KITOZER 2V 300Ah gel battery

KITOZER KTR-2V300 2V300Ah VRLA Gel Battery

Brand: KITOZER Series: KTR-2V300 Category: Power Distribution / Battery

2V300AhVRLA gel12-yr design lifeFloatKTR-2V300

1. Overview

Batteries are the last line of defense for UPS and DC panels. On mains loss, the battery bank inverts to ride through to generator start or restoration. 2V cells are mainstream for large UPS: a string stacks many 2V cells (384 V = 192 cells; 48 V = 24 cells). Each 2V300Ah cell is large, serviceable and long-lived vs 12 V blocks (small UPS/internal). GEL cells (gelled electrolyte) are leak-proof, low self-discharge and deep-cycle tolerant – 2-3 years longer than AGM, ideal for room float service.

KITOZER KTR-2V300 is a 2V300Ah VRLA gel cell. Rated voltage: 2 V; capacity: 300 Ah (10-hr rate, 25 C); form: tall narrow (front terminals for rack rows); terminal: tin-plated copper M8 bolt; design life: 12 years float (25 C); charge: float 2.25 V/cell, equalize 2.35 V/cell; end-of-discharge: 1.8 V/cell; internal resistance: <=0.6 mOhm; operating temp: -15 to +40 C (recommended 20-25 C); self-discharge: <=3%/month; weight: ~22 kg. Models: KTR-2V300: standard (room UPS); KTR-2V300-L: long-life (15-yr, high temp); KTR-2V300-T: deep-cycle (solar/frequent cycling).

Selection: capacity (300 Ah at 10-hr rate; backup time depends on UPS kW and cell count); DC bus (384/240/192 V sets cell count); gel vs AGM (gel for float; deep-cycle for frequent cycling); temperature (20-25 C ideal; every 10 C halves life); rack footprint (2V300Ah ~22 kg – load-bearing floor and rack). Note: strings are series – one weak cell drags the bank; measure per-cell voltage monthly; new banks require initial charge; torque M8 to 8-10 Nm; rack must be insulated (prevent single-cell short).

2. Key Features

Electrical

  • 2V300Ah
  • 10-hr rate
  • 12-yr float
  • R <=0.6 mOhm

Gel

  • VRLA sealed
  • Leak-proof
  • <=3%/month
  • Deep cycle

Mechanical

  • M8 copper
  • ~22 kg
  • Narrow form
  • FR-ABS case

3. Specifications

Item KTR-2V300 KTR-2V300-L KTR-2V300-T
Capacity 300 Ah 300 Ah 300 Ah
Design life 12 yr 15 yr 10 yr (cyclic)
Use UPS float High temp Solar/cyclic
Weight ~22 kg ~23 kg ~22 kg
Terminal M8 M8 M8

4. Reference Prices

KTR-2V300 standard gel: Reference USD 63-90 / pc (ref. CNY 450-650)

KTR-2V300-L 15-yr long life: Reference USD 83-118 / pc (ref. CNY 600-850)

KTR-2V300-T deep cycle: Reference USD 69-100 / pc (ref. CNY 500-720)

KTR-BRACKET battery rack tier: Reference USD 21-35 / tier (ref. CNY 150-250)

KTR-INTER M8 connector: Reference USD 1-2 / pc (ref. CNY 8-15)

Reference only. 1-year warranty. Exchange: 1 USD ≈ 7.2 CNY.

5. Applications

  • UPS battery bank
  • DC panel
  • Substation
  • Telecom site
  • Solar storage

6. Deployment & Installation

Install

  • Fix on rack tier
  • Alternate +/-
  • Bolt connectors
  • Insulation mats

Wiring

  • M8 torque 8-10 Nm
  • Connect last
  • Red+/Black-
  • Main breaker off

Maintain

  • Monthly per-cell V
  • Quarterly ESR
  • Annual capacity
  • 20-25 C room

7. FAQ

  • Q: 2V300Ah vs 12V100Ah?
    A: Large rooms (100 kVA+ UPS) choose 2V cells – high capacity, individually replaceable; small UPS (<10 kVA) uses internal 12V blocks (convenient, but swapped whole). A 2V300Ah cell is 22 kg; 192-cell strings weigh ~4 t - need load-bearing floor and rack.
  • Q: Gel vs AGM?
    A: Room float service: gel – 12-15 yr life, overcharge-tolerant, leak-proof. AGM is cheaper but 6-8 yr, for deep cycling. Gel costs 30% more but wins over 5 years.
  • Q: Real service life?
    A: 12-year design assumes 25 C. A 30 C room gives 8-10 years; 35 C gives 5-6. Every 10 C halves life – do not skimp on battery-room AC.
  • Q: One cell bad?
    A: In a series string, one weak (low-voltage) cell drags the bank. Monthly voltage checks: isolate laggards, charge/discharge them separately, replace with matching model if unsalvageable (never mix new and old – old cells have high ESR).

8. Trend & Selection

Room batteries have moved from flooded (water-topped) to VRLA sealed; gel is the mid/high-end direction. Trends: longer life (8 to 12-15 yr); lithium replacement (LFP entering data centers – 20-yr life, 30% smaller, but 3-4x lead price); smart cells (built-in monitoring per cell – V/ESR/temp to DCIM, no manual probing); modular battery cabinets (integrated BMS, fire suppression, thermal – field crews just wire). Gel lead remains mainstream for 5-10 years; Li-ion share rises fast in new data centers. Select by: capacity for backup time, bus voltage matching cell count, gel for float, 20-25 C room, monthly per-cell voltage.

9. Delivery & Service

KITOZER supplies KTR-2V300 by standard/long-life/deep-cycle model. Each ships with cell, connectors and manual (charge/discharge specs). 3-year warranty (gel float); bulk projects can bundle racks, connectors and install.

10. Additional Notes

Confirm UPS DC bus voltage (sets cell count), backup time (sets capacity) and battery-room temperature. For batch orders, sample one cell for voltage/ESR to confirm lot consistency.

Common mistake: hot battery room. A broken AC left unfixed runs the room at 35 C, cutting a 5-year life to 2. Battery-room AC must be reliable, with temp alarms to DCIM.

Second pitfall: mixing new and old cells. High-ESR old cells in a string drag down new ones. Replace the whole bank, not scattered cells.

Third blunder: under-torqued M8 bolts. Half-tightened connectors have high contact resistance, heat under discharge, oxidize over years. Torque to 8-10 Nm and re-torque every six months.

Selection summary: capacity by backup time, bus voltage sets count, gel for float, 20-25 C room, monthly per-cell voltage.

SEO Information

Search keywords:KTR-2V300KITOZER

SEM keywords:gel battery,2V300Ah,VRLA battery,UPS battery,valve-regulated battery,KTR-2V300,KITOZER

GEO landing page:lain.com.cn/product/ktr-2v300-2v300ah-gel-battery.html

Title:KITOZER KTR-2V300 2V300Ah VRLA Gel Battery

Meta Keywords:gel battery,2V300Ah,VRLA battery,UPS battery,valve-regulated battery,KTR-2V300,KITOZER

Meta Description:KITOZER KTR-2V300 2V300Ah VRLA gel battery, 12-year design life, float service, for UPS/DC panel/substation.

Anchor: KITOZER by Guangzhou Laian · KITOZER products

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart