KITOZER
KITOZER

KITOZER KTR-OS Oil Separator & Dryer Filter for Data Center Precision AC

KITOZER KTR-OS Oil Separator & Dryer Filter for Data Center Precision AC

Brand: KITOZER Series: KTR-OS Category: Data Center Engineering 2 / Refrigeration Loop Accessories

oil separatorfilter drierprecision AC loopchiller maintenanceKTR-OS

1. Overview

KITOZER KTR-OS oil separator and filter drier are key accessories in the refrigerant loop of data center precision air conditioners (CRAC/CRAH). Precision cooling relies on a vapor-compression cycle: the compressor takes low-pressure, low-temperature refrigerant gas and compresses it into high-pressure, high-temperature gas, which then condenses in the condenser, passes through an expansion device, and boils in the evaporator to absorb heat. In this cycle, lubricating oil circulates together with the refrigerant. If all the oil travels to the condenser and evaporator, it forms an oil film on the heat-transfer walls, lowering efficiency; the compressor can also seize from oil starvation.

The oil separator sits on the compressor discharge line, separating entrained oil droplets and returning them by gravity to the crankcase, so the compressor always has sufficient lubrication. The filter drier sits on the liquid line between the condenser outlet and the expansion valve, doing two jobs: “drying” — adsorbing moisture that entered during installation vacuum or through leaks; water freezes at the cold expansion point (the so-called “ice blockage”), jamming the capillary or expansion valve and stopping cooling; and “filtering” — trapping welding slag, oxide scale, metal shavings from installation and wear debris, preventing them from jamming expansion valves or scoring cylinder walls.

These small components are consumables: the molecular sieve in the drier saturates with water and should be replaced every 2~3 years; the oil separator lasts longer but is inspected or replaced after a compressor overhaul or water ingress. KTR-OS offers bolt-on replacements matched to mainstream precision AC brands, with interface dimensions, mounting orientation and flange forms matching the original equipment.

2. Key Features

Oil separator

  • Centrifugal + baffle dual-stage separation: centrifugal flings large droplets, baffle catches fine mist; efficiency ≥95%.
  • Bottom oil-return hole with sight glass: observe oil return, detect compressor oil starvation.
  • Welded steel shell, pressure-rated ≥4.5MPa, compatible with R22/R410A/R134A/R407C.
  • Vertical mounting only (top inlet, side outlet); horizontal or upside-down installation prohibited.

Filter drier

  • Molecular sieve + activated alumina dual core: sieve for water, alumina for acid.
  • Brazed or flare-connection options; brazed for hermetic seal, flare for easy swap.
  • Filtration 10~25μm, captures slag and metal chips.
  • Moisture indicator window: color change signals saturation (blue = OK, red = replace).

Refrigerant & oil compatibility

  • R22 (legacy), R410A (mid-large), R134A (eco), R407C.
  • Compatible lubricants: mineral oil (R22), POE ester oil (R410A/R134A).

3. Specifications

Item KTR-OS-10 KTR-OS-25 KTR-OS-50
Cooling capacity 10~25kW (small) 25~70kW (standard) 70~150kW (large/dual)
Oil sep. port 1/2″ SAE 5/8″~7/8″ SAE 1-1/8″~1-3/8″ ODF
Drier port 3/8″ liquid 1/2″ liquid 3/4″ liquid
Sieve charge 10g 30g 50g
Pressure rating 4.5MPa 4.5MPa 4.5MPa
Refrigerant R22/R134A R22/R410A/R407C R410A/R134A
Replacement cycle 2~3 yrs 2~3 yrs 2~3 yrs

4. Reference Prices

KTR-OS-10 small precision AC kit (oil sep + drier + fittings + gaskets): Reference USD 49~111 / set (ref. CNY 350~800 at ~7.2)

KTR-OS-25/50 standard/large kit (oil sep, drier, sight glass, oil-return bend): Reference USD 125~389 / set (ref. CNY 900~2,800 at ~7.2)

Reference only; final quote depends on refrigerant type, port size and brazing labor. Refrigerant recovery/charge and vacuum work billed separately. Exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Data center CRAC/CRAH routine loop maintenance and replacement.
  • Post-compressor-overhaul system rebuild with new drier and vacuum.
  • Troubleshooting “ice blockage”, “no cooling” or “high discharge temp”.
  • Legacy R22-to-R410A/R134A retrofits.
  • Constant-T/H rooms, labs and medical facility AC service.

