ToggleKITOZER KTR-BAT24F Battery / 12V24Ah Gel Deep-Cycle
Brand: KITOZER Series: KTR-BAT24F Category: Power Distribution / Backup Battery
12V24AhGel deep-cycleMaintenance-freeUPS backupLong life
1. Overview
UPS and DC panels rely on battery strings to carry the load during mains loss; the string is the heart of backup power. Rooms commonly use 12V VRLA batteries in series to reach the DC bus (e.g. 32 x 12V for a 384V system). Gel batteries suspend electrolyte in a gel, so it does not stratify or leak and they can be mounted in any orientation; deep-cycle performance outlasts ordinary AGM when discharges are deeper and cycles more frequent.
The KITOZER KTR-BAT24F is a 12V24Ah VRLA gel deep-cycle battery. Nominal 12V, 24Ah (20-hour rate), with gel electrolyte and pasted plates. The sealed valve-regulated design emits no acid mist and needs no water under normal use. Self-discharge is about 3% per month at 25C. Design float life is 10-12 years at 25C; about 600 deep cycles at 100% DOD. Carrying handle and valve-regulated terminals suit rack stacking in series strings.
Selection: system voltage sets series count; backup runtime sets total Ah (N x single-cell capacity); correct for discharge rate and temperature. 24Ah suits small UPS, DC panels and monitoring backup; large rooms use bigger cells or parallel strings. Limit parallel groups to four, and never mix old and new cells. Keep 20-25C; every 10C above halves life. Float at 13.5-13.8V/cell, equalize at 14.4-15.0V/cell.
A battery string is a chain: its runtime is limited by the weakest cell, not the average. That is why periodic conductance or internal-resistance readings matter – they reveal the laggard before the whole string fails a load test. Cells should be replaced as a matched set, not individually, because mixing a new 12V cell into an aged string causes mismatched charge acceptance and circulating currents. Temperature is the other silent killer: every 10 C above 25 C roughly halves service life, so a 30 C battery room already trades years off a 10-year design life. Charge voltage must be temperature-compensated; floating too high dries out the gel, floating too low causes sulfation. When decommissioning exhausted cells, follow local lead-acid recycling rules rather than discarding them with general waste.
2. Key Features
Gel deep-cycle
- Gel electrolyte, no stratify or leak.
- About 600 cycles at 100% DOD.
- Tolerates deep discharge better than AGM.
- Mount in any orientation.
Sealed maintenance-free
- Valve-regulated, no topping up.
- No acid mist in normal use.
- ~3% per month self-discharge at 25C.
- 10-12 year float design life.
Form and accessories
- Standard 12V24Ah footprint.
- Handle and valve terminals.
- Rack stacking in series/parallel.
- Flame-retardant ABS case.
String health
- Track internal resistance per cell.
- Replace cells as a matched set.
- Compensate charge voltage for temp.
- Recycle exhausted cells properly.
3. Specifications
| Item | Specification |
|---|---|
| Nominal voltage | 12 V |
| Nominal capacity | 24 Ah (20h, 1.75V/cell cutoff) |
| Type | VRLA gel lead-acid |
| Float voltage | 13.5 ~ 13.8 V/cell (25C) |
| Equalize voltage | 14.4 ~ 15.0 V/cell |
| Deep-cycle life | about 600 cycles at 100% DOD |
| Self-discharge | about 3%/month at 25C |
| Operating temp | -15 to +50 C (recommended 25C) |
| Terminals | M5/M6 valve-regulated |
| Case | Flame-retardant ABS |
4. Reference Prices
KTR-BAT24F 12V24Ah gel battery: USD 39~78 (ref. CNY 280~560)
Inter-cell connector (per string): USD 2~4 (ref. CNY 15~30)
Battery capacity test service: USD 42~83 (ref. CNY 300~600)
Reference only; final quote applies. 1-year warranty. Bulk pricing available. Certificate and manual included. Exchange: 1 USD ≈ 7.2 CNY.
5. Applications
- Small UPS backup strings.
- DC panels and switchgear power.
- Monitoring and access backup.
- PV / solar auxiliary storage.
- Emergency lighting and fire backup.
6. Installation & Maintenance
Installation
- Series to the required bus voltage.
- Never mix old/new or brands.
- Tighten connectors diagonally.
- Rack-stack with ventilation.
- Hold 20-25 C ambient.
- Series first, parallel <=4 groups.
- Do commissioning capacity test.
Maintenance
- Measure float voltage quarterly.
- Run capacity discharge yearly.
- Check connectors for heat/oxidation.
- Keep the room ventilated and cool.
- Log internal-resistance trends.
7. FAQ
- Q: Gel or AGM?
A: Gel tolerates deep cycles and heat; AGM handles high current better. For float UPS both work; choose gel for frequent deep discharge. - Q: How long do they last?
A: 10-12 years at 25C float; heat and deep discharge shorten real life. - Q: How many parallel strings?
A: Usually <=4 of identical batch; more causes circulating current and imbalance. - Q: Can I use a swollen battery?
A: No. Swelling means gas generation or dry-out; replace the whole string to avoid leakage and thermal runaway.
8. Trend & Selection
Backup batteries evolve from plain VRLA toward gel and Li-ion, but 12V lead-acid stays mainstream due to maturity and cost. String monitoring (internal-resistance trending) becomes standard to predict weak cells. Size runtime properly, use same batch, and treat temperature control as the key life-extender.
9. Delivery & Service
KITOZER ships KTR-BAT24F with the cell, connectors, certificate and manual. Strings include connectors and rack layout, with runtime and capacity sizing calculations.
10. Notes
A common mistake is reading Ah without temperature correction; heat cuts both real capacity and life, so room cooling matters.
Another pitfall is mixing old cells in series: the weak cell drags the whole string, dies first under discharge, and gets reverse-charged.
In short: 12V24Ah, gel deep-cycle, 10-12 year float, maintenance-free, series-stringed. The heart of UPS backup.
System-wise, one weak cell cuts the whole string’s runtime; periodic capacity tests are not skippable.
Cost-wise, a cell costs a few hundred CNY; an outage caused by failed batteries costs far more.
Operationally, runtime equals the weakest cell’s capacity, so trending internal resistance finds the laggard years before an outage exposes it.