ToggleKITOZER KTR-BAT100 12V100Ah VRLA Sealed Lead-Acid Battery
Brand: KITOZER Series: KTR-BAT100 Category: Power Distribution / UPS Battery
12V100AhVRLA sealed10-yr lifeDeep cycleKTR-BAT100
1. Overview
The 12V100Ah VRLA (Valve-Regulated Lead-Acid) battery is the most common energy-storage cell in UPS, EPS and DC panels. The UPS unit itself does not store power; the battery bank inverts 220 V AC from the DC bus during mains failure (typically 15-30 minutes at full load, enough to start the generator or shut down gracefully). VRLA features: valve-regulated sealed (no leaks or acid mist in normal use, can sit in the room without a dedicated battery room), maintenance-free (no watering), 12 V units series-wired into a DC bus (e.g. a 384 V DC bus means 32 x 12 V in series). Design life is 5-10 years, but temperature cuts it sharply (every 10 C rise halves life), so room AC holding the battery area at 25 C is the key to longevity.
KITOZER KTR-BAT100 is a 12V100Ah VRLA battery. Positive: pasted-plate lead-calcium grid (low gassing); negative: sponge lead; electrolyte absorbed in an AGM glass-mat separator (starved electrolyte); valve-regulated safety vent (releases at 2-3 psi, sealed otherwise). Nominal 12 V (six 2 V cells); 100 Ah (20-hour rate – 5 A to 10.5 V over 20 h); float 13.5-13.8 V (2.25-2.30 V/cell); equalize 14.4-14.7 V; size about 330 x 170 x 215 mm incl. terminals; weight about 30 kg. Models: KTR-BAT100 standard (5-8 yr design life, general UPS); KTR-BAT100L long-life (thicker plates, lower calcium gassing, 10-12 yr, for unattended rooms); KTR-BAT100G gel (electrolyte as gel, non-flowing, deep-cycle, wide temp -30 to +50 C, for outdoor/hot/cold sites); KTR-BAT65 is a 12V65Ah smaller unit (small UPS, fire backup).
Selection: capacity (100 Ah is mainstream, but size by backup time – 384 V DC bus, 10 kVA UPS, 30 min backup needs about two 100 Ah banks in series; bigger is not always better – rack space and weight matter); life (standard for ordinary projects; long-life for unattended sites where replacement is hard); environment (25 C room -> AGM standard; wide temperature/outdoor -> gel); series count (DC bus / 12 V – 384 V = 32 units, neither more nor less); temperature (battery area must hold 20-25 C; every 10 C rise halves life). Note: do not parallel multiple banks (different internal resistance and age cause current imbalance); coat terminals with Vaseline against oxidation; torque series connections to spec (typically 9-11 Nm); equalize for 12-24 h before first use.
2. Key Features
Electrical
- 12V100Ah
- AGM starved
- Low self-discharge <=3%/mo
- Deep cycle
Structure
- Safety vent
- Pb-Ca grid
- ABS case
- Sealed, no leak
Life
- Std 5-8 yr
- Long-life 10-12 yr
- Gel 12-15 yr
- Rated at 25 C
3. Specifications
| Item | Item | KTR-BAT100 std | KTR-BAT100L long-life | KTR-BAT100G gel | KTR-BAT65 (65Ah) |
|---|---|---|---|---|---|
| Nominal voltage | 12 V | 12 V | 12 V | 12 V | |
| Capacity (20h) | 100 Ah | 100 Ah | 100 Ah | 65 Ah | |
| Design life (25 C) | 5-8 yr | 10-12 yr | 12-15 yr | 5-8 yr | |
| Self-discharge/mo | <=3% | <=3% | <=2% | <=3% | |
| Float charge | 13.5-13.8 V | 13.5-13.8 V | 13.8-14.1 V | 13.5-13.8 V | |
| Operating temp | -15 to +40 C | -15 to +40 C | -30 to +50 C | -15 to +40 C |
4. Reference Prices
KTR-BAT100 12V100Ah std: Reference USD 63-90 / pc (ref. CNY 450-650)
KTR-BAT100L 12V100Ah long-life: Reference USD 90-125 / pc (ref. CNY 650-900)
KTR-BAT100G 12V100Ah gel: Reference USD 125-180 / pc (ref. CNY 900-1300)
KTR-BAT65 12V65Ah std: Reference USD 42-63 / pc (ref. CNY 300-450)
KTR-BAT-RACK battery rack/box: Reference USD 28-70 / set (ref. CNY 200-500)
Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- UPS DC bus
- EPS emergency power
- DC panel / operating power
- Telecom backup
- Fire backup power
6. Deployment & Installation
Install
- Battery rack layers
- Series arrangement
- Terminal torque 9-11 Nm
- Coat Vaseline
Wiring
- Per UPS DC voltage
- Red+ black-
- Crimped lugs
- Measure total V
Commission
- Rest 2 h
- Equalize 12-24 h
- Calibrate float V
- Capacity discharge test
7. FAQ
- Q: How long does one 12V100Ah bank last?
