KITOZER Battery Patrol: 48 Channel Battery Inspection System

Product Overview

The KITOZER 48 channel battery inspection system continuously monitors the health of stationary VRLA, flooded, or lithium-ion battery banks used to back up UPS systems, DC power supplies, and solar storage arrays. Each channel measures individual cell voltage, cell internal resistance, and cell temperature, and the master unit reports per-cell data, string current, and total bank voltage over Modbus TCP or RS485. Early detection of a weak or failing cell prevents a surprise battery outage during a utility event, because a single bad cell can drag the whole string down when load is applied. The system also tracks charge and discharge current, integrates ampere-hours, and triggers alarms on over voltage, under voltage, high resistance, high temperature, and ground fault.

Technical Specifications

Channels: 48 cell voltage inputs per master, expandable up to 240 cells with slave units. Voltage range per cell: 0 to 3V for 2V cells, 0 to 16V for 12V blocks, 0 to 5V for lithium. Voltage accuracy: plus minus 0.5 percent. Internal resistance measurement: plus minus 5 percent, injects low AC signal during charge or discharge. Temperature inputs: up to 48 NTC sensor inputs. String current: external DC shunt or Hall sensor, 0 to 500A configurable. Alarm: over voltage, under voltage, high resistance, high temperature, ground fault, charge over current. Display: 5 inch color LCD, per-cell bar graph. Communication: Ethernet Modbus TCP, RS485 Modbus RTU, optional SNMP, Web HMI. Power supply: 85 to 265VAC or 48VDC. Mounting: DIN rail or panel, operating -10 to 55 degrees C. Standards: CE, 5 year warranty.

Application Scenarios

The 48 channel battery patrol is installed wherever a battery bank supports critical load. Typical sites include data center UPS rooms with 40 to 60 cell VRLA strings, telecom central office DC plants with 48V strings, industrial DC control and emergency systems, solar plus storage arrays, and large battery rooms for power plants and substations. It is also used in hospitals, railways, and oil and gas facilities where battery-backed control systems must be reliable. By trending per-cell resistance over time, the system predicts end-of-life months in advance, allowing planned replacement rather than emergency swap during a battery failure.

Key Advantages

Continuous per-cell monitoring catches weak cells that manual monthly measurements would miss. Internal resistance trending is the most reliable early indicator of VRLA degradation. Ground fault detection alerts on insulation issues before they become safety events. The system integrates with UPS monitoring and BMS platforms, giving a single view of power chain health. Web HMI and SNMP allow remote access from the operations center. Expandability up to 240 cells supports large banks without multiple masters. The 5 year warranty and DIN rail mounting simplify spares. The system also reduces the need for technicians to walk the battery room monthly with a handheld tester, saving labor and improving safety.

Installation and Maintenance Recommendations

Mount the master in a DIN rail enclosure near the battery bank, route voltage sense leads per cell with fused taps, install NTC sensors on cells prone to heat, and install the current shunt or Hall sensor in the main return path. Configure cell type, nominal voltage, alarm thresholds, and current ratio. On commissioning, verify each cell voltage matches a handheld meter and verify that resistance measurement works during charge. Maintenance: check sense lead torque quarterly, inspect NTC adhesion, and trend per-cell resistance every month. Replace cells whose resistance rises by 20 percent above baseline or whose voltage deviates by more than 0.05V under load. Keep spares of master and slave units. Because battery rooms are safety sensitive, follow local procedures for DC arc flash and ground fault testing.

The 48 channel battery patrol reduces the need for technicians to walk the battery room monthly with a handheld tester, because every cell voltage, resistance, and temperature is trended automatically. Ground fault detection alerts on insulation issues before they become safety events. The system integrates with UPS monitoring platforms, giving operators a single view of the full power chain from utility incomer to battery bank.

Ordering Information

The 48 channel battery patrol master is supplied with a 48 cell voltage harness, NTC temperature leads, and a current shunt or Hall sensor. The standard configuration includes Ethernet Modbus TCP, RS485, a 5 inch color LCD, and event logging. Optional packages include SNMP, Web HMI, slave units to expand up to 240 cells, and lithium BMS integration for LiFePO4 banks. The master can be powered by 85 to 265VAC or by the 48VDC battery bus for telecom sites. Lead time is two to three weeks. KITOZER provides a wiring diagram per bank layout, a Modbus register list, and commissioning support. The five year warranty covers the master and harness.

Price

From $1,280 per master including 48 channel harness. Contact the factory for slave expansion, lithium BMS integration, and SNMP option. Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com