring system.

6. Over-discharge protection verification: If conditions permit, continue discharging to the discharge cutoff voltage, check whether the BMS reliably cuts off the discharge circuit, and verify no output voltage and no abnormalities after protection.

7. Recovery test: Restore mains power supply, start the switching power supply, check whether the battery automatically resumes charging and whether the system returns to normal operation.

10.4.2 Capacity Verification Test

For important base stations, a capacity verification test is required to confirm the actual battery capacity meets specifications:

1. After the battery is fully charged, connect a dedicated external dummy load and discharge at a constant current at the 10-hour rate.

2. When discharging reaches the termination voltage, record the discharge duration and calculate actual capacity: Capacity = Discharge current × Discharge time.

3. At 25°C ambient temperature, the actual capacity should be ≥ 100% of rated capacity; capacity retention rate at low temperatures should meet standard requirements.

4. Record cell voltage changes during the test to assess cell consistency; cell voltage differential should not increase significantly after the capacity test.

10.5 Communication Commissioning

10.5.1 Communication with Switching Power Supply

1. Confirm physical wiring is correct and communication parameters match (baud rate, address, protocol).

2. Read battery parameters on the switching power supply side, including total voltage, current, SOC, temperature, alarm information, etc.; data should be consistent with the battery’s local display.

3. Test the coordinated control between the switching power supply and the battery, such as charge current limiting, temperature derating, and other functions.

10.5.2 Commissioning with Dynamic Environment Monitoring FSU

1. Configure battery communication parameters according to the dynamic environment monitoring protocol, setting the correct device address, baud rate, data bits, and parity bits.

2. View battery telemetry and remote signaling data on the monitoring platform, confirm all monitoring point data is uploaded correctly and refreshes normally.

3. Simulate fault alarms to confirm the monitoring platform receives alarm information with accurate alarm level, type, and delay meeting requirements.

4. Test remote parameter configuration functions (if supported), confirm protection thresholds, alarm thresholds, and other parameters can be modified remotely.

10.5.3 Parallel System Commissioning

For multi-group parallel systems, verify parallel functions:

1. Check that communication for each battery group is normal and all groups can identify other parallel units.

2. Monitor each group’s current during charge/discharge to verify current sharing; the current sharing error for each group should be ≤ 5%.

3. Simulate a single group fault to check whether the faulty group automatically exits while other groups operate normally without affecting system power supply.

10.6 Overall System Operation Verification

After all individual commissioning items are completed, conduct a continuous operation verification for no less than 2 hours:

1. The system transitions to normal float charge standby state and operates continuously for 2 hours; observe that all parameters are stable with no abnormal alarms.

2. Monitor that the float charge current remains stable within the normal range with no sustained excessive current.

3. No abnormal temperature rise; cabinet and wiring terminal temperature rise meet requirements.

4. Communication is stable with no frequent disconnections or data jumps.

5. Record final operating parameters and fill in the commissioning record form.

10.7 Commissioning Closing Work

After commissioning is complete:

1. Close the cabinet door, lock it, and clean the construction site.

2. Organize commissioning records, fill in the commissioning report, and record all parameters and test results.

3. Provide simple operational training to on-site operations and maintenance personnel, explaining daily precautions and basic operations.

4. Restore original on-site facilities and confirm no safety hazards before departing.

11.1 Installation Safety Precautions

1. Installation must be carried out by professional electricians, strictly following electrical safety operating procedures. Unlicensed or non-compliant operation is strictly prohibited.

2. Before installation, all related power must be disconnected, warning signs posted, and the “power off, verify no voltage, ground, and tag” lockout procedure must be followed.

3. During work, insulating gloves, goggles, and other protective equipment must be worn, insulated tools must be used, and wearing watches, bracelets, or other metal ornaments is prohibited.

4. It is strictly prohibited to touch both battery positive and negative terminals simultaneously with metal tools, and short-circuiting positive and negative terminals is strictly forbidden. Short circuits generate enormous current that can cause battery burnout, fire, or even explosion.

5. Handle batteries gently when transporting; rolling, dropping, or squeezing batteries is strictly prohibited. Do not pull on terminals, wiring harnesses, or other weak points. For large-capacity batteries, use hydraulic carts or lifting equipment to prevent crushing injuries.

6. Smoking, using open flames, or generating sparks near batteries is prohibited. Suitable fire-fighting equipment must be available on site.

7. Disassembling battery modules and BMS, or dismantling cells, is prohibited. Doing so will void the warranty and create safety risks.

8. Mixing batteries of different models, capacities, manufacturers, or differing age/condition in parallel is strictly prohibited.

9. Storage of flammable or explosive materials near the installation site is prohibited. Maintain good ventilation and keep away from heat sources and direct sunlight.

10. When installing at height, safety harnesses must be worn and tools placed in tool bags to prevent tools from falling and causing injury or short circuits.

11.2 Operational Usage Precautions

1. The battery system must be used within the specified voltage, current, and temperature ranges. Operation beyond rated parameters is strictly prohibited.

2. Modifying BMS protection parameters without authorization is strictly prohibited. Adjustments must be performed under the guidance of manufacturer technical personnel. Improper parameter modification can cause battery damage or safety accidents.

3. If abnormal odor, unusual noise, smoke, swelling, or other phenomena occur during operation, immediately disconnect power, evacuate the area, and contact the manufacturer. Never disassemble the system yourself.

4. Do not place objects on battery equipment or block ventilation openings. Ensure the cooling air path is unobstructed.

5. Regularly check wiring terminals for looseness, overheating, or corrosion, and address issues promptly. After high-current discharge, pay special attention to terminal temperature rise.

6. In humid environments, take moisture protection measures to prevent condensation from degrading insulation. In underground equipment rooms, regularly check for water ingress.

7. For batteries in long-term float charge operation, it is recommended to perform a deep discharge calibration every 3 months to correct SOC error and maintain battery activity.

8. In areas with frequent mains power outages, avoid prolonged undercharge of batteries. After mains power is restored, ensure batteries are fully charged.

9. Connecting other loads in series in the battery circuit is prohibited, and privately connecting other types of batteries or power sources in parallel is prohibited.

10. Pay attention to equipment status during lightning weather. After lightning strikes, check the surge protectors and equipment operating status, replacing damaged components promptly.

11.3 Transportation and Storage Precautions

11.3.1 Transportation Precautions

1. Battery transportation must comply with dangerous goods transport regulations. Choose logistics providers with lithium battery transport qualifications.

2. Before transportation, adjust battery SOC to 30%–50%. Full-charge transportation is strictly prohibited to reduce transport risk.

3. Batteries must be transported in their original packaging, which must be sturdy to prevent collision, compression, and dropping. Stacking layers must comply with packaging requirements, and heavy pressure is prohibited.

4. During transportation, avoid sun exposure and rain, keep away from heat sources and flammable/explosive materials, and ensure the vehicle compartment is well ventilated.

