KITOZER MRI Shielded Room Configuration Quotation List
Table of Contents
Toggle2. Project Requirement Description
Project Requirements: Construct one set of MRI radio-frequency (RF) shielded room system, suitable for 1.5T/3.0T MRI equipment. The system must meet RF shielding requirements, comply with hospital construction specifications and MRI equipment manufacturer technical standards, effectively prevent external RF signal interference affecting imaging quality, and prevent internal MRI RF signals from leaking and interfering with surrounding equipment.
Quantity Requirement: 1 complete set of MRI shielded room system, custom-designed to accommodate different magnetic field strength MRI equipment.
Functional Requirements:
- RF shielding effectiveness ≥ 100dB
- Equipped with shielded door, shielded observation window, power filtering system, ventilation waveguide, and cooling pipe interface
- Interlocking between equipment room and operation room to satisfy medical workflow
- Compliance with hospital infection control and fire protection regulations
Performance Requirements:
- RF attenuation ≥ 100dB within 10MHz to 130MHz frequency band
- Ground insulation resistance ≥ 1000Ω
- Meet MRI equipment manufacturer acceptance standards
3. System Composition Introduction
The MRI Shielded Room System consists of 7 core subsystems:
- Copper RF Shielded Enclosure System (six-sided cuboid structure)
- MRI Dedicated Shielded Door System
- Shielded Observation Window System
- Power & Signal Filtering System
- Ventilation, Air Conditioning & Cooling Pipe Waveguide Interface System
- Grounding & Insulation System
- Interior Finishing & Decoration System
4. Core Product Specifications & Parameters
Core Performance Indicators
| Parameter | Specification |
|---|---|
| RF Shielding Effectiveness | ≥ 100dB (10MHz ~ 130MHz) |
| Enclosure Insulation Resistance | ≥ 1000Ω to ground |
| Grounding Resistance | ≤ 1Ω (single-point independent grounding) |
| Airtightness | Meets constant temperature & humidity air-conditioning requirements |
| Internal Clear Dimensions | Length 7m × Width 6m × Height 3.5m (compatible with mainstream 3.0T MRI equipment) |
| Design Service Life | ≥ 15 years |
Key Component Parameters
- Shielded Enclosure: 2.0mm high-quality copper plate, fully welded structure, continuous electrical conductivity, anti-oxidation surface treatment
- MRI Shielded Door: Manual side-hung type, door opening 1200×2100mm, copper beryllium-copper spring leaf multi-seal, with self-closing and interlocking device
- Shielded Observation Window: 1200×800mm, double-layer laminated conductive glass, light transmittance ≥ 70%, shielding effectiveness ≥ 90dB
- Power Filter: Multi-stage medical-grade filtering structure, leakage current meets medical safety standards, insertion loss ≥ 100dB
- Ventilation Waveguide: Honeycomb copper waveguide, compatible with hospital central air-conditioning system, cut-off frequency lower than MRI operating frequency
5. Core Functions & Features of Products
Core Functions
- RF Shielding Function: Comprehensive isolation from external RF interference, ensuring clear MRI imaging and preventing image artifacts; simultaneously preventing leakage of MRI RF signals to protect surrounding electronic equipment and personnel
- Medical Adaptation Function: Equipped with medical-grade power filtering, shielded observation window, and patient passage, fully compliant with hospital workflow and infection control requirements
- Interface Compatibility Function: Pre-reserved multiple interface waveguides for cooling water pipes, helium gas pipes, signal cables, and air-conditioning ducts, fully compatible with mainstream brand MRI equipment
- Safety Protection Function: Equipped with emergency door release device, access control interlock, and quench alarm interface, compliant with MRI room safety regulations
Product Features
- High Electrical Conductivity: Copper plate enclosure provides excellent conductivity, stable RF shielding performance, suitable for high-field MRI equipment
- Superior Craftsmanship: Copper plate joints use continuous argon arc welding, ground smooth with no protrusions or sharp edges, preventing magnetic field distortion
- Medical-Grade Standards: All materials comply with hospital fire protection, environmental protection, and infection control requirements; odor-free, no hazardous substance emission
- Strong Equipment Compatibility: Compatible with GE, Siemens, Philips and other mainstream brand MRI equipment of various models, satisfying equipment manufacturer acceptance standards
6. Core Advantages of The Solution
- Customized Design: Shielding solutions tailored to MRI equipment model, magnetic field strength, and site dimensions, precisely matching equipment parameter requirements
- Full-Process Turnkey Service: Complete chain of services from on-site survey, solution design, manufacturing, to installation and acceptance; coordinated acceptance with MRI equipment manufacturer
- Confidential Construction: Hospital project information and technical solutions are strictly confidential; construction process complies with hospital management regulations
- Core Components in Stock: Standard specification copper plates, shielded doors, observation windows, and filters are kept in stock to ensure hospital project schedule requirements
7. Manufacturer Strength Introduction
KITOZER (Guangzhou Lai’an Intelligent System Development Co., Ltd.), founded in 2002, is a high-tech enterprise certified with ISO 9001, ISO 14001, and ISO 45001 management systems. The company holds professional qualifications in medical shielding engineering with extensive project experience and in-depth mastery of MRI RF shielding core technology. KITOZER has successfully delivered certified MRI shielded rooms for numerous hospitals and medical examination centers. The company operates its own dedicated copper processing and welding professional team, ensuring fine craftsmanship and stable shielding performance. KITOZER is thoroughly familiar with interface requirements and acceptance standards of various MRI equipment brands and can fully coordinate with equipment installation and commissioning, guaranteeing one-pass project acceptance. As a manufacturer, all products undergo complete quality inspection before shipment.
8. Detailed Quotation Table
| No. | Product Name | Model & Spec | Technical Parameter | Qty | Unit | Unit Price (USD) | Total Price (USD) | Brand | Remark | |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | MRI Shielded Wall Copper Plate | KTZ-HC-Q20 | 2.0mm copper plate, fully welded, anti-oxidation treatment | 91 | ㎡ | 503.13 | 45784.02 | KITOZER | Total four wall areas | |
| 2 | MRI Shielded Ceiling Copper Plate | KTZ-HC-D20 | 2.0mm copper plate, with hoisting reinforcement structure | 42 | ㎡ | 584.58 | 24552.16 | KITOZER | Total ceiling area | |
| 3 | MRI Shielded Floor Copper Plate | KTZ-HC-B20 | 2.0mm copper plate, full welding, moisture-proof insulation base layer | 42 | ㎡ | 577.18 | 24241.53 | KITOZER | Floor shielding layer | |
| 4 | MRI Dedicated Shielded Door | KTZ-PM-H12 | Door opening 1200×2100mm, copper sealing, self-closing with interlock | 1 | Unit | 11543.15 | 11543.15 | KITOZER | Patient/Personnel passage | |
| 5 | Shielded Observation Window | KTZ-CK-H12 | 1200×800mm, double-layer conductive glass, transmittance ≥ 70% | 1 | Set | 4735.83 | 4735.83 | KITOZER | Operation room observation | |
| 6 | Medical-Grade Three-Phase Filter | KTZ-LB-HS63 | Three-phase 380V/63A, medical-grade low leakage, loss ≥ 100dB | 1 | Unit | 2663.91 | 2663.91 | KITOZER | Main power filtering | |
| 7 | Single-Phase Auxiliary Filter | KTZ-LB-HD16 | Single-phase 220V/16A, medical-grade, leakage current ≤ 0.5mA | 2 | Unit | 562.57 | 1125.13 | KITOZER | Lighting auxiliary circuit | |
| 8 | Signal Filter Interface Group | KTZ-LB-XHC | MRI signal, control signal filtering, fiber-optic waveguide | 1 | Set | 1775.94 | 1775.94 | KITOZER | Equipment signal interface | |
| 9 | Copper Honeycomb Ventilation Waveguide | KTZ-BD-H600 | 600×600mm, copper honeycomb, cut-off frequency adapted | 4 | Pcs | 1258.07 | 5032.26 | KITOZER | Air-conditioning ventilation interface | |
| 10 | Cooling Pipe Waveguide Group | KTZ-BD-LQ | Non-metallic waveguide tube, adapted for cooling water pipe & helium gas pipe | 1 | Set | 1006.45 | 1006.45 | KITOZER | Liquid-cooled pipeline interface | |
| 11 | Insulation Base Layer System | KTZ-JY-HC | Floor insulation layer, insulation to ground ≥ 1000Ω | 42 | ㎡ | 47.36 | 1988.99 | KITOZER | Enclosure-to-ground insulation | |
