KITOZER KTR-SPD-P40 Power Surge Protector (2P 40kA Type 2)

KITOZER KTR-SPD-P40 Power Surge Protector (2P 40kA Type 2)

Brand: KITOZER Series: KTR-SPD-P40 Category: SPD / Power Surge

2PIn 20 kAImax 40 kA275 Vremote contactKTR-SPD-P40

1. Overview

The KITOZER KTR-SPD-P40 is a 2P DIN-rail power surge protective device (SPD) installed after the main breaker in a distribution cabinet. It diverts transient over-voltages from lightning induction and switching operations, protecting downstream UPS, precision air conditioners, servers and network gear. Power SPDs are the second stage (Type 2) of low-voltage distribution lightning protection, and a mandatory item in data centers and low-voltage rooms.

KTR-SPD-P40 uses a metal-oxide varistor (MOV) as the diverting element: nominal discharge current In = 20 kA (8/20 us), maximum discharge current Imax = 40 kA, maximum continuous operating voltage Uc = 275 V AC, voltage protection level Up 1.5 kV. 2P construction (one MOV per L and N), DIN 35 mm rail, modular design (replace a failed module without removing the whole unit). It has a remote-signal contact (dry contact to the EMCS when the module ages or fails) and a visual indicator (green normal, red failed).

Typical uses: room distribution cabinet secondary protection (three-stage: main building cabinet In 100 kA, room cabinet In 20 kA, rack PDU In 10 kA); telecom room distribution boxes; security rack power input; PV AC side; outdoor base-station power cabinets. KTR-SPD-P40 is the standard second-stage configuration.

2. Key Features

MOV discharge

  • Metal-oxide varistor.
  • In = 20 kA (8/20 us).
  • Imax = 40 kA.
  • Up 1.5 kV.

2P construction

  • L+N pole protection.
  • DIN 35 mm rail.
  • Modular replaceable.
  • Uc = 275 V AC.

Status indication

  • Window indicator (green/red).
  • Dry remote contact.
  • Aging alarm.
  • Remote monitoring link.

Safety

  • Internal thermal disconnector.
  • Fails open (no fire).
  • GB 18802.1 compliant.
  • UL94-V0 housing.

3. Specifications

Item Parameter
Model KTR-SPD-P40
SPD type Type 2 (parallel)
Poles 2P (L+N)
Rated voltage Uc 275 V AC
Nominal discharge In 20 kA (8/20 us)
Max discharge Imax 40 kA (8/20 us)
Voltage protection Up 1.5 kV
Response time 25 ns
Remote contact Dry contact (NC/NO selectable)
Status Window (green/red)
Conductor size 2.5 to 25 mm2
Mounting DIN 35 mm rail
Operating temp -40 to +85 C
Flame rating UL94-V0
Dimensions about 36x90x65 mm (2P module)

4. Reference Prices

KTR-SPD-P40 2P 40 kA Type 2: Ref. USD 17~28 / pc (CNY 120~200 at 7.2)

KTR-SPD-P80 4P 80 kA Type 1: Ref. USD 39~63 / pc (CNY 280~450 at 7.2)

KTR-SPD-P20 1P 20 kA rack-end: Ref. USD 8~14 / pc (CNY 60~100 at 7.2)

KTR-SPD-SIG signal SPD (RJ45): Ref. USD 6~11 / pc (CNY 45~80 at 7.2)

KTR-SPD-BNC video signal SPD: Ref. USD 5~8 / pc (CNY 35~60 at 7.2)

SPD backup breaker (16 A C-curve): Ref. USD 3~6 / pc (CNY 25~45 at 7.2)

Reference only; exchange: 1 USD ~ 7.2 CNY (Oct 2026).

5. Applications

  • Room cabinet secondary protection.
  • Telecom room distribution input.
  • Security rack power input.
  • PV AC side protection.
  • Outdoor base-station power cabinet.