5. Handle gently during loading and unloading. Throwing, rolling, or stepping on batteries is strictly prohibited. Use dedicated lifting slings for hoisting; using steel wire ropes for direct bundling is strictly prohibited.

6. Periodically inspect during transportation. If packaging damage, leakage, overheating, or other abnormalities are found, address them promptly.

7. Mixed transportation with flammable, explosive, or corrosive materials in the same vehicle is strictly prohibited.

11.3.2 Storage Precautions

1. Batteries should be stored in a dry, ventilated, cool warehouse with a recommended ambient temperature of 0°C–35°C and relative humidity ≤ 75%.

2. Keep away from heat sources and ignition sources, avoid direct sunlight, and avoid corrosive gases.

3. During storage, maintain battery SOC at 30%–50%. Recharge every 3 months to prevent over-discharge damage; charging to 50% SOC is sufficient.

4. Batteries should be stored upright. Stacking layers must comply with requirements. Inverted or side placement is prohibited. Placing heavy items on top of batteries is prohibited.

5. Periodically check battery voltage and appearance during storage. If abnormally low voltage, swelling, corrosion, or other abnormalities are found, address them promptly.

6. For batteries stored for more than 6 months, perform one charge/discharge activation cycle before use to restore performance.

7. The warehouse must be equipped with fire-fighting equipment, have comprehensive fire prevention measures, and have an emergency response plan.

11.4 Emergency Handling Precautions

11.4.1 Short Circuit Emergency Handling

1. Immediately disconnect the battery main switch and upstream switch to cut off the fault circuit.

2. Evacuate personnel from the area, maintain ventilation, and observe battery status for heating or smoke.

3. If battery temperature continues to rise with fire risk, immediately call the fire department and evacuate personnel.

4. After the battery has completely cooled, investigate the cause of the short circuit. A professional should assess whether the battery can continue to be used.

5. Reclosing power immediately after a short circuit is strictly prohibited. Restoring operation before identifying the cause is strictly prohibited.

11.4.2 Battery Fire Emergency Handling

1. Immediately cut off all power, evacuate all personnel, and call the fire department (119 in China).

2. Use dry powder fire extinguishers or CO₂ fire extinguishers. Using water directly on a lithium battery fire is strictly prohibited — water reacting with high-temperature cells can intensify combustion.

3. If the fire is small, use a fire blanket to cover and isolate oxygen, and simultaneously bury with large amounts of sand or soil.

4. Maintain ventilation at the scene to prevent accumulation of toxic smoke. Personnel should stand upwind.

5. After the fire is extinguished, the battery may still reignite. Continuous observation for at least 24 hours is required to confirm complete cooling with no reignition risk.

6. Burned batteries must be treated as hazardous waste and handed over to qualified units for disposal. Indiscriminate disposal is strictly prohibited.

11.4.3 Personnel Electric Shock Emergency Handling

1. Immediately cut off power, or use an insulated object to separate the victim from the power source. Directly pulling the victim with bare hands is strictly prohibited.

2. Move the victim to a ventilated area, loosen the collar, and check breathing and heartbeat.

3. If breathing and heartbeat have stopped, immediately perform CPR and call the emergency medical services (120 in China).

4. Preserve the scene, report the accident, and investigate the cause of the electric shock.

11.4.4 Electrolyte Leakage Emergency Handling

LiFePO₄ battery electrolyte is an organic electrolyte. Leakage is typically small in volume. When handling:

1. Wear rubber gloves and goggles to avoid direct skin contact with electrolyte.

2. Use dry cloths or absorbent pads to absorb leaked electrolyte and collect it in a sealed container.

3. Rinse skin with clean water if contacted; if splashed into eyes, immediately rinse with large amounts of clean water for 15 minutes and seek medical attention.

4. Ventilate the leak area to prevent accumulation of electrolyte vapors.

5. Isolate the leaking battery and hand it over to professional personnel for inspection and repair.

12.1 Daily Inspection Standards

Daily inspection is the foundation for timely detection of hidden hazards and ensuring stable battery operation. It is divided into remote inspection and on-site inspection. Daily operations rely primarily on remote inspection, supplemented by periodic on-site inspection and verification.

12.1.1 Daily Remote Inspection (Every Day)

View battery operating status remotely through the dynamic environment monitoring system. Inspection items include:

  • Whether system total voltage and charge/discharge current are within normal ranges;
  • Whether SOC is normal, with no continuous decline or abnormal jumps;
  • Whether maximum cell voltage, minimum cell voltage, and cell voltage differential are normal;
  • Whether maximum temperature and minimum temperature are within normal ranges, with no abnormal temperature rise;
  • Whether there are alarm messages and whether alarms are cleared promptly;
  • Whether communication is normal with no offline or disconnection issues.

Inspection requirements: At least 1 inspection per day; increase frequency for important sites; promptly dispatch work orders for abnormal alarms and arrange on-site troubleshooting; maintain inspection records and establish an operation ledger.

12.1.2 Monthly On-site Inspection

Perform a monthly on-site inspection covering:

Visual Inspection:

  • Cabinet exterior is intact, no deformation, corrosion, or paint peeling; door locks are functional;
  • Cabinet interior is clean, no dust, debris, or standing water;
  • Battery modules are intact in appearance, no swelling, leakage, or deformation; labels are clear;
  • Cables are neatly arranged, no damage or aging, labels clear, and fixation secure.

Connection Inspection:

  • Power terminals are not loose, with no heating or oxidation marks; bolts are tightened;
  • Communication cables and grounding cables are firmly connected with no loose connections;
  • Use an infrared thermometer to measure terminal and busbar temperatures; temperature rise ≤ 30K with no abnormal hot spots.

Status Inspection:

  • Panel indicator lights are normal and consistent with remote monitoring;
  • Fans operate normally (for air-cooled models), no abnormal noise or jamming;
  • Dust screens are clean and unblocked; clean or replace when dirty.

Environmental Inspection:

  • Equipment room temperature and humidity meet requirements with good ventilation;
  • No flammable or explosive materials in the vicinity; ventilation openings are not blocked;
  • Fire-fighting facilities are intact and functional.

Data Verification:

  • Read BMS data on-site and compare with remote monitoring data to ensure accuracy;
  • Record key operating parameters and update the equipment ledger.

12.1.3 Quarterly Maintenance

Perform in-depth maintenance every quarter, adding the following items on top of the monthly inspection:

1. Tightening check: Use a torque wrench to re-tighten all power connection bolts to specified torque, eliminating looseness caused by thermal expansion and contraction.

2. Insulation test: Measure system insulation resistance to confirm good insulation performance with no declining trend.

3. Grounding test: Measure ground resistance and check the reliability of grounding connections.

4. Cleaning and dust removal: Open the cabinet door and use a brush and vacuum cleaner to clean internal dust, focusing on cooling air ducts, fans, and BMS circuit boards. Take anti-static precautions.