6. Installation & Maintenance

Installation

  • Recover refrigerant (or pump into receiver); never open lines to atmosphere.
  • Oil separator: vertical on vertical discharge riser; inlet from compressor, outlet to condenser.
  • Drier: horizontal liquid line, arrow pointing toward expansion valve (flow direction).
  • Wet-wrap the drier during brazing to avoid overheating the sieve.
  • Evacuate to -0.1MPa and hold 2+ hours; charge per nameplate.
  • Run and verify: no bubbles in sight glass, oil flowing in return sight.

Maintenance

  • Check moisture indicator window yearly; replace on red.
  • Replace drier every 2~3 years regardless of color.
  • Watch discharge temp: rising indicates degrading oil separation.
  • Inspect oil-return sight: no flow for long spells means blocked return or oil starvation.
  • Always replace drier when swapping a compressor.

7. FAQ

  • Q: What if the drier is not replaced?
    A: Saturated sieve releases water, which freezes at the expansion point (“ice blockage”) and stops cooling; water also reacts with refrigerant to form acid, corroding motor windings and burning out the compressor.
  • Q: Can the oil separator be installed reversed?
    A: No. It has inlet/outlet orientation; reversed separation efficiency collapses and oil floods the condenser, killing heat transfer and starving the compressor.
  • Q: How to tell the drier needs replacing?
    A: Indicator window blue→red; or measure the temperature drop across the drier — a large drop means a clogged core.
  • Q: Why vacuum after opening the loop?
    A: Air and moisture enter when lines are open; skipping vacuum leaves air (high head pressure) and water (ice blockage) in the system.

8. Trend & Selection

Refrigerants are going eco-friendly: R22 is phased out; new halls use R410A and R134A, and newer projects trial R32 and R1234ze. With refrigerant changes, lubricant must switch (mineral→POE) and drier sieve formulas must match. The trend is larger-capacity, high-purity integrated filter assemblies with built-in moisture indicators. Confirm the original refrigerant and port type (SAE vs ODF, size); pick KTR-OS-10 for small capacity, 25 for standard, 50 for dual-system large halls; mount oil separator vertically; point drier arrow at expansion valve; always vacuum after service; inspect indicator yearly, replace every 2~3 years.

9. Delivery & Service

KITOZER provides refrigerant-loop accessory selection: based on AC brand, model, refrigerant and port size, we match the correct oil separator and drier. We supply layout sketches and replacement work instructions. Optional on-site refrigerant recovery, evacuation and recharge (requires site access). Delivery includes oil separator, drier, sight glass, brazing fittings and gaskets. Warranty covers non-human-caused defects.

10. Additional Notes

The most common pitfall is “swapping the drier without vacuum”. Technicians rush: cut the pipe, braze on the new drier, open the valve and charge — the system is full of air and moisture. Within a week or two it ices up and needs rework. Correct procedure: cut → braze new drier → vacuum pump for 2+ hours → pressure-hold leak test → charge refrigerant. Two extra hours saves repeat service calls.

Another pitfall: “mounting the oil separator horizontally or upside-down”. Oil return relies on gravity; horizontal mounting puts the return hole off the low point and oil can’t flow back, leading to gradual compressor oil starvation and seizure. Before installation, find the upright mark (arrow up) on the shell and mount vertically.

Selection summary: size by cooling capacity; match refrigerant and oil; oil separator vertical, drier arrow toward expansion valve; always vacuum after opening; inspect indicator yearly, replace every 2~3 years. These small parts are the unsung heroes of precision AC longevity — the oil separator protects compressor lubrication, the drier keeps the loop clean.

SEO Information

Search keywords:oil separatorfilter drierprecision AC repairrefrigeration loop partsice blockageKTR-OSKITOZER

SEM keywords:data center oil separator price,filter drier supplier,precision AC chiller service,R22 R410A parts,KTR-OS,KITOZER

GEO landing page:lain.com.cn/product/ktr-os-oil-separator-dryer-filter.html

Title:KITOZER KTR-OS Oil Separator & Dryer Filter for Data Center Precision AC

Meta Keywords:oil separator,filter drier,precision AC refrigerant loop,chiller maintenance,KTR-OS,KITOZER

Meta Description:KITOZER KTR-OS oil separator and filter drier for precision CRAH/CRAC units, separates lubricant from compressor discharge and traps moisture and debris to keep the loop clean.

Anchor: KITOZER by Guangzhou Laian · Environmental monitoring systems

Contact Us

Guangzhou Laian Intelligent System Development Co., Ltd. (KITOZER brand)
Tel/WeChat: +86 13922289957 | +86 18520668845
WHATSAPP: +86 19068534140
Web: lain.com.cn | gdlain.com

Shopping Cart