ToggleKITOZER KTR-BTL4850 LiFePO4 Battery (48V50Ah Energy Storage)
Brand: KITOZER Series: KTR-BTL4850 Category: Energy Storage / LiFePO4 Battery
48V50AhLiFePO4BMS≥6000 cyclesparallel expandKTR-BTL4850
1. Overview
The KITOZER KTR-BTL4850 is a 48V50Ah (2.56 kWh) LiFePO4 battery pack, built from 16S × 3.2V50Ah cells with a built-in BMS for over-charge/discharge, over-current, short-circuit and temperature protection. Standard 19-inch 3U rack-mount, parallellable up to 16 units, for UPS replacing lead-acid, telecom tower backup, PV storage and off-grid systems.
KTR-BTL4850 nominal 51.2 V (16S), full 58.4 V, cutoff 40 V. Rated 50 Ah, charge/discharge 0.5C (25 A), peak 1C (50 A). Cycle life ≥6000 (80% DoD, 25℃). BMS communicates via RS485/CAN with UPS or storage inverter, reporting SOC/SOH/cell voltage/temperature. Parallel up to 16 packs for 40 kWh.
Typical uses: room UPS backup (replacing lead-acid — half the footprint, 4× life); telecom tower 48 V DC backup; PV off-grid/grid-tie storage; small C&I storage cabinets.
2. Key Features
LiFePO4 cells
- 16S × 3.2V50Ah.
- Safe, no fire.
- ≥6000 cycles.
- Long life at 80% DoD.
Smart BMS
- Over-charge/discharge/current protection.
- Temp sampling.
- RS485/CAN.
- SOC/SOH estimation.
Rack design
- 19-inch 3U.
- Parallel up to 16.
- Fan cooling.
- LCD display.
Wide temp
- -20~60℃ discharge.
- 0~55℃ charge.
- Heating option (low temp).
- IP20 indoor.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-BTL4850 |
| Chemistry | LiFePO4 |
| Nominal voltage | 51.2 V (16S) |
| Full/cutoff | 58.4 V / 40 V |
| Rated capacity | 50 Ah |
| Rated energy | 2.56 kWh |
| Charge/discharge rate | 0.5C (25 A), peak 1C |
| Cycle life | ≥6000 (80% DoD, 25℃) |
| Communication | RS485 / CAN |
| Parallel expand | Up to 16 (40 kWh) |
| Dimensions | 19-inch 3U (~482×132×450 mm) |
| Weight | ~45 kg |
| Operating temp | -20~60℃ discharge / 0~55℃ charge |
4. Reference Prices
KTR-BTL4850 48V50Ah pack (incl. BMS):Ref. USD 830~1250 / unit (CNY 6000~9000 @7.2)
KTR-BTL4850 low-temp heating version:Ref. USD 970~1460 / unit (CNY 7000~10500 @7.2)
Parallel comm cable (CAN/RS485):Ref. USD 7~21 / pc (CNY 50~150 @7.2)
Battery rack (19-inch):Ref. USD 42~85 / pc (CNY 300~600 @7.2)
Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Room UPS backup.
- Telecom tower 48 V backup.
- PV off-grid storage.
- C&I storage cabinet.
- RV / marine auxiliary power.
6. Installation & Maintenance
Installation
- Mount pack in 3U rack slot.
- Connect parallel packs (same model).
- DC bus +/- terminals.
- BMS comm to UPS/inverter.
- Ground protection.
- Initial charge/discharge activation.
- LCD shows SOC normal.
- Set parallel parameters.
Maintenance
- Check SOC/SOH monthly.
- Balance charge semi-annually.
- Inspect fan cooling.
- Clean terminals.
- Log capacity fade.
- Pack life 8~10 years.
7. FAQ
- Q:Can LiFePO4 and lead-acid be mixed?
A:No. Lead-acid (2V cells, float 2.25 V/cell) and LiFePO4 (3.2V cells) have totally different voltage curves and charging methods. Mixing causes over-charge/discharge. UPS/inverter must be configured for Li charging (58.4 V float, 54 V balance). Old UPS with default lead-acid params needs firmware upgrade or a dedicated Li charging module. - Q:How to parallel for expansion?
A: ① All packs same model (KTR-BTL4850); ② Charge fully (>95% SOC) before parallel, voltage diff ≤0.5 V; ③ Use same-spec parallel cables (≥25 mm²) for +/-; ④ BMS comm daisy-chain; ⑤ Set first as master, rest slave; ⑥ Observe 48 h after first parallel, confirm uniform voltage. - Q:Can I charge below 0℃?
A:Charging LiFePO4 below 0℃ causes lithium plating, damaging cells. Standard KTR-BTL4850 charging range is 0~55℃. If ambient <0℃, choose the low-temp heating version (built-in heating film; BMS heats first below 5℃ before charging). Discharge can go to -20℃. - Q:How to handle end-of-life packs?
A:When SOH<80% (actual capacity below 80% rated), recommend replacement. Do not discard old packs — they are hazardous waste. Contact a licensed battery recycler (second-life or material recovery). KITOZER provides old-pack recycling guidance to avoid environmental pollution.
8. Trend & Selection
Storage batteries are trending high-capacity (314 Ah cells), high-voltage (400/800 V), liquid cooling and smart cloud monitoring. LiFePO4 replacing lead-acid is the long-term trend in rooms and towers; 6000-cycle life is the key metric.
9. Delivery & Service
KITOZER sizes KTR-BTL4850 count by UPS power and backup time, providing capacity calculation and parallel topology. Delivery includes pack, parallel cables, comm cables, certificate. Warranty covers BMS commissioning and capacity test support.
10. Additional Notes
A common pitfall is connecting a Li battery directly to a lead-acid UPS. Old UPS charge voltage (2.25 V/cell ×24=54 V) is low for LiFePO4 (3.65 V/cell ×16=58.4 V); long-term under-charging gives fake-high SOC and short actual backup. Confirm UPS supports Li charging params, or add a dedicated Li charging module.
Another pitfall is parallel packs with inconsistent voltage. If voltage diff >0.5 V before parallel, inrush equalization current may damage BMS fuses. Charge fully before parallel, rest 24 h, confirm diff ≤0.5 V. Long-term: balance periodically (semi-annual full charge to 58.4 V).
Selection summary: 48V50Ah LiFePO4; 16S; BMS; ≥6000 cycles; 16 parallel. The battery pack is the UPS fuel tank — right charging params, proper parallel balancing, periodic BMS check, keeps backup reliable.