5. Alarm test: Test alarm functions by simulating faults to verify alarm upload is functioning normally.

6. Parameter calibration: Compare BMS data with meter measurements; calibrate if deviations are significant.

12.1.4 Annual Maintenance and Service

Perform comprehensive maintenance and performance testing once per year, including:

1. Comprehensive cleaning: Thoroughly clean the cabinet interior and exterior, clean or replace dust screens, and clean cooling air ducts.

2. Comprehensive tightening: Re-torque all electrical connection points; check for oxidation and corrosion; sand and apply conductive grease where necessary.

3. Performance testing:

  • Conduct a capacity verification test to measure actual battery capacity and assess SOH health status;
  • Test cell voltages and internal resistance to assess cell consistency;
  • Test charge/discharge protection functions to verify protection thresholds are accurate and reliable.

4. Function verification: Comprehensively verify all BMS functions, including protection, balancing, communication, and alarms.

5. Hazard investigation: Comprehensively investigate safety hazards, including cable aging, insulation degradation, poor grounding, and inadequate heat dissipation.

6. Software upgrade: Upgrade BMS firmware as needed to optimize performance and functionality.

7. Ledger update: Update equipment ledger, record annual testing data, assess remaining service life, and formulate replacement plans.

12.2 Regular Maintenance Key Points

12.2.1 Charge Maintenance

1. For batteries in long-term float charge operation, perform a deep discharge every 3 months (discharge 30%–50% of capacity), then fully recharge. This activates battery performance, calibrates SOC, and reduces capacity fade.

2. For sites with frequent power outages causing deep discharges, ensure the battery is fully charged before returning to float charge after mains restoration, avoiding prolonged undercharge.

3. Reduce charge current appropriately at low temperatures to avoid lithium plating from high-current charging at low temperatures.

4. Overcharging is prohibited. The float charge voltage must be strictly set according to manufacturer recommendations. Excessive voltage accelerates battery aging and can even cause safety accidents.

12.2.2 Temperature Maintenance

1. Maintain equipment room temperature at 15°C–30°C as optimal. Avoid prolonged high-temperature operation — for every 10°C temperature increase, battery life is halved.

2. During summer high-temperature periods, strengthen ventilation and heat dissipation, check fan operation, and clean cooling passages. In winter low-temperature regions, check that heating functions operate normally.

3. Avoid direct sunlight on the battery cabinet. Outdoor cabinets should have sun-shading measures.

4. Regularly check the accuracy of temperature sensors to prevent temperature detection failure from causing thermal management failure.

12.2.3 Balancing Maintenance

1. Regularly check cell voltage consistency. When cell voltage differential exceeds 80mV, manually initiate balancing and perform a complete equalization charge.

2. After initial installation, after long-term storage and re-use, or after capacity testing, it is recommended to perform a full charge with full equalization to improve consistency.

3. Pay special attention to lagging cells, track them continuously, and replace them promptly if they continue to deteriorate.

12.3 Fault Repair Standards

12.3.1 Repair Safety Principles

1. Repair work must be performed by professional technical personnel familiar with battery structure and principles and proficient in safety operating procedures.

2. Before repair, all power must be disconnected and verified to be de-energized before work begins. High-voltage capacitors must be discharged.

3. During repair, wear insulating protective equipment, use insulated tools, and take anti-static measures.

4. Hot-plugging BMS boards and wiring harnesses while energized is strictly prohibited. Disassembling modules while powered is strictly prohibited.

5. Replacement parts must be original factory parts of the same specification. Use of non-conforming substitutes is strictly prohibited.

6. During repair, maintain insulation protection to prevent short circuits between positive and negative terminals. Tools and parts must be properly placed to prevent falling.

7. After repair, a comprehensive inspection must be performed to confirm no tools are left behind and no wiring errors exist before energizing for testing.

12.3.2 Common Component Repair and Replacement

BMS Main Board Replacement

1. Disconnect the battery main switch, unplug all BMS wiring connectors, and record wiring positions.

2. Remove the mounting screws and take out the old main board.

3. Install the new main board, plug in all wiring harnesses according to the markings, and confirm secure connections.

4. Power on and test to verify all functions are normal; calibrate parameters and address.

Fan Replacement

1. Disconnect fan power, remove mounting screws, and take out the old fan.

2. Install the new fan, ensuring correct airflow direction and wiring connections.

3. Power on and test that the fan operates normally with no abnormal noise.

Fuse/Circuit Breaker Replacement

1. Disconnect upstream power and verify de-energized.

2. Remove the damaged component and replace with a new component of the same specification and model.

3. Tighten connections and test on/off function.

Single Cell Replacement

1. Cell replacement must be performed under manufacturer guidance and requires professional equipment and processes.

2. Before replacement, discharge the entire pack to a safe voltage and disconnect all connections.

3. Remove the faulty cell and replace with a new cell of the same model, capacity, and SOC.

4. Reconnect busbars and sense wires, ensuring reliable connections.

5. After installation, perform an equalization charge to match the new cell with the rest of the pack.

12.3.3 Post-repair Acceptance

1. After repair completion, conduct functional tests to verify the fault is eliminated and all parameters are normal.

2. Conduct a trial run of no less than 30 minutes to confirm stable operation with no abnormal alarms.

3. Check that appearance and wiring are restored to original condition with no hidden hazards.

4. Fill in repair records, documenting fault cause, repair content, replaced components, and test results; store in the equipment ledger.

12.4 Scrapping and Recycling

1. When battery capacity decays below 80% of rated capacity, or in cases of serious faults that cannot be repaired, the battery should be scrapped.

2. Scrapped batteries must not be discarded arbitrarily. LiFePO₄ batteries are classified as general industrial solid waste and must be handed over to qualified recycling enterprises for processing.

3. Before transportation, scrapped batteries should be discharged to below 30% SOC, with positive and negative terminals insulated to prevent short circuits during transport.

4. Privately dismantling scrapped batteries, disposing of them in household waste, or throwing them into fire is strictly prohibited.

