A telecom power distribution unit (PDU) takes -48 V DC from the rectifier and battery bus and distributes it to individual telecom loads through protected, metered branches — the last disciplined link between the power plant and the equipment it feeds. This page answers the questions network engineers and site managers ask when specifying, upgrading or troubleshooting DC distribution at base stations, exchanges and data centers.
Guangzhou Lain Intelligent System Development Co., Ltd. manufactures telecom PDUs and DC power distribution systems with branch metering and monitoring. The answers below reflect our standard product range and engineering practice.

2. Function and Architecture
2.1 What does a telecom power distribution unit do?
It distributes -48 V DC from the rectifier/battery bus to individual telecom loads through protected branches, and reports branch current, voltage and trip status to the site monitoring system. Each load gets its own breaker or fuse, so a fault on one branch is isolated without taking down the rest of the site — and the monitoring system sees which branch tripped, when and why.
2.2 What is the difference between PDU and PDB?
Both terms are used for DC distribution panels (power distribution unit/board). PDU often refers to rack or cabinet-level distribution; PDB to the larger room-level panel. Functionally they are the same family and can be built to either size — a rack PDU feeds a cabinet’s loads, while a room-level PDB feeds multiple racks, each of which may carry its own mini-PDU.

3. Ratings and Outputs
3.1 Which output currents are available?
Standard branches cover 10 A, 16 A, 32 A, 63 A and 100 A using pluggable DC MCBs or fuse carriers. Total panel ratings range from 100 A to 630 A (larger on request). Branches are configured to match the actual load list, with spare ways reserved for growth — so the panel you install today still fits the site next year.
3.2 Can the panel be monitored remotely?
Yes. With the smart version, each branch is metered and data is sent via RS485/Modbus or dry-contact alarms to the site controller, so the NOC sees branch trips and load balance in real time. Voltage, total current, per-branch current, breaker status and alarm events are all available on the monitoring platform.

4. Protection and Battery Life
4.1 Why is low-voltage disconnect needed?
LVD automatically disconnects non-critical loads when battery voltage falls (e.g. below 43.2 V for a 48V system), protecting the battery from deep discharge and keeping critical transmission loads alive longer during long outages. Without LVD, the whole site drains the battery to the point of cell damage — and the load that matters most dies with the load that doesn’t.
4.2 How are branches protected?
Each branch carries a DC-rated MCB or fuse sized to the load and cable; optional surge protection guards the distribution from lightning-induced transients on incoming feeders. Protection coordination between the branch device, the feeder and the rectifier output is designed so the smallest device nearest the fault clears first.

5. AC Distribution and Standards
5.1 Do you make AC distribution too?
Yes. We also supply AC distribution boxes for mains input, air conditioners and sockets, and combined AC/DC panels where space is limited — a single enclosure with both AC and DC sections, each with its own protection and metering, is a common way to clean up crowded telecom rooms.
5.2 What standards do the panels comply with?
Design and testing follow IEC/GB requirements for DC equipment, including clearance/creepage distances, temperature rise limits and surge protection, with type-test documentation available on request. Material certificates and test records accompany every panel.

6. Delivery and Support
6.1 How long is delivery?
Standard panels ship in 10–15 days; smart panels with branch metering in 15–20 days after drawing approval. Custom ratings and layouts extend the schedule only by the drawing approval cycle, and urgent spares are handled on request.
6.2 What documentation comes with a panel?
Drawings (front view, schematic and wiring), test certificates, spare lists and an installation guide. For monitored panels we also provide the Modbus register map so your NMS/EMS can integrate the data without reverse engineering.

7. Frequently Asked Questions — Quick Reference
Telecom PDU FAQ
1. What does a telecom power distribution unit do?
It distributes -48V DC from the rectifier/battery bus to individual telecom loads through protected branches, and reports branch current, voltage and trip status to the site monitoring system.
2. What is the difference between PDU and PDB?
PDU often refers to rack or cabinet-level distribution; PDB to the larger room-level panel. Functionally the same family, built to either size.
3. Which output currents are available?
Standard branches cover 10 A, 16 A, 32 A, 63 A and 100 A using pluggable DC MCBs or fuse carriers; total panel ratings range from 100 A to 630 A (larger on request).
4. Can the panel be monitored remotely?
Yes — the smart version meters each branch and reports via RS485/Modbus or dry contacts, so the NOC sees branch trips and load balance in real time.
5. Why is low-voltage disconnect needed?
LVD disconnects non-critical loads when battery voltage falls (e.g. below 43.2 V for 48V systems), protecting the battery from deep discharge and keeping critical loads alive longer.
6. Do you make AC distribution too?
Yes — AC distribution boxes for mains, air conditioners and sockets, plus combined AC/DC panels where space is limited.
7. What standards do the panels comply with?
IEC/GB requirements for DC equipment including clearance/creepage, temperature rise and surge protection, with type-test documentation available.
8. How long is delivery?
Standard panels ship in 10–15 days; smart panels with branch metering in 15–20 days after drawing approval.
9. Can branches be configured to my load list?
Yes — branch ratings and quantities are configured per load list with spare ways reserved for growth.
10. What documentation comes with a panel?
Drawings, test certificates, spare lists, installation guide and (for smart panels) the Modbus register map for NMS/EMS integration.
8. Related Solutions
- Telecom Power Distribution Unit (PDU): Complete Guide
- DC Distribution Cabinet
- LiFePO4 Batteries for Base Stations
- LiFePO4 Batteries for UPS
- General Outdoor Cabinets
About Guangzhou Lain Intelligent System Development Co., Ltd.
Guangzhou Lain Intelligent System Development Co., Ltd. manufactures telecom power distribution units, DC panels and monitored distribution systems for base stations, exchanges and data centers worldwide. From single rooms to enterprise facilities, KITOZER provides design, manufacturing, integration, testing and after-sales service under one roof and exports worldwide.
Contact us for a free technical consultation:
- Company: Guangzhou Lain Intelligent System Development Co., Ltd.
- Address: 1st Floor, Building A, Chaotian Industrial Park, Zhongrun Industrial Park, Shilou Town, Panyu District, Guangzhou, Guangdong, China
- Tel/WeChat: +86 135-0923-8849 | +86 135-0923-8849
- WhatsApp: +86 135-0923-8849
- Email: zl19068534140@gmail.com
- Website: www.gdlain.com | Request a Quote
Typical response time: within one business day. Project references, drawings and samples are available on request.