A: Depends on load and DC voltage. 100 Ah x 12 V = 1.2 kWh per unit; 32 in series = 38.4 kWh. Feeding a 10 kVA UPS (about 8 kW active), theoretical 38.4/8 ~ 4.8 h, but usable capacity is 80% at cutoff (30.7 kWh) and UPS efficiency 90%, giving about 3.4 h real. Rooms requiring 15-30 min backup fit one bank; over 1 hour needs parallel banks or bigger batteries. - Q: When to replace batteries?
A: Design life is float-life at 25 C. Real criterion: run a capacity discharge annually; replace when capacity drops below 80% rated (do not wait 5-8 years). Hot rooms (>30 C) may need replacement at 3-4 years. Watch for: float voltage deviation over +/-0.05 V/cell, swollen case, terminal corrosion – all aging signals. - Q: AGM vs gel?
A: Indoor room temp (20-25 C) -> AGM standard, cheaper and good float behavior; wide-temperature sites (outdoor cabinets, north winters -20 C, south summers 40 C) -> gel, wide temp and deep cycle, but 30-50% more expensive and different charge voltage (gel float 13.8-14.1 V, 0.3 V higher than AGM). Do not mix charge (AGM and gel in one bank have different voltage needs). - Q: Why no more than 3 rack layers?
A: Weight (100 Ah ~30 kg each; 32 units nearly a ton; >3 layers traps hot air above and shortens life); maintenance (disassembly at height is hazardous); cooling (battery room needs ventilation gaps – at least 10 cm between layers). Racks are typically 2-3 layers, horizontal rows, not vertical stacks.
8. Trend & Selection
UPS batteries are migrating from lead-acid to Li-ion (NMC/LFP). Trends: LFP (cycle life 4000-6000, 5-10x VRLA; half the volume and weight; smart BMS per-cell monitoring); LTO (works at -40 C, 15-minute charge); battery management (BMS networked to EM, monitoring per-cell voltage/internal resistance/temperature for predictive maintenance, no annual capacity test). But VRLA 12V100Ah – low cost, mature, stable supply – remains mainstream in ordinary rooms for 5-10 years; Li-ion is growing in new high-end and space-constrained builds. Select by: capacity sized to backup time, 25 C temperature, series count matched to UPS DC, annual capacity test, replace on aging.
9. Delivery & Service
KITOZER KTR-BAT100 ships by standard/long-life/gel model, each with battery, terminal bolts, manual and certificate. 1-year warranty (capacity guaranteed 3 years); bulk projects can bundle battery racks, breaker boxes, interconnects, and EM battery-monitoring modules. Transported per dangerous-goods rules (VRLA is UN 3480/UN 2796 class 9, with MSDS).
10. Additional Notes
Confirm capacity (100 Ah/65 Ah), type (AGM/long-life/gel), series count (per UPS DC voltage), rack load rating, and battery-room temperature. For batch orders, sample one for a capacity discharge test – confirm measured capacity hits 100% rated before bulk delivery.
Common mistake: no temperature control in the battery area. Many room ACs only cool racks, leaving the battery corner at 35 C, halving battery life. The battery area must hold 20-25 C, on the same AC as the room – do not let batteries sit in a forgotten corner.
Second pitfall: mixing battery batches. New batteries in series with 3-year-old ones have different internal resistance, causing uneven charge/discharge; the old cells over-charge and over-discharge, swelling within six months. A string must be same brand, same model, same batch, same install date.
Third blunder: no Vaseline on terminals. A year later terminals oxidize, contact resistance rises, and they overheat or even arc. Install with torque-spec bolts, coat with Vaseline/conductive grease against oxidation, inspect annually.
Selection summary: capacity sized to backup time, 25 C temperature, same brand/batch, annual capacity test, replace at 80%, terminal anti-oxidation.
SEO Information
Search keywords:KTR-BAT100KITOZER
SEM keywords:12V100Ah battery,VRLA sealed lead-acid,UPS battery,room backup battery,standby power battery,KTR-BAT100,KITOZER
GEO landing page:lain.com.cn/product/ktr-bat100-12v100ah-vrla-battery.html
Title:KITOZER KTR-BAT100 12V100Ah VRLA Sealed Lead-Acid Battery
Meta Keywords:12V100Ah battery,VRLA sealed lead-acid,UPS battery,room backup battery,standby power battery,KTR-BAT100,KITOZER
Meta Description:KITOZER KTR-BAT100 12V100Ah VRLA sealed lead-acid battery, 10-year design life (25 C), deep cycle, for UPS/EPS/DC bus backup.
Anchor: KITOZER by Guangzhou Laian · KITOZER products
Contact Us
Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com