13.1 Electrical Faults

Fault Symptom Possible Causes Troubleshooting Steps Solutions
Battery system has no output voltage, indicator lights off 1. Battery main switch not closed or damaged<br>2. Internal fuse blown<br>3. BMS power circuit fault<br>4. Severe over-discharge causing BMS undervoltage protection 1. Check main switch position, measure switch input/output voltage<br>2. Check fuse continuity<br>3. Measure total cell voltage to determine over-discharge<br>4. Check BMS power wiring 1. Close main switch; replace if damaged<br>2. Investigate short circuit cause, then replace fuse<br>3. Repair BMS power circuit<br>4. Use low-current activation charging to restore voltage
No charging current, cannot charge 1. Charge circuit open, switch not closed<br>2. BMS overcharge protection activated<br>3. Low-temperature protection, temperature below charge threshold<br>4. Charge voltage lower than battery voltage<br>5. BMS charging MOSFET damaged 1. Check charge switch and wiring continuity<br>2. Read BMS status, check for overcharge alarm<br>3. Check if battery temperature is below 0°C<br>4. Measure charger output voltage and battery voltage<br>5. Measure charging MOSFET drive and continuity 1. Close switch, repair wiring<br>2. Automatically recovers after voltage drops, or manual reset<br>3. Automatically recovers after temperature rises; activate heating<br>4. Adjust charger voltage to correct value<br>5. Replace BMS or MOSFET
No discharge output, cannot support load 1. Discharge switch not closed or poor contact<br>2. BMS over-discharge protection activated<br>3. Overcurrent/short circuit protection triggered<br>4. Load short circuit or overload<br>5. Discharge MOSFET damaged 1. Check discharge switch and wiring<br>2. Measure cell voltages, check for undervoltage<br>3. Check BMS fault records for overcurrent protection<br>4. Check if load has short circuit or power exceeds rating<br>5. Measure discharge MOSFET status 1. Close switch, tighten wiring<br>2. Automatically recovers after charging<br>3. Clear fault, then manual or automatic reset<br>4. Eliminate load fault, reduce load power<br>5. Replace BMS or MOSFET
Float charge current too high 1. Float charge voltage set too high<br>2. Battery SOC low, in replenishment charging phase<br>3. High battery self-discharge or internal micro short circuit<br>4. Poor cell consistency, some cells overcharging 1. Verify float charge voltage setting<br>2. Check SOC value to determine if in replenishment<br>3. Observe voltage drop rate after rest<br>4. Check cell voltages for individual high cells 1. Adjust float charge voltage to recommended 54.0V<br>2. Current naturally decreases after full charge — normal phenomenon<br>3. Test cells; replace module if micro short circuit<br>4. Activate balancing to improve consistency
Large cell voltage differential 1. Factory cell consistency deviation<br>2. Balance not activated during long-term float charge<br>3. Some cells have high self-discharge<br>4. Uneven temperature distribution<br>5. Balancing circuit fault 1. Check individual cell voltage values<br>2. Check if balancing function is enabled and balance parameters set<br>3. Test self-discharge rate of each cell after rest<br>4. Measure temperature at various positions<br>5. Test whether balancing circuit works properly 1. Perform one complete equalization charge<br>2. Enable automatic balancing, adjust balance threshold<br>3. Cells with excessive self-discharge need replacement<br>4. Optimize heat dissipation for temperature uniformity<br>5. Repair or replace BMS balancing circuit
SOC display inaccurate, jumping 1. BMS SOC cumulative error<br>2. Long-term no full-charge calibration<br>3. Large current sampling deviation<br>4. Poor cell consistency<br>5. Large temperature variation 1. Check SOC jump amplitude and frequency<br>2. Check last full charge time<br>3. Calibrate current sampling<br>4. Check cell voltage differential<br>5. Check ambient temperature variation 1. Perform one complete charge/discharge to calibrate SOC<br>2. Regularly perform full charge calibration<br>3. Calibrate current sensor<br>4. Improve cell consistency<br>5. Algorithm auto-compensation — normal phenomenon

13.2 Communication Faults

Fault Symptom Possible Causes Troubleshooting Steps Solutions
RS485 communication not working, no monitoring data 1. Communication wires reversed, broken, or shorted<br>2. Communication parameters mismatch (baud rate, address, protocol)<br>3. BMS communication module damaged<br>4. Monitoring device fault<br>5. Severe interference causing communication abnormality 1. Measure communication wire continuity, verify A/B polarity<br>2. Verify communication parameter settings on both ends<br>3. Connect test device directly to battery to determine if BMS side is normal<br>4. Check monitoring device communication port<br>5. Check if running parallel with power cables, whether shielded 1. Wire correctly, repair breaks and shorts<br>2. Unify communication parameters<br>3. Replace BMS communication module<br>4. Repair monitoring device<br>5. Ground shielding layer, keep away from power cables, add ferrite cores
Intermittent communication, data packet loss 1. Poor wire contact<br>2. Communication distance too long or too many nodes<br>3. Electromagnetic interference<br>4. Termination resistor mismatch<br>5. Power supply fluctuation 1. Check terminal connections for looseness<br>2. Measure bus length and node count<br>3. Observe interference pattern, whether synchronized with high-power equipment start/stop<br>4. Check termination resistor configuration<br>5. Measure BMS supply voltage stability 1. Tighten terminal connections<br>2. Add repeaters, reduce nodes<br>3. Improve shielding and grounding, separate wiring<br>4. Add 120Ω termination resistors at both bus ends<br>5. Stabilize power supply
Dry contact alarm no output 1. Alarm wiring disconnected<br>2. BMS alarm relay damaged<br>3. Alarm threshold improperly set, not triggered<br>4. Alarm type configuration error<br>5. Monitoring end acquisition circuit fault 1. Measure alarm wire continuity<br>2. Simulate fault, measure relay contact continuity<br>3. Check alarm threshold settings, simulate fault test<br>4. Verify alarm output definitions<br>5. Check monitoring end acquisition circuit and power supply 1. Repair alarm wiring<br>2. Replace BMS relay output circuit<br>3. Adjust alarm thresholds to reasonable values<br>4. Correctly configure alarm output type<br>5. Repair monitoring end acquisition circuit
Parallel group communication abnormal 1. Parallel communication wire disconnected or reversed<br>2. Device address conflict<br>3. Software version inconsistency<br>4. Termination resistor configuration error 1. Check parallel communication wiring<br>2. Check if each device address is unique<br>3. Check software versions of each unit<br>4. Check head/tail termination resistors 1. Connect communication wires correctly<br>2. Change to unique addresses<br>3. Upgrade all to the same version<br>4. Enable termination resistors on first and last units, disable on middle units

