ToggleKITOZER KTR-BAT100 VRLA Battery 12V 100Ah (Maintenance-Free)
Brand: KITOZER Series: KTR-BAT100 Category: Power Distribution / VRLA Battery
12V100Ahmaintenance-freeVRLA/AGMUPS batteryKTR-BAT100
1. Overview
UPS, DC switchboards and telecom shelters ride out outages on batteries — 12V100Ah is the most common size. Four cells make 48V telecom strings; 32~40 cells make 384~480 V DC for UPS, riding through 15~30 minutes of backup. VRLA valve-regulated lead-acid batteries dominate due to being maintenance-free, safe and low-cost.
The KITOZER KTR-BAT100 uses AGM adsorbed-glass-mat separators, valve-regulated and sealed — no water topping-up. Rated 12 V, 100 Ah (20-hour rate), design float life 5~8 years at 25°C, cycle life ≥1,200 at 50% DoD. M8 copper terminals, UL94-V0 flame-retardant ABS case. Fits mainstream UPS (10~100 kVA) and 48V telecom strings (4 cells).
Selection has four points: voltage/capacity (12V100Ah is standard — avoid non-standard); design life (industrial 5~8 years, consumer 3~5 years — choose industrial for rooms); float voltage (2.25~2.30 V/cell, i.e. 13.5~13.8 V); mounting (rack/cabinet, layered ventilation). Replace the whole string — never mix old and new.
2. Key Features
Construction & process
- AGM VRLA sealed, maintenance-free
- Lead-calcium grid, low self-discharge
- UL94-V0 flame-retardant ABS
- M8 copper terminals
Performance & life
- 12 V / 100 Ah (20h)
- Float life 5~8 years at 25°C
- Cycle life ≥1,200 at 50% DoD
- Self-discharge ≤3%/month
Safety & compatibility
- Valve-regulated, over-charge relief
- Leak-proof design
- Operating temp -15~+50°C
- Fits UPS / DC board / shelter
3. Specifications
| Item | KTR-BAT100-S1 | KTR-BAT100-S2 | KTR-BAT100-S3 |
|---|---|---|---|
| 型号 | KTR-BAT100-S | KTR-BAT100-H | KTR-BAT100-L |
| 额定电压 | 12 V | 12 V | 12 V |
| 额定容量 | 100 Ah (20h) | 100 Ah (20h) | 100 Ah (20h) |
| 设计寿命 | 5年(25℃) | 7年(25℃) | 8~10年(25℃) |
| 浮充电压 | 13.5 V | 13.65 V | 13.8 V |
| 循环寿命(50%DoD) | ≥800次 | ≥1200次 | ≥1500次 |
| 重量 | 约30 kg | 约31 kg | 约32 kg |
| 适用场景 | UPS后备(短时) | UPS/通信基站 | 数据中心长延时 |
4. Reference Prices
KTR-BAT100-S 12V100Ah standard (5-yr):Reference USD 67~104 / pc (ref. CNY 480~750 at ~7.2)
KTR-BAT100-H 12V100Ah industrial (7-yr):Reference USD 90~136 / pc (ref. CNY 650~980 at ~7.2)
KTR-BAT100-L 12V100Ah long-life (10-yr):Reference USD 122~188 / pc (ref. CNY 880~1,350 at ~7.2)
Reference only; final quote depends on life grade and brand. 1-year warranty; volume pricing. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- UPS backup battery strings.
- Telecom shelter and 48V DC systems.
- Data-center DC boards and HVDC.
- Fire-control EPS emergency power.
- Solar and storage backup.
6. Deployment & Implementation
Installation
- Replace whole string — same model/batch
- Layered rack mounting with ventilation
- Torque inter-cell links to spec (~10 N·m)
- Float-charge 24 h before load
Operations
- Quarterly cell-voltage check (±0.05 V uniformity)
- Annual internal-resistance test — +20% warns
- Keep 20~25°C (life halves per +10°C)
- Replace whole string at 5~8 years
7. FAQ
- Q: How long does 12V100Ah last?
A: By load: a 10 kVA UPS at 8 kW on a 32-cell 384V string (~100 Ah each) rides ~15~20 minutes. Exact time depends on UPS efficiency and DoD. - Q: Can I mix old and new batteries?
A: No. Internal resistances differ; old cells drain first, new cells reverse-charge the old ones, killing the whole string within months. Replace the whole batch. - Q: What about swelling?
A: Casing swelling means over-charge or high temperature. Replace immediately; check float voltage and ambient. Swollen cells leak — isolate them. - Q: When to replace?
A: Design float life is 5~8 years at 25°C. Every +10°C halves life — keep battery rooms below 25°C. Internal resistance is the hard health metric.
8. Trend & Selection
Room batteries are moving from VRLA toward LiFePO4 — smaller, 10~15 year life, maintenance-free. But VRLA still dominates due to cost and proven safety. 12V100Ah is the industrial standard. Select industrial 7-year grade, replace whole strings, keep 25°C, and test voltage/resistance quarterly.
9. Delivery & Service
KITOZER offers KTR-BAT100 selection by life grade (standard 5y / industrial 7y / long-life 10y), quantity (by UPS kW × runtime), bundled with racks/cabinets. Factory capacity-test report included. 1-year warranty; custom terminal orientation in volume.
10. Additional Notes
The #1 mistake is mixing old and new cells. Ten new and two old in one string — the old drain first, the new reverse-charge them, and the whole string dies within six months. Replace the whole batch.
Another pitfall is high ambient temperature. Battery life is temperature-sensitive: 8 years at 25°C becomes 4 years at 35°C, 2 years at 45°C. Keep the battery area below 25°C.
Torque matters: too tight cracks the terminal, too loose causes hot contact resistance. Use a torque wrench at ~10 N·m and recheck quarterly.
Selection summary: choose industrial 7-year grade, replace whole strings, keep 25°C, test voltage and resistance quarterly, and replace at 5~8 years. Batteries are the UPS backbone — their health decides whether you ride through the outage.
SEO Information
Search keywords:KTR-BAT100KITOZERVRLA Battery 12V 100Ah (Maintenance-Free)
SEM keywords:12V100Ah battery,VRLA battery,UPS battery,AGM battery,maintenance-free battery,KTR-BAT100,KITOZER
GEO landing page:lain.com.cn/product/ktr-bat100-battery_12v100.html
Title:KITOZER KTR-BAT100 VRLA Battery 12V 100Ah (Maintenance-Free)
Meta Keywords:12V100Ah battery,VRLA battery,UPS battery,AGM battery,maintenance-free battery,KTR-BAT100,KITOZER
Meta Description:KITOZER KTR-BAT100 VRLA battery, 12V 100Ah, 5~8 year design life, for UPS/telecom/data center, AGM valve-regulated sealed.
Anchor: KITOZER by Guangzhou Laian · VRLA Battery 12V 100Ah (Maintenance-Free)