KITOZER KTR-DPS2 DC 48V Class B+C Surge Protector

KITOZER KTR-DPS2 DC 48V Class B+C Surge Protector

Brand: KITOZER Series: KTR-DPS2 Category: Power Distribution / Surge Protection

SPDDC 48VClass B+Csurge protectionrack mountKTR-DPS2

[Product image: KITOZER KTR-DPS2 rack-mount SPD module with terminals and status window]

1. Overview

KITOZER KTR-DPS2 is a DC 48V Class B+C surge protective device (SPD) installed in -48V DC power systems to protect telecom rectifiers, DC distribution, servers and network gear from lightning surges and switching transients. Telecom sites and data centers use -48V DC: rectifiers convert AC to -48V, then a DC distribution cabinet feeds each rack. On this DC bus, lightning surges can be induced from the AC side, or switching transients from load steps — transient voltages reach thousands of volts, far above telecom equipment withstand ratings.

The SPD is paralleled across the DC bus. It is high-impedance during normal operation and invisible to the load; when a surge appears, the internal MOV or gas tube conducts within nanoseconds, clamping the surge to a residual voltage the equipment can survive (typically <100 V), and diverts surge current to the grounding grid. "Class B+C" integrates two stages in one module — B stage (high current, coarse protection) dissipates most energy; C stage (low residual, fine protection) clamps the remainder, saving intermediate wiring.

KTR-DPS2 is a rack-mount module on a 35 mm DIN rail or 19-inch rack, Uc=60 V DC (suitable for -48V systems), In=20 kA (8/20μs), Imax=40 kA, Up≤1.5 kV. A status window shows green (normal) or red (degraded, replace). A remote-signaling contact lets the BMS monitor SPD health. Pure-copper terminals accept 16~35 mm² conductors for direct busbar connection.

2. Key Features

B+C in one module

  • High-current B + low-residual C.
  • Integrated in one unit.
  • No inter-stage wiring.

DC 48V dedicated

  • Uc=60 V DC for -48V.
  • +, – and ground protected.
  • Pure-copper high-current terminals.

Visible status

  • Green/red window.
  • Remote-signaling contact.
  • Hot-swap replacement.

Rack / DIN mount

  • 35 mm rail or 19-inch rack.
  • Pluggable module.
  • 16~35 mm² conductors.

3. Specifications

Item KTR-DPS2
Max continuous voltage Uc 60 V DC
Nominal discharge In (8/20μs) 20 kA
Max discharge Imax 40 kA
Voltage protection Up ≤1.5 kV
Modes +PE / -PE / +-
Mount 35 mm rail / 19-inch rack
Conductor 16~35 mm² copper terminals
Status Green (ok) / red (degraded)
Remote contact Dry contact 2A/250VAC
Operating temp -40~70℃
Housing UL94V-0 flame retardant

4. Reference Prices

KTR-DPS2 DC 48V B+C SPD (DIN rail, 20 kA, no remote): Reference USD 25~44 / unit (ref. CNY 180~320 at ~7.2)

KTR-DPS2 DC 48V B+C SPD (rack, 40 kA, with remote): Reference USD 53~94 / unit (ref. CNY 380~680 at ~7.2)

Reference only; priced by current rating, mount, remote. Ground busbar and leads not included. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • -48V telecom DC distribution.
  • Rectifier output terminals.
  • DC row-end cabinets.
  • Base stations and remote sites.
  • Industrial DC busbars.

6. Installation & Maintenance

Installation

    [‘

  • Confirm Uc matches -48V system.
  • ‘, ‘

  • Wire SPD in parallel across +/-.
  • ‘, ‘

  • Keep ground lead short and thick, ≤0.5 m.
  • ‘, ‘

  • Ground lead straight to ground busbar.
  • ‘, ‘

  • Connect remote contact to BMS.
  • ‘, ‘

  • Install upstream of protected gear.
  • ‘, ‘

  • Test insulation before energizing.
  • ‘, ‘

  • Hot-swap modules without powering down.
  • ‘]

Maintenance

    [‘

  • Check status window monthly.
  • ‘, ‘

  • Replace module on red immediately.
  • ‘, ‘

  • Retorque terminals annually.
  • ‘, ‘

  • Inspect before/after storm season.
  • ‘, ‘

  • Test remote contact periodically.
  • ‘]

7. FAQ

    [‘

  • Q: Can I keep using a red SPD?
    A: No. Red means the MOV is degraded; continued use risks fire or failure. Replace at once. B+C modules hot-swap without powering down.
  • ‘, “

  • Q: Why must the ground lead be short?
    A: Longer leads add inductance; the lead’s own drop raises the residual voltage during a surge, weakening protection. Code requires ≤0.5 m, short, thick and straight.
  • “, ‘

  • Q: Can an AC 220V SPD be used on DC 48V?
    A: No. AC SPDs rely on current zero-crossing to extinguish the arc; DC has no zero-crossing, so follow-through current cannot stop — fire hazard. Use a DC-specific SPD.
  • ‘, ‘

  • Q: How many SPDs per system?
    A: Staged: B at main intake, B+C at row-end, C at rack. KTR-DPS2 B+C suits row-end and rack input.
  • ‘]

8. Trend & Selection

[“

DC power evolves toward higher voltages, but -48V remains mainstream in telecom and edge sites. SPDs move from separate B/C stages to integrated B+C, remote-signaling, pluggable modules. Select: Uc matched to DC system; In≥20 kA; short thick ground lead; remote to BMS; check status window routinely. The SPD is the DC bus’s fuse — idle in normal operation, it stands between gear and surges.

“]

9. Delivery & Service

[‘

KITOZER supplies KTR-DPS2 B+C SPDs matched to the DC system voltage and protected equipment, with DIN rail and terminals. We provide the surge-protection and grounding drawing. Warranty covers degraded-module replacement.

‘]

10. Additional Notes

[‘

A common mistake: long ground leads. Looping the lead to the busbar adds inductance; the residual voltage stays high and the SPD is wasted. Keep the lead short, thick and straight.

‘, ‘

Another pitfall: using an AC SPD on DC. Buying cheaply and installing a 220 V AC SPD on a -48V bus — DC has no zero-crossing, so after the MOV breaks down follow-through current cannot stop, causing fire. Use a DC-specific SPD.

‘, ‘

Selection summary: DC 48V dedicated; B+C integrated; In=20 kA; ground ≤0.5 m; remote to BMS; replace on red. SPDs are consumable — every surge ages them; checking the window matters more than post-incident repair.

‘]