13.3 Temperature and Thermal Management Faults

Fault Symptom Possible Causes Troubleshooting Steps Solutions
Battery temperature too high alarm 1. High ambient temperature<br>2. Long duration high-current charge/discharge<br>3. Cooling fan failure, poor heat dissipation<br>4. Ventilation openings blocked, air path obstructed<br>5. High contact resistance, terminal heating<br>6. Temperature sensor fault, false alarm 1. Measure ambient temperature<br>2. Check charge/discharge current magnitude and duration<br>3. Check if fan is running and speed is normal<br>4. Check if dust screen and ventilation openings are blocked<br>5. Use infrared thermometer on terminals and busbars<br>6. Compare actual measured temperature with displayed temperature 1. Reduce ambient temperature, strengthen equipment room ventilation<br>2. Reduce charge/discharge current; resumes after temperature drops<br>3. Replace faulty fan<br>4. Clean dust screen and ventilation openings<br>5. Tighten terminals, treat oxidation<br>6. Replace temperature sensor, calibrate temperature
Fan not spinning or abnormal noise 1. Fan power supply fault<br>2. Fan motor damaged<br>3. Temperature not reaching start threshold<br>4. Fan bearing worn or lack of lubrication<br>5. Excessive dust, blade jammed 1. Measure fan supply voltage<br>2. Direct power test whether fan operates<br>3. Check temperature value and fan start threshold<br>4. Listen to noise type to determine bearing fault<br>5. Clean dust, check blade rotation 1. Repair fan power circuit<br>2. Replace fan<br>3. Automatically starts when temperature reaches threshold — normal<br>4. Replace fan bearing or entire fan<br>5. Clean dust, lubricate bearings
Cannot charge at low temperature 1. Low-temperature charge protection activated<br>2. Heating system fault, temperature cannot rise<br>3. Temperature sensor fault, reading low<br>4. Ambient temperature too low, outside operating range 1. Check BMS for low-temperature protection alarm<br>2. Check if heating pad heats up and power supply is normal<br>3. Compare actual battery temperature with displayed value<br>4. Measure ambient temperature 1. Automatically recovers after temperature rises — normal protection<br>2. Repair heating system; replace heating pad or power supply<br>3. Replace temperature sensor<br>4. Implement additional insulation and heating measures
Abnormal temperature display, value jumping 1. Temperature sensor poor contact<br>2. Sensor damaged<br>3. BMS sampling circuit fault<br>4. Electromagnetic interference 1. Check sensor wiring connector<br>2. Measure sensor resistance value<br>3. If still abnormal after sensor replacement, check sampling circuit<br>4. Observe whether affected by interference 1. Reconnect wiring to ensure good contact<br>2. Replace NTC temperature sensor<br>3. Repair or replace BMS<br>4. Improve shielding and anti-interference

13.4 Structural and Appearance Faults

Fault Symptom Possible Causes Troubleshooting Steps Solutions
Battery module swelling/deformation 1. Overcharge causing internal gas generation<br>2. High-temperature aging causing gas generation<br>3. Internal micro short circuit causing gas generation<br>4. Manufacturing defect 1. Check swelling degree, measure thickness change<br>2. Check historical operation data for overcharge or overtemperature<br>3. Measure self-discharge rate<br>4. Confirm if within warranty period 1. Slight swelling with capacity meeting spec can continue observation<br>2. Severe swelling: immediately stop use and replace module<br>3. Investigate overcharge cause, correct charging parameters<br>4. Contact manufacturer for replacement if within warranty
Terminal heating, oxidation 1. Loose connection bolts, high contact resistance<br>2. Terminal surface oxidation, poor contact<br>3. Long-term high-current operation<br>4. Terminal specification mismatch 1. Check bolt tightening torque<br>2. Observe if terminal surface is oxidized or blackened<br>3. Check operating current magnitude<br>4. Verify terminal and cable specifications 1. Tighten bolts to specified torque<br>2. Sand oxidation layer, apply conductive grease; replace terminal if severe<br>3. Reduce current or upgrade terminal specification<br>4. Replace with matching specification terminals
Cabinet water leakage, dust ingress 1. Sealing strip aged or fallen off<br>2. Cable entry holes not sealed<br>3. Cabinet deformation, door gap not tight<br>4. Ventilation dust screen damaged 1. Check seal integrity and elasticity<br>2. Check cable gland sealing<br>3. Check cabinet for deformation and door gap<br>4. Check dust screen integrity 1. Replace sealing strips<br>2. Re-seal, tighten cable glands<br>3. Correct cabinet deformation, adjust door lock<br>4. Replace dust screen

13.5 System-level Comprehensive Faults

Fault Symptom Possible Causes Troubleshooting Steps Solutions
Short battery backup time, insufficient capacity 1. Battery not fully charged, low float charge voltage<br>2. Battery aging, capacity fade<br>3. Poor cell consistency, short-board effect<br>4. Low ambient temperature, capacity reduction<br>5. Load power exceeds design value<br>6. BMS SOC estimation error 1. Check charging parameters, confirm adequate charging<br>2. Check years of service, perform capacity test<br>3. Check cell voltages; check if any cell reaches cutoff voltage first during discharge<br>4. Confirm ambient temperature<br>5. Measure actual load power<br>6. Calibrate SOC 1. Adjust charging parameters, ensure full charge<br>2. Replace battery if capacity below 80%<br>3. Balance optimization; replace lagging cells if severe<br>4. Normal at low temperature; increase capacity or add heating<br>5. Expand battery pack to match load<br>6. Perform charge/discharge calibration for SOC
Frequent tripping, protection frequently activated 1. Load short circuit or leakage fault<br>2. Protection threshold set too low<br>3. Large load starting surge<br>4. BMS protection false activation 1. Check load and line insulation, troubleshoot short circuits<br>2. Check protection threshold settings<br>3. Measure starting current peak<br>4. Simulate tests to verify protection accuracy 1. Eliminate load and line faults<br>2. Reasonably adjust protection thresholds<br>3. Add soft-start or reduce starting current<br>4. Calibrate BMS protection parameters or replace
Poor current sharing in parallel system, uneven group currents 1. Inconsistent cable length and gauge between groups<br>2. Inconsistent voltage and SOC between groups<br>3. Parallel communication fault<br>4. Large internal resistance differences between groups 1. Check cable specifications and lengths of each branch<br>2. Measure open-circuit voltage and SOC of each group<br>3. Check if parallel communication is normal<br>4. Measure internal resistance of each group 1. Standardize cable specifications and lengths to reduce line impedance differences<br>2. Equalize charge to the same voltage before paralleling<br>3. Repair parallel communication<br>4. Replace battery groups with poor consistency

14.1 Basic Knowledge

Q1: What advantages do base station-specific LiFePO₄ batteries have compared to lead-acid batteries?

A: Compared to traditional lead-acid batteries, LiFePO₄ batteries offer advantages in six main areas: First, longer lifespan — cycle life is 8–10 times that of lead-acid, float charge life is 2–3 times, with lower total lifecycle cost. Second, higher energy density — volume and weight are only 1/2 to 1/3 of lead-acid, saving space and reducing load requirements. Third, stronger temperature adaptability — normal operation from -10°C to 55°C, far exceeding lead-acid high/low-temperature performance. Fourth, higher efficiency — charge/discharge conversion efficiency ≥ 95%, saving energy. Fifth, maintenance-free — no water refilling, acid density testing, or periodic equalization charging required; maintenance workload reduced by 80%. Sixth, environmentally friendly — no heavy metals, no acid mist pollution.

Q2: Are LiFePO₄ batteries safe? Can they catch fire or explode?

A: LiFePO₄ material itself has excellent thermal stability with a decomposition temperature exceeding 500°C. Unlike NCM/NCA lithium materials, it does not release oxygen at high temperatures through decomposition, providing inherent intrinsic safety. Additionally, products incorporate multiple layers of safety protection from cell, BMS, structure, to system levels, including overcharge, over-discharge, overcurrent, and short-circuit protection, temperature protection, explosion-proof valves, and flame-retardant housings. Under normal use and standard maintenance, they are very safe. As long as installation and use strictly follow the manual, avoiding improper operation and extreme abuse, the risk of fire or explosion is extremely low.

Q3: What is the relationship between the rated 48V and the 51.2V battery voltage?

