KITOZER STS: 1600A Static Transfer Switch For Data Center

Product Overview

The KITOZER 1600A static transfer switch is a tier-class power distribution appliance designed for large data centers that require two independent utility incomers feeding a common critical bus, without the milliseconds of interruption that mechanical transfer equipment imposes. Built with heavy forced-air cooled SCR stacks per phase and a redundant, dual-CPU controller, the unit performs break-before-make transfer in under 4ms at full 1600A rating, ensuring that upstream UPS systems and IT loads never see a source break. The controller samples both sources 4000 times per second, applies programmable voltage and frequency windows, and can be configured to prefer source A, source B, or to automatically re-transfer after the preferred source returns for a configurable stable period. The cabinet integrates a fully rated maintenance bypass breaker, a sequence-of-event recorder with time-stamped transfer logs, and a graphical touchscreen HMI that shows per-source voltage, per-phase current, energy, harmonics, and a waveform snapshot of the most recent transfer.

Technical Specifications

Rating: 1600A continuous at 400V three phase plus neutral, 50 or 60Hz. Transfer: SCR static per pole, break-before-make, typical 4ms, maximum 8ms; synchronized transfer mode optional for motor and transformer loads. Source monitoring: three phase RMS voltage, current, frequency, unbalance, phase rotation, power factor, THD on both feeds. Voltage window programmable 320V to 460V, frequency window 47Hz to 63Hz. Cooling: redundant hot-swap forced air fans with temperature control. HMI: 7 inch color touchscreen, event log with time stamping, waveform capture. Communication: dual Ethernet Modbus TCP, optional SNMP v3, BACnet IP, Web HMI, email and SNMP trap alarms. Protection: fast semiconductor fuses per pole, SCR over temperature, over current, source reverse phase, earth leakage option. Mechanical: floor standing IP32 cabinet, busbar top or bottom entry, operating 0 to 40 degrees C. Standards: CE, IEC 60947, 5 year warranty.

Application Scenarios

The 1600A STS is sized for multi-megawatt data halls, carrier-neutral colocation facilities, and large enterprise data centers where each UPS system is fed from a switchboard that must itself be dual sourced. It sits between the two utility incomers and the critical bus feeding UPS input cabinets. It is also suitable for large semiconductor fabs, glass plants, and pulp and paper lines where a half-cycle outage ruins a multi-batch process. In mission-critical healthcare, it can feed the emergency bus of a large hospital complex. For offshore oil and gas platforms, it offers fast source selection between shore cable, platform generator, and emergency generator without the interruption that would trip controls. In commercial high-rise main distribution, it provides seamless selection between two utility feeds for life safety and vertical transportation loads.

Key Advantages

The defining advantage is sub-8ms transfer at 1600A, which means upstream UPS batteries are barely touched and IT loads do not even notice the event. Redundant dual-CPU control means a single controller fault does not cause a transfer or a failure; the standby CPU takes over transparently. Hot-swap fans allow cooling service without opening the SCR compartment. Embedded power quality and waveform capture give engineers forensic data after any event, which is essential for root-cause analysis in tier-certified facilities. The maintenance bypass is fully rated so routine servicing is live work. Open protocols Modbus TCP, SNMP, and BACnet integrate directly into DCIM, BMS, and enterprise alarm platforms without custom gateways. Finally, the unit is factory tested under full load before shipment, with a test report supplied, reducing commissioning risk on site.

Installation and Maintenance Recommendations

Mount on a rigid concrete plinth with cable entry top or bottom per design, maintain minimum 1 meter clearance front and 600mm side clearance. Verify upstream protection coordination with the factory, because the STS fuses must coordinate with main incomer breakers. On site, calibrate voltage and frequency windows, set preferred source and re-transfer delay, and force a transfer on each source under real load to confirm behavior. Verify the bypass interlock mechanically prevents paralleling the two sources. Maintenance program: torque power terminals annually, inspect and replace air filters quarterly or per site dust loading, read event logs monthly, trend power quality monthly, and exercise bypass annually. Keep spare SCR trigger boards, fuses, and a fan module on site. Because this is a tier facility asset, log every transfer in the site management system and review waveform snapshots with the UPS team to ensure the two systems act coherently during source events.

Ordering Information

The 1600A STS is offered in floor standing cabinets with top or bottom busbar entry, and the synchronized transfer mode is recommended whenever motor or transformer loads share the bus. The standard configuration includes dual Ethernet Modbus TCP, a 7 inch touchscreen HMI, and a fully rated maintenance bypass breaker. Optional add-ons include SNMP v3 for DCIM integration, BACnet IP for BMS, email and SNMP trap alarm forwarding, and a remote HMI panel for the NOC wall. The cabinet can be supplied with IP32 or IP42 rating depending on the switchroom environment, and busbar stubs can be prefabricated to site drawings. Lead time is eight to twelve weeks for standard configurations, and factory acceptance testing under full load is offered with a supplied report.

Price

From $42,800 per piece. Contact the factory for full-load test report, custom busbar entry, and SNMP integration. Guangzhou Laian Intelligent System Development Co., Ltd. | Tel/WeChat: +86 13922289957 / +86 18520668845 | WhatsApp: +86 19068534140 | www.gdlain.com