ToggleKITOZER KTR-DPS2 DC 48V Class B+C Surge Protector
Brand: KITOZER Series: KTR-DPS2 Category: Power Distribution / Surge Protection
SPDDC 48VClass B+Csurge protectionrack mountKTR-DPS2
1. Overview
KITOZER KTR-DPS2 is a DC 48V Class B+C surge protective device (SPD) installed in -48V DC power systems to protect telecom rectifiers, DC distribution, servers and network gear from lightning surges and switching transients. Telecom sites and data centers use -48V DC: rectifiers convert AC to -48V, then a DC distribution cabinet feeds each rack. On this DC bus, lightning surges can be induced from the AC side, or switching transients from load steps — transient voltages reach thousands of volts, far above telecom equipment withstand ratings.
The SPD is paralleled across the DC bus. It is high-impedance during normal operation and invisible to the load; when a surge appears, the internal MOV or gas tube conducts within nanoseconds, clamping the surge to a residual voltage the equipment can survive (typically <100 V), and diverts surge current to the grounding grid. "Class B+C" integrates two stages in one module — B stage (high current, coarse protection) dissipates most energy; C stage (low residual, fine protection) clamps the remainder, saving intermediate wiring.
KTR-DPS2 is a rack-mount module on a 35 mm DIN rail or 19-inch rack, Uc=60 V DC (suitable for -48V systems), In=20 kA (8/20μs), Imax=40 kA, Up≤1.5 kV. A status window shows green (normal) or red (degraded, replace). A remote-signaling contact lets the BMS monitor SPD health. Pure-copper terminals accept 16~35 mm² conductors for direct busbar connection.
2. Key Features
B+C in one module
- High-current B + low-residual C.
- Integrated in one unit.
- No inter-stage wiring.
DC 48V dedicated
- Uc=60 V DC for -48V.
- +, – and ground protected.
- Pure-copper high-current terminals.
Visible status
- Green/red window.
- Remote-signaling contact.
- Hot-swap replacement.
Rack / DIN mount
- 35 mm rail or 19-inch rack.
- Pluggable module.
- 16~35 mm² conductors.
3. Specifications
| Item | KTR-DPS2 |
|---|---|
| Max continuous voltage Uc | 60 V DC |
| Nominal discharge In (8/20μs) | 20 kA |
| Max discharge Imax | 40 kA |
| Voltage protection Up | ≤1.5 kV |
| Modes | +PE / -PE / +- |
| Mount | 35 mm rail / 19-inch rack |
| Conductor | 16~35 mm² copper terminals |
| Status | Green (ok) / red (degraded) |
| Remote contact | Dry contact 2A/250VAC |
| Operating temp | -40~70℃ |
| Housing | UL94V-0 flame retardant |
4. Reference Prices
KTR-DPS2 DC 48V B+C SPD (DIN rail, 20 kA, no remote): Reference USD 25~44 / unit (ref. CNY 180~320 at ~7.2)
KTR-DPS2 DC 48V B+C SPD (rack, 40 kA, with remote): Reference USD 53~94 / unit (ref. CNY 380~680 at ~7.2)
Reference only; priced by current rating, mount, remote. Ground busbar and leads not included. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- -48V telecom DC distribution.
- Rectifier output terminals.
- DC row-end cabinets.
- Base stations and remote sites.
- Industrial DC busbars.
6. Installation & Maintenance
Installation
- [‘
- Confirm Uc matches -48V system.
- Wire SPD in parallel across +/-.
- Keep ground lead short and thick, ≤0.5 m.
- Ground lead straight to ground busbar.
- Connect remote contact to BMS.
- Install upstream of protected gear.
- Test insulation before energizing.
- Hot-swap modules without powering down.
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘]
Maintenance
- [‘
- Check status window monthly.
- Replace module on red immediately.
- Retorque terminals annually.
- Inspect before/after storm season.
- Test remote contact periodically.
‘, ‘
‘, ‘
‘, ‘
‘, ‘
‘]
7. FAQ
- [‘
- Q: Can I keep using a red SPD?
A: No. Red means the MOV is degraded; continued use risks fire or failure. Replace at once. B+C modules hot-swap without powering down. - Q: Why must the ground lead be short?
A: Longer leads add inductance; the lead’s own drop raises the residual voltage during a surge, weakening protection. Code requires ≤0.5 m, short, thick and straight. - Q: Can an AC 220V SPD be used on DC 48V?
A: No. AC SPDs rely on current zero-crossing to extinguish the arc; DC has no zero-crossing, so follow-through current cannot stop — fire hazard. Use a DC-specific SPD. - Q: How many SPDs per system?
A: Staged: B at main intake, B+C at row-end, C at rack. KTR-DPS2 B+C suits row-end and rack input.
‘, “
“, ‘
‘, ‘
‘]
8. Trend & Selection
[“
DC power evolves toward higher voltages, but -48V remains mainstream in telecom and edge sites. SPDs move from separate B/C stages to integrated B+C, remote-signaling, pluggable modules. Select: Uc matched to DC system; In≥20 kA; short thick ground lead; remote to BMS; check status window routinely. The SPD is the DC bus’s fuse — idle in normal operation, it stands between gear and surges.
“]
9. Delivery & Service
[‘
KITOZER supplies KTR-DPS2 B+C SPDs matched to the DC system voltage and protected equipment, with DIN rail and terminals. We provide the surge-protection and grounding drawing. Warranty covers degraded-module replacement.
‘]
10. Additional Notes
[‘
A common mistake: long ground leads. Looping the lead to the busbar adds inductance; the residual voltage stays high and the SPD is wasted. Keep the lead short, thick and straight.
‘, ‘
Another pitfall: using an AC SPD on DC. Buying cheaply and installing a 220 V AC SPD on a -48V bus — DC has no zero-crossing, so after the MOV breaks down follow-through current cannot stop, causing fire. Use a DC-specific SPD.
‘, ‘
Selection summary: DC 48V dedicated; B+C integrated; In=20 kA; ground ≤0.5 m; remote to BMS; replace on red. SPDs are consumable — every surge ages them; checking the window matters more than post-incident repair.
‘]