A: The conventional -48V in the telecommunications industry is the system nominal voltage. A 16-series LiFePO₄ battery has a nominal cell voltage of 3.2V, giving a total nominal voltage of 51.2V. The float charge voltage is approximately 54V, and the discharge cutoff voltage is approximately 40V. The entire operating voltage range covers the -48V system operating window and is fully compatible with existing telecommunications -48V power systems, allowing direct replacement of lead-acid batteries.

Q4: Can LiFePO₄ batteries directly replace existing lead-acid batteries? Does the switching power supply need to be modified?

A: Yes, direct replacement is possible. This product’s output voltage, interface dimensions, and installation method are all compatible with traditional lead-acid battery systems. The switching power supply requires no hardware modification — only charging parameters (float charge voltage, equalize charge voltage, charge current limit) need to be adjusted to match lithium battery characteristics. Some intelligent switching power supplies can directly select lithium battery mode for simple switching.

Q5: What does a 6000-cycle battery life mean? How many years can it be used in a base station?

A: The 6000-cycle life refers to the number of cycles at 25°C, 1C charge/discharge, 80% depth of discharge, with capacity retention ≥ 80%. Base station backup power supplies normally remain in float charge standby and discharge infrequently — this is a float charge application mode with a design float charge life of ≥ 10 years. In areas with frequent power outages where discharge cycles occur more often annually, actual lifespan will correspondingly shorten but still far exceeds lead-acid batteries.

14.2 Installation and Wiring

Q6: What happens if the positive and negative terminals are reversed during installation? How can this be avoided?

A: Reverse polarity connection will directly damage the BMS protection board and, in severe cases, cause battery short circuit or fire. This is an extremely dangerous non-compliant operation. Avoidance methods: First, repeatedly verify polarity markings before wiring — both battery and power supply sides have clear positive/negative markings. Second, implement a dual-person review system — one person wires while another checks. Third, use a multimeter to measure polarity at both ends before connecting. Fourth, connect one side first, then measure voltage polarity on the other side before connecting.

Q7: What should be noted when paralleling multiple battery groups? What is the maximum number of parallel groups?

A: Parallel batteries must satisfy the “five-identical principle”: same manufacturer, same model, same capacity, same batch, same age/condition. Mixing different types of batteries in parallel is strictly prohibited. Standard models support a maximum of 8 groups in parallel. When paralleling, minimize cable length and ensure consistent cable length and gauge for all branches to achieve good current sharing. Parallel communication wires should be connected in series for coordinated management. Each group should be equipped with an independent circuit breaker for convenient single-group maintenance.

Q8: Is the grounding wire mandatory? Can it be omitted?

A: Reliable grounding is mandatory. Grounding is an important measure for ensuring personnel safety and equipment safety: First, protective grounding prevents electric shock from energized equipment enclosures. Second, working grounding maintains DC system potential stability. Third, lightning protection grounding discharges lightning currents to protect equipment from lightning damage. Operating without grounding poses electric shock risks, reduced equipment anti-interference capability, and lightning protection failure — operating without grounding is strictly prohibited.

Q9: Can the battery be installed outdoors? Will rainwater enter during rainy weather?

A: Outdoor models have an IP55 protection rating for dust and water jet protection and can be directly installed outdoors under normal environmental conditions, functioning normally in rain without water ingress. However, installation must ensure cable entry points are sealed, cabinet doors are fully closed, and sealing strips are intact. The unit cannot be submerged in water — in low-lying areas, install on raised platforms to avoid flooding. Indoor models cannot be installed outdoors and will suffer water damage.

14.3 Commissioning and Operation

Q10: What float charge voltage should be set on the switching power supply? What happens if set too high?

A: The recommended float charge voltage is 54.0V, which can be adjusted slightly based on ambient temperature — reduce by 0.2–0.3V in high-temperature environments. If float charge voltage is set too high, the battery will be in a prolonged overcharge state, accelerating electrolyte decomposition and cell aging. In severe cases, internal gas generation and swelling will occur, shortening lifespan and potentially causing safety accidents. If set too low, the battery will not charge fully, resulting in insufficient capacity and shortened backup time.

Q11: Why does the SOC display not show 100% for a newly installed battery?

A: Factory batteries are typically shipped at 30%–50% SOC for transportation and storage convenience, so it is normal for SOC not to be 100% upon initial installation. After connecting to the switching power supply, the battery will automatically charge, and SOC will display 100% when fully charged. It is recommended to perform one complete charge after installation before placing the battery into formal operation.

Q12: Will a battery deteriorate if unused for a long time? How should it be stored?

A: Long-term storage involves self-discharge, and excessive discharge can damage cells. Storage precautions: First, maintain SOC at 30%–50% — neither fully charged nor fully discharged storage. Second, store in a 0°C–35°C dry, ventilated environment, avoiding high and low temperatures. Third, recharge every 3 months to prevent over-discharge. Fourth, store upright, avoiding compression and impact. For batteries stored more than 6 months, perform one charge/discharge activation cycle before use.

Q13: How long can the battery support the load during a power outage? How is backup time calculated?

A: Backup time = Total battery energy × Discharge efficiency / Load power. For example, a 48V100Ah battery has total energy of 5.12kWh, discharge efficiency 0.95, and load power 1kW, giving backup time of approximately 5.12 × 0.95 ÷ 1 ≈ 4.8 hours. Actual backup time is affected by load size, ambient temperature, battery aging, and depth of discharge. Lower temperatures and larger loads result in shorter backup times.

Q14: What is a normal cell voltage differential as displayed by the BMS? What impact does an excessive differential have?

A: Under normal static conditions, cell voltage differential should be ≤ 50mV; under discharge conditions, ≤ 100mV is considered good. An excessive voltage differential indicates poor cell consistency, resulting in the “short-board effect” where total pack capacity is determined by the weakest cell. This causes a reduction in overall usable capacity and shortened cycle life. In severe cases, individual cells may experience overcharge or over-discharge, leading to faults.

14.4 Maintenance and Care

Q15: Do LiFePO₄ batteries require periodic equalization charging?

A: No, they do not require periodic equalization charging like lead-acid batteries. LiFePO₄ batteries have no memory effect, and normal float charging is sufficient to maintain a fully charged state. However, it is recommended to perform a deep discharge followed by a full charge every 3 months to calibrate the SOC and activate the battery cells, while also promoting cell balancing to maintain consistency. This differs fundamentally from lead-acid equalization charging.

Q16: What routine maintenance work is required? Is it troublesome?

A: Routine maintenance is very simple, primarily consisting of remote monitoring of data to check whether voltage, temperature, SOC, and alarms are normal; a monthly on-site inspection to check appearance, wiring, temperature, and clean dust; quarterly tightening and deep inspection; and an annual capacity test. Compared to lead-acid batteries which require water topping-up, acid density measurement, and frequent equalization charging, the maintenance workload for lithium batteries is extremely small, truly achieving maintenance-free operation.

Q17: Can the battery be rinsed with water if it gets dirty?

A: No. The battery contains electronic components and circuits internally. Rinsing with water can cause short circuits, corrosion, and equipment damage. For cleaning, use a dry cloth or a wrung-out damp cloth to wipe surface dust. For internal dust, use a soft brush combined with a vacuum cleaner. The outdoor cabinet surface can be wiped with a neutral cleaning agent; avoid organic solvents.

Q18: At what capacity level should the battery be replaced?

A: When the actual battery capacity decays to below 80% of its rated capacity, replacement is recommended. At this point, the backup time will be significantly reduced and can no longer meet backup power requirements. Continued use will accelerate the rate of decay, deteriorate cell consistency, and increase the risk of failure. For general sites where backup time requirements are not stringent, the threshold may be relaxed to 70%, but enhanced monitoring is required.

14.5 Safety and Emergency Response

Q19: What type of fire extinguisher should be used for battery fires? Can water be used?

A: For lithium battery fires, dry powder fire extinguishers or CO₂ fire extinguishers are recommended. Fire blankets or large quantities of sand/soil can also be used for smothering. Direct water application is strictly prohibited, as water reacts with high-temperature lithium cells, producing hydrogen gas which can intensify combustion or even cause an explosion. In the event of a large-scale battery fire, prioritize personnel evacuation, call the fire department, and leave the response to professional firefighters.

Q20: Can a battery with a swollen/bulging case still be used?

A: For slight swelling where capacity remains normal and no other abnormalities are present, continued use is acceptable, but monitoring must be intensified, inspection intervals shortened, and the swelling observed for any progression. If the swelling is severe (thickness increase exceeding 5%), capacity is noticeably reduced, accompanied by high self-discharge or abnormal temperature, the battery must be immediately taken out of service and replaced to prevent further deterioration that could lead to a safety incident.

Q21: Is battery electrolyte leakage toxic? What should be done if it contacts skin?

A: The electrolyte in LiFePO₄ batteries is an organic carbonate-based electrolyte, which has a certain degree of irritation and toxicity, though the quantity is small. If skin contact occurs, immediately rinse with copious amounts of clean water. If splashed into eyes, rinse immediately with clean water for 15 minutes and seek medical attention. If vapor is inhaled, quickly leave the area and move to fresh air. Batteries with leakage should be taken out of service and properly disposed of, avoiding extensive contact.

Chapter 15 Product Acceptance

15.1 Factory Acceptance

Factory Acceptance Testing (FAT) is the acceptance performed after production is completed at the factory and before shipment. It is executed by the manufacturer’s quality inspection department, and customers may send representatives to witness the process.

15.1.1 Factory Acceptance Items

Appearance and Structural Inspection: Verify that product appearance, markings, structural dimensions, and mounting dimensions conform to standards and order requirements; the surface is free of defects; and the structure is robust.

Electrical Performance Testing:

  • Open-circuit voltage test: Total voltage and individual cell voltages are within normal range, and consistency meets requirements;
  • Insulation resistance test: Insulation resistance between live parts and enclosure ≥ 10 MΩ;
  • Withstand voltage test: AC 1500V/1min without breakdown or arcing;
  • Charge/discharge test: Constant current charging, constant voltage charging, and discharge functions operate normally, with accurate protection actions.

Functional Testing:

  • BMS protection function test: Verification of overcharge, over-discharge, overcurrent, short circuit, over-temperature, and low-temperature protection;
  • Balancing function test: Verification of normal balancing circuit operation;
  • Communication function test: Data transmission on all communication interfaces is normal, and protocols are correct;
  • Alarm function test: All alarm output levels operate normally.

Safety Performance Sampling: Batch products undergo proportional sampling of safety performance tests, such as short circuit and overcharge tests, to ensure safety compliance.

Documentation and Accessories Inspection: Verify that random documentation and accessories are complete and conform to the packing list requirements.

15.1.2 Factory Acceptance Criteria

All items must comply with the YD/T 2344.1-2023 standard and the product technical specification requirements. Upon passing inspection, a factory inspection report and product certificate of conformity are issued. Non-conforming products are returned for rework and repair, and must pass re-inspection before shipment.

15.2 Delivery Acceptance

After the equipment arrives at the site, the purchaser, contractor, and manufacturer jointly conduct delivery acceptance.

15.2.1 Acceptance Contents

Packaging Inspection: Check whether the outer packaging is intact, with no damage, water immersion, or impact marks; transport markings are clear.

Quantity Verification: Check the model numbers and quantities of the main unit, accessories, and documentation against the contract order and packing list.

Appearance Inspection: Check the equipment appearance for transit damage, deformation, paint chipping, corrosion, and interface damage.

Preliminary Electrical Acceptance: Measure open-circuit voltage; verify correct polarity, no short circuits, and voltage within normal range.

Documentation Acceptance: Verify that the product certificate of conformity, factory inspection report, instruction manual, and other technical documentation are complete.

15.2.2 Acceptance Procedure

1. Three parties (purchaser, contractor, manufacturer) are present to jointly conduct unpacking and inspection;

2. Check and verify item by item, and fill in the delivery acceptance record form;

3. Upon passing acceptance, all parties sign for confirmation, and the installation phase begins;

4. If defects, damage, or model discrepancies are found, record and photograph them, then contact the manufacturer for replacement or replenishment.

15.3 Installation Acceptance

After installation and wiring are completed, installation quality acceptance is conducted prior to commissioning.

15.3.1 Acceptance Items

Installation Position and Layout: Conforms to design drawing requirements; accurate positioning; reasonable layout; sufficient space for operation and maintenance.

Installation Firmness: Equipment is securely fixed; bolts are complete and tightened; levelness and verticality conform to standards.

Cabling Workmanship: Cables are laid out neatly, tied securely, and labeled clearly; bending radii meet requirements; power cables and signal cables are routed separately.

Wiring Quality: Terminal crimping is to specification; bolt tightening torque meets requirements; polarity is correct; contact is good; insulation protection is in place.

Grounding System: Protective grounding, working grounding, and lightning protection grounding are correctly and reliably connected; grounding resistance meets design requirements.

Labeling and Protection: Equipment labels, warning signs, and cable tags are complete and legible; safety protection measures are in place.

Site Environment: Construction site is cleaned up with no leftover debris; ventilation and heat dissipation conditions meet requirements.

15.3.2 Acceptance Criteria

Strictly implemented in accordance with DL/T 5892-2024 “Code for Construction and Acceptance of Battery Systems in Electrical Installation Engineering” and engineering design requirements. All items must pass before proceeding to the commissioning phase.

15.4 Commissioning Acceptance

After system commissioning is completed, commissioning acceptance is conducted to verify that system functions and performance meet the requirements.

15.4.1 Acceptance Items

No-load Operation Acceptance: System operates normally under no-load conditions; indicator light statuses are correct; all parameter displays are normal; no alarms.

Charging Function Acceptance:

  • Constant current charging and constant voltage float charging transitions operate normally;
  • Charging current and voltage conform to design values;
  • Float charging current remains stable within normal range;
  • No abnormal alarms during charging process; individual cell voltages and temperatures are normal.

Discharge Function Acceptance:

  • Discharge switching is smooth with no power interruption impact;
  • Discharge voltage is stable with good platform characteristics;
  • Low voltage alarm and over-discharge protection operate accurately and reliably;
  • Temperature and temperature rise during discharge meet requirements.

Protection Function Acceptance: Overcharge, over-discharge, overcurrent, short circuit, over-temperature, and low-temperature protection functions all operate normally; protection thresholds are accurate; actions are reliable.

Communication and Monitoring Acceptance:

  • Communication with the switching power supply is normal, with accurate data;
  • Integration testing with the environment monitoring system (DCIM) is successful; all telemetry and tele-signaling points are uploaded correctly;
  • Alarm reporting is timely and accurate; remote monitoring function operates normally.

Capacity Acceptance: For critical sites, capacity testing is performed; actual capacity ≥ 100% of rated capacity (at 25°C).

Parallel Operation Acceptance: Current sharing in parallel systems is good; current distribution error ≤ 5%; failure of a single group does not affect overall system operation.

15.4.2 Acceptance Procedure

1. The contractor completes self-inspection and submits commissioning records and acceptance application;

2. The construction unit, supervision unit, and manufacturer jointly conduct on-site acceptance;

3. Test items are verified one by one according to the acceptance items, with acceptance data recorded;

4. All items pass, and the commissioning acceptance report is signed;

5. If problems exist, rectification is completed within a specified period, followed by re-acceptance.

15.5 Completion Acceptance

After the overall project is completed, the final completion acceptance is conducted. This is the final stage of project delivery.

15.5.1 Acceptance Documentation

Complete completion documentation must be submitted for completion acceptance, including:

  • Project completion description;
  • Commencement report and completion report;
  • Unpacking inspection records, installation records, commissioning records;
  • Factory inspection report, product certificate of conformity, product instruction manual;
  • System wiring diagrams, layout plans, design change documents;
  • Test reports: insulation test, grounding test, capacity test reports;
  • Acceptance certificates, handover lists;
  • Operation and maintenance training records.

15.5.2 Acceptance Procedure

1. The contractor submits completion documentation and acceptance application;

2. The construction unit organizes an acceptance team to review the completion documentation;

3. Conduct on-site spot checks of system operation and re-verify key performance indicators;

4. Provide operational training and handover to operation and maintenance personnel;

5. Upon passing acceptance, sign the completion acceptance certificate and formally hand over for service;

6. Enter the warranty period; the manufacturer provides warranty services as specified in the contract.

15.6 Acceptance Determination Criteria

  • All acceptance items pass and documentation is complete and comprehensive — acceptance is deemed qualified;
  • General items have minor defects that do not affect safety or operation — rectified within a specified period and re-inspected;
  • Key items fail, such as safety performance not meeting standards, insufficient capacity, or protection failure — acceptance is deemed unqualified, requiring rework and rectification followed by re-acceptance;
  • The acceptance process shall be documented, with all parties signing for confirmation, serving as the basis for project delivery and settlement.

Chapter 16 SEO Optimization System and Keyword Layout

16.1 Search Keyword Classification Layout

16.1.1 Core Primary Keywords

Base station dedicated LiFePO₄ battery, LiFePO₄ battery for base stations, base station LiFePO₄ battery, 48V LiFePO₄ battery, communication base station LiFePO₄ battery

16.1.2 High-Conversion Long-Tail Keywords

Base station dedicated LiFePO₄ battery installation manual, base station LiFePO₄ battery wiring and commissioning specification, 48V 100Ah base station LiFePO₄ battery parameters, communication base station backup power LiFePO₄ battery, outdoor base station dedicated LiFePO₄ battery cabinet, macro base station LiFePO₄ battery configuration solution, base station LiFePO₄ battery maintenance manual, base station lithium battery installation wiring tutorial

16.1.3 Industry Traffic Keywords

Communication LiFePO₄ battery pack, 5G base station backup power lithium battery, base station energy storage lithium battery, communication room LiFePO₄ battery, tower base station lithium battery, -48V communication lithium battery, base station standby power lithium battery, base station second-life LiFePO₄ battery

16.1.4 Brand-Specific Keywords

Guangdong Lai’an LiFePO₄ battery, Lai’an base station lithium battery, Lai’an intelligent equipment room lithium battery, Guangzhou Lai’an LiFePO₄ battery, lain base station dedicated battery, Lai’an 48V LiFePO₄ battery

16.1.5 Dropdown/Related Search Keywords

Base station LiFePO₄ battery installation method, how to wire base station LiFePO₄ battery, base station LiFePO₄ battery commissioning steps, base station LiFePO₄ battery service life in years, difference between base station LiFePO₄ battery and lead-acid battery, base station LiFePO₄ battery float charging voltage setting, common base station LiFePO₄ battery faults, base station LiFePO₄ battery acceptance criteria

16.2 SEO Optimization Tag System

16.2.1 Page Core Optimization Tags

Page Core Theme: Base station dedicated LiFePO₄ battery installation, wiring, and commissioning manual

Core Optimization Direction: Cover the full technical process of base station lithium battery installation, wiring, commissioning, maintenance, and acceptance; meet the technical query needs of communication engineering and operation-maintenance personnel; create a high-value technical documentation page.

16.2.2 Title Tag

Base Station Dedicated LiFePO₄ Battery Installation Wiring Commissioning Manual_48V Communication Base Station Lithium Battery Parameters_Guangdong Lai’an Intelligent Equipment Room

16.2.3 Meta Keywords

Base station dedicated LiFePO₄ battery, base station LiFePO₄ battery installation, 48V LiFePO₄ battery wiring and commissioning, communication base station lithium battery, base station backup power lithium battery, LiFePO₄ battery technical parameters, base station lithium battery maintenance, Guangdong Lai’an lithium battery

16.2.4 Meta Description

Guangdong Lai’an Intelligent Equipment Room provides professional base station dedicated LiFePO₄ batteries. This manual details the product principles, technical parameters, installation wiring, commissioning and operation, maintenance, fault troubleshooting, and acceptance specifications of 48V communication base station LiFePO₄ batteries. Suitable for macro base stations, micro base stations, and various other communication scenarios, compliant with YD/T industry standards, providing a one-stop solution for the complete base station lithium battery installation, operation, and maintenance process.

16.2.5 H1 Tag

Base Station Dedicated LiFePO₄ Battery Installation Wiring Commissioning Manual

16.2.6 H2 Tags

Product Introduction, Product Composition, Product List, Product Working Principle, Product Technical Parameters, Product Functions and Features, Product Application Scenarios, Product Installation, Product Wiring, Product Commissioning, Product Precautions, Product Repair and Maintenance, Product Common Problems and Solutions, Product FAQ