| 12 | Independent Grounding System | KTZ-JD-HC | Independent grounding electrode, copper busbar, grounding cable | 1 | Set | 2663.91 | 2663.91 | KITOZER | Single-point independent grounding | |
| 13 | Interior Decoration System | KTZ-ZS-HC | Medical clean wall panels, PVC flooring, compliant with infection control requirements | 133 | ㎡ | 71.04 | 9448.87 | KITOZER | Overall interior decoration | |
| 14 | Medical Lighting System | KTZ-ZM-HC | Medical LED flat panel lights, flicker-free, shielded installation | 6 | Set | 266.39 | 1598.34 | KITOZER | Interior lighting | |
| 15 | Installation Auxiliary Material Kit | KTZ-FC-HC | Welding materials, conductive gaskets, sealing adhesive, fasteners | 1 | Batch | 3700.02 | 3700.02 | KITOZER | Construction supporting materials | |
| 16 | On-site Installation & Construction Fee | KTZ-AZ-HC | Copper plate welding, system installation, commissioning | 1 | Item | 17759.36 | 17759.36 | KITOZER | Professional team construction | |
| 17 | Shielding Effectiveness Testing Fee | KTZ-JC-HC | RF shielding effectiveness test, coordinated with equipment manufacturer acceptance | 1 | Item | 6660.05 | 6660.05 | KITOZER | Special acceptance testing | |
| — | — | — | — | — | — | — | — | — | — | |
| Total | 171,282.97 | KITOZER | — |
Total Quotation Price: USD 171,282.97
9. Quotation Terms & Conditions
1. Price Terms: All prices quoted in USD. Prices are on EXW (Ex-Works) Guangzhou, China basis, unless otherwise negotiated. Price includes installation and acceptance coordination services.
2. Taxation: The above prices do not include tax and freight. Value-added tax (VAT) special invoice: additional 10%; VAT general invoice: additional 3%.
3. Freight: Shipping arranged via logistics with freight collect (payable upon delivery), unless otherwise agreed.
4. Payment Terms: 30% deposit upon order confirmation, 70% balance before shipment (negotiable).
5. Lead Time: 15-30 working days depending on configuration and order quantity.
6. Validity: This quotation is valid for 30 days from the date of issue.
7. Packing: Export-standard packing included; special packing requirements quoted separately.
10. After-sales Service Description
- Warranty: 12-24 months warranty for all products (specific warranty period varies by product category), covering manufacturing defects and workmanship issues.
- Lifetime Technical Support: Free lifetime technical consultation and application support for all KITOZER products.
- Spare Parts Availability: Genuine spare parts available for the entire product lifecycle; standard components maintained in stock for rapid dispatch.
- Field Service: Remote troubleshooting available via phone, email, or video conference; on-site diagnostic and repair services available upon request with rapid response time.
- Periodic Inspection: Optional annual shielding effectiveness inspection and maintenance service packages available.
11. Contact & Order Information
- Order Channel: Place orders via the official website gdlain.com or contact the KITOZER sales team directly.
- Response Commitment: All inquiries will receive a response within 24 hours.
- Manufacturer: Guangzhou Lai’an Intelligent System Development Co., Ltd. / Guangdong Lai’an Intelligent Equipment Room Equipment Co., Ltd.
- Brand: KITOZER
- Contact: Mr. Zhou
- Tel/WeChat: +86 13538869979
- Address: Chaotian Park, Zhongrun Industrial Park, No.5 Huashan Road, Shilou Town, Panyu District, Guangzhou, China
- Customization: Please provide your MRI equipment model, field strength, site dimensions, and specific requirements for a tailored quotation.
12. SEO Keywords & Tags
MRI shielded room, MRI RF shielded room, shielding MRI room, 1.5T/3.0T MRI shielding, hospital MRI shielding room price, KITOZER MRI shielding quotation, MRI RF shielding room manufacturer, hospital nuclear magnetic shielding room construction cost, 3.0T MRI shielded room custom, MRI shielded door, RF shielding effectiveness 100dB, MRI room grounding system, medical RF shielding project, KITOZER quotation, MRI shielded room price list, hospital shielded room factory price, wholesale MRI shielding quotation, MRI shielded room supplier, MRI shielded chamber, RF shielded enclosure for MRI, nuclear magnetic resonance shielding engineering