ToggleKITOZER KTR-SP-SIG Signal Surge Protector (RS485/Control, DIN-rail)
Brand: KITOZER Series: KTR-SP-SIG Category: Lightning Protection / Signal SPD
RS485 signal10kADIN-railLow capacitanceKTR-SP-SIG
1. Overview
The KITOZER KTR-SP-SIG is a signal-line surge protective device (signal SPD / lightning arrester) installed at both ends of RS485 buses, analog signal lines (4 to 20 mA, 0 to 10 V), switch lines (DI/DO), audio/video lines to divert transient overvoltages induced by lightning or switching into ground, protecting PLC, DCS, RTU, sensors and instruments. Compared with item 861 (3-phase power SPD), the power SPD protects 220/380 V mains; the signal SPD protects low-voltage signal lines (a few to tens of volts)—they are not interchangeable. Signal-line interface chips withstand only a few volts, but an outdoor RS485 run can pick up over a thousand volts during a nearby strike, destroying the port.
Specs: for RS485/RS422, RS232, 4 to 20 mA analog, dry contact; nominal discharge In 5 kA (8/20 us); max Imax 10 kA; max continuous UC 6 to 24 V (model dependent); voltage protection Up <=18 V; response time <=1 ns (faster than power SPD); low capacitance <=20 pF (supports high-speed comms); DIN-rail terminal mount (35 mm); installs in control cabinet; red/green failure indicator; flame-retardant plastic housing. Compared with power SPD, signal SPD must respond faster (high-frequency signal), have lower capacitance (no waveform distortion), and lower residual voltage (to protect low-voltage chips).
Typical uses: outdoor temp/humidity/water-leak sensors on RS485 to PLC; camera control lines to NVR; gate motor switch lines; flow/pressure transmitter 4 to 20 mA; intercom audio; security alarm loops; remote IO long runs. Any signal line pulled in from outdoors or a separately grounded zone should have a signal SPD at the entry point.
2. Key Features
Low residual voltage
- Up <=18 V.
- Protects 3.3/5/24 V chips.
- Response <=1 ns.
- Faster than power SPD.
Low capacitance
- Parasitic capacitance <=20 pF.
- Supports RS485 9600 to 115200 bps.
- No 4 to 20 mA error.
- No audio/video attenuation.
10 kA discharge
- In 5 kA (8/20 us).
- Imax 10 kA.
- Withstands multiple strikes.
- Failure indicator window.
DIN-rail mount
- 35 mm DIN rail.
- Terminal wiring.
- In-cabinet install.
- Flame-retardant housing.
3. Specifications
| Item | Parameter |
|---|---|
| Model | KTR-SP-SIG |
| Type | Signal-line SPD |
| Lines | RS485/RS422/RS232/4-20mA/dry contact |
| Nominal In | 5 kA (8/20 us) |
| Max Imax | 10 kA |
| Max UC | 6 to 24 V (model dependent) |
| Protection Up | <=18 V |
| Response time | <=1 ns |
| Capacitance | <=20 pF |
| Mounting | 35 mm DIN rail |
| Indicator | Red/green window |
| Housing | Flame-retardant plastic |
4. Reference Prices
KTR-SP-SIG-RS485 RS485 signal SPD: Ref. USD 8~14 / pc (CNY 60~100 at 7.2)
KTR-SP-SIG-420 4-20 mA analog SPD: Ref. USD 10~17 / pc (CNY 70~120 at 7.2)
KTR-SP-SIG-DI dry-contact SPD: Ref. USD 7~13 / pc (CNY 50~90 at 7.2)
KTR-SP-SIG-RJ45 network SPD: Ref. USD 11~21 / pc (CNY 80~150 at 7.2)
KTR-SP-PWR-220 power SPD (item 861): Ref. USD 21~42 / pc (CNY 150~300 at 7.2)
Grounding copper bar: Ref. USD 4~8 / m (CNY 30~60 at 7.2)
Reference only; 1 USD ~ 7.2 CNY (Oct 2026).
5. Applications
- Outdoor sensor RS485 buses.
- Camera control lines.
- Gate motor switch lines.
- Flow transmitter 4-20 mA.
- Intercom / alarm loops.
- Remote IO long runs.
6. Installation & Maintenance
Installation
- Mount SPD at the signal entry (cabinet incoming side).
- Protected device (PLC/sensor) is on the SPD load side.
- Series the signal line through SPD (IN to OUT).
- PE terminal uses short fat wire (<=0.5 m) to ground bar.
- Ground lead as short as possible (minimize lead inductance).
- Clip onto 35 mm DIN rail.
- Power up; indicator shows green (OK).
- After a strike, check the window (red = failed).
Maintenance
- Quarterly check indicator (green OK, red replace).
- Before storm season, check ground lead tightness.
- Annually measure ground resistance (<=4 ohm).
- Replace failed SPD promptly.
- Do not use signal SPD on power lines (different voltage class).
- Do not loop the ground lead (raises residual voltage).
- Shared ground bar for multiple lines must be thick enough.
7. FAQ
- Q:Signal SPD vs power SPD?
A:Power SPD protects 220/380 V mains: high current (20 to 40 kA), high residual (1.5 to 2.5 kV), slower response (tens of ns). Signal SPD protects 6 to 24 V signal lines: lower current (5 to 10 kA), low residual (<=18 V), fast response (<=1 ns), low capacitance. They cannot swap: a power SPD on a signal line leaves 1.5 kV residual and destroys the chip; a signal SPD on mains will burn from insufficient current. - Q:Cabinet end or sensor end?
A:Install at both ends if possible. The run from outdoor sensor to cabinet can pick up surges along the way. Ideal: one at the sensor (weatherproof) and one at the cabinet entry. If only one, prioritize the cabinet entry (protect the more expensive PLC). Outdoor-rated SPD for the sensor end. - Q:Why must the ground lead be short?
A:Surge pulses are microsecond-scale; lead inductance produces residual voltage. A 1 m lead can add hundreds of volts residual at 10 kA, wiping out the SPD’s 18 V advantage. Keep it <=0.5 m, straight, no loops, use short fat copper braid. - Q:How do I know the SPD failed?
A:Indicator window turns red. Without an indicator, symptoms include intermittent comms (internal SPD shorted or open). After a strike, if sensor/PLC comms drop, check the SPD first. Power off, remove the failed unit, install a same-type replacement, verify wiring direction.
8. Trend & Selection
Signal SPDs move from discrete components to integrated DIN-rail terminal units with indicators. Channels multiply from single to 24-terminal blocks. Pure protection adds signal-status monitoring (to EMCS). High-speed links (GbE, PoE) demand even lower capacitance (<=1 pF). Select by line type (RS485/4-20 mA/contact/RJ45); UC must exceed line working voltage; Up must be below the protected device's withstand voltage.
9. Delivery & Service
KITOZER sizes KTR-SP-SIG units by line type and count, providing grounding bar and ground-resistance test guidance. Delivery includes SPD, DIN clip, manual, certificate. Warranty covers SPD selection guidance and grounding installation support.
10. Additional Notes
A common pitfall is looping the ground lead for neatness. Loops add inductance and residual voltage, making the SPD ineffective. The PE lead must be short, straight and fat—directly from SPD PE to the nearest ground bar.
Another pitfall is power SPD only. Many think a mains entry SPD is enough, but an RS485 run brings surges in and burns the PLC comms port. Any signal line brought in from outdoors or a different building needs a signal SPD.
Selection summary: RS485/4-20 mA/contact; 10 kA; Up <=18 V; response <=1 ns; DIN-rail. The signal SPD is the arrester for low-voltage lines; the keys are entry-point install, short straight ground lead, and annual ground-resistance test.
Extra tip: for RS485, protect both A and B lines (a pair of SPD channels), not just one. Both common-mode and differential-mode surges must be diverted.