6. Installation & Maintenance

Installation

  • Install after the main breaker, before branch breakers.
  • L to phase, N to neutral, PE to ground (ground lead as short as possible, 0.5 m).
  • Clip onto DIN rail; torque terminals to 2.5 N-m.
  • Add a backup breaker (16 A C-curve) upstream to isolate SPD faults.
  • Wire the remote contact to the EMCS (NC: closed normal, open on failure).
  • Ground lead: yellow-green, 6 mm2 or larger, to the cabinet ground bar.
  • Confirm the indicator window shows green after install.
  • Before energizing, check L-N, L-PE, N-PE resistance (no short).

Maintenance

  • Check the window quarterly (green = good).
  • Inspect after thunderstorms (damage may not show red yet).
  • Replace the module immediately when red (hot-swap, no power interruption).
  • Test ground resistance yearly (4 ohm or less).
  • Do not install an RCD upstream (SPD leakage causes nuisance trips).
  • Keep a spare same-model module.

7. FAQ

  • Q:How to size Type 1/2/3 SPDs?
    A:Three-stage coordination: Type 1 (main building cabinet) In 100 kA, 10/350 us waveform, diverts direct-strike current; Type 2 (room cabinet, KTR-SPD-P40) In 20 kA, 8/20 us, limits residual voltage; Type 3 (rack PDU) In 10 kA, fine protection. Keep 10 m cable (or a decoupling inductor) between stages, otherwise the upstream stage wears first. Do not skip Type 2; Type 1 residual voltage is still about 2 kA and kills downstream gear.
  • Q:Does the SPD need a backup breaker?
    A:Yes. After repeated strikes, the MOV may short circuit; a sustained short causes fire. Add a 16 A C-curve MCB upstream; it trips on SPD short. Do not use a fuse (too slow; the SPD already burned). KTR-SPD-P40 recommends a 16 A C-curve breaker.
  • Q:Must I replace the SPD when the window turns red?
    A:Yes. Red means the MOV has aged (leakage current rose after repeated strikes and the internal thermal disconnector opened). The SPD no longer protects, but power continues (no outage), so it often goes unnoticed. The remote contact alarms to the EMCS; without remote contact, do quarterly manual inspection. Replace the module promptly (hot-swap, no outage).
  • Q:What ground resistance is required?
    A:Room grounding 1 ohm (combined), general building 4 ohm. The SPD ground lead should be short (0.5 m) and thick (6 mm2 or more). A long ground lead develops an L di/dt voltage drop during the strike, adding to Up and still killing gear. Do not run a long ground wire to the SPD.

8. Trend & Selection

Power SPDs move from single-stage to coordinated three-stage. MOVs integrate thermal disconnector, remote contact and window indication for remote status monitoring. Combined SPD + MCB units spread in small distribution boxes. Online surge monitoring (real-time leakage, strike count) grows in critical data centers. Type 2 Up drops from 1.5 kV to 1.2 kV for finer protection.

9. Delivery & Service

KITOZER sizes KTR-SPD-P40 by distribution stage and lightning risk, providing three-stage SPD coordination diagrams and ground resistance requirements. Delivery includes SPD, installation manual and certificate. Warranty covers module replacement guidance and remote-contact wiring diagrams.

10. Additional Notes

A common pitfall is bolting the SPD ground to the cabinet shell instead of the ground bar. The shell-to-bar path has rust and bolt contact resistance; the strike cannot discharge. The ground lead must go directly to the copper ground bar, not via the shell.

Another pitfall is not stocking a spare module. When the window turns red and there is no spare on site, the cabinet runs unprotected for days while you procure. Critical rooms keep a same-model module in the cabinet.

Selection summary: 2P; In 20 kA; Imax 40 kA; Uc 275 V; remote contact. The power SPD is the cheapest yet most lifeguarding device in the cabinet; the keys are three-stage coordination, short thick ground leads, backup breaker, and replace when the window goes red.

Additional tip: The SPD is consumable. A nearby direct strike halves its life. High-thunderstorm regions batch-inspect every season. With remote contact to the EMCS, aging alarms in real time